Tender For 08-Fire Fighting Network In - Construction Work Of District Hospital At Balotra - Supplying, Installation, Testing & Commissioning ofElectrical Driven fire fighting duty pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given asA, B, C, D, E, F, G and H. 2 (A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head 3 (B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal 4 (C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head 5 (D) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed 2900 / 1500 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect . 6 ( E)Common bed plate fabricated frommild steel channel for installation of pump and Motor including anti vibration pads. 7 (F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works inPhysical presence of Department’s representatives. 8 (G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM 9 (H)Suitable size Reinforced cementconcrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge. 10 2280 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage, 2900 RPM 11 Supplying, Installation, Testing & Commissioning ofDiesel Engine Driven fire fighting duty pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given asA, B, C, D, E, F, G and H. 12 (A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head 13 (B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal 14 (C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head 15 (D) Heat Exchanger cooled Diesel Engineas per NFPA 20 developing suitable BHP for the below mentioned dischargeat 1500 / 1800 RPM, flexible coupling and coupling guard with the Pump, common bed plate for mounting of the Engine and Pump,Antivibration damping arrangement by cushy foot, Diesel Engine starting Panel for starting of the engine automatically if the Normal electrical supply fails with a unit of battery bank of 12/24v,180 Ah, Lead Acid Battery with Boost / Trickle charger as required for operation of Diesel engine, Exhaust Pipe of suitable diameter upto 10 M length (with LRB insulation & Alum. Cladding), with muffler, Diesel tank of 300 Lts capacity (made out from 2 mm thick MS sheet with filling Cap) with drain cock, Diesel level Indicator, Suitable MS angle iron stand for placing tank, first Filling of Diesel tank. 16 (E) Diesel Engine Control comprising Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication, Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter, All standard relays and accessories for automatic operation of diesel engine System Controller in Existing Fire Fighting Control panel 17 (F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives. 18 (G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM 19 (H) Pump to be placed on Suitable size Existing Reinforced cementconcrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge. 20 2280 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage, 1800 / 2300 RPM 21 Supplying, Installation, Testing & Commissioning ofElectrical Driven fire fighting duty Jockey pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEMsuitable for automatic operation and consisting of following details given asA, B, C, D, E,F and G 22 (A) Horizontal End suction Single / Multi Stage Centrifugal Back pull type pump complete for delivery of below mentioned discharge and Head 23 (B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal 24 (C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 2900 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect . 25 (D)Common bed plate fabricated frommild steel channel for installation of pump and Motor including anti vibration pads. 26 (E) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Virtual / Physical presence of Department’s representatives. 27 (F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM 28 (G)Suitable size Reinforced cementconcrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ) All as per pre approved by Engineer in charge. 180 LPM suitable for 70 Mtr Single Stage 29 Providing & fixing Stainless Steel pressure gauge with dial of 150 mm dia size and range 0 to 20 kg/sq.cmwith 3 / 8 BSP bottom entry , Ball valve , SS Syphon tube all fittings etc, dulycalibrated before installation in MKS and FPS units, Accuracy Level +/- 1% including Making Drilling in Existing MS PipeEtc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 30 SITC of pressure switches ofpressure range 3 to 15 Bar for Main, Jockey, Terrace pumpandDiesel pumps, Etc. as Required ( Control Cable from Pressure switch to Panel to be Paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 31 SITC of UL listed and FM Approved Polyethelene vane type water flow switch with actuation & delay mechanism for sensitivity in the range of 4 to 10 GPM and suitable for installation in following sizes of Sprinkler pipe for a Staticpressure rating up to 250 PSIin cluding making connections, making hole in pipe for inserting the vane etc. as required. All as per pre approved by Engineer in charge. 32 80 mm Dia. 33 100 mm Dia. 34 150 mm Dia. 35 Providing & fixing pressure transducer in M.S. Pipe line (pressure range 0 to 10 kg/cm2) suitable for 12 volts/24 volt DC. Including connection etc. as required. ( Control Cable from Pressure Transducer to Panel to be Paid Extra ). All as per pre approved by Engineer in charge. 36 Supplying and fixing cylindrical air vessel of continuous welded construction for pump room made of 450 mm dia,fabricated out of 10 mm thick dished ends and 8 mm thick MS sheet, 2000 mm in height withflanged connection,Provision for25 mm dia drain valve,air release valve,safety valve pressure gauge as required accessories and painting with two coats of Red Oxide and two coat of post office red enamel paint including The tank shall be installed on suitable vertical legs. The legs shall be provided with M.S. Angle of size 75 mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement concrete foundation. as required. ( Air Release valve, Drain valve, PRV, Pressure Gauge shall be Paid Extra ). All as per pre approved by Engineer in charge. 37 Providingandconstructingmasonrychamber 90 x90x100cms inside withbrick work in cement mortar 1:5 (1cement : 5fine sand) for water meter ,M.S. cover (6mmthick sheet with locking arrangement, 600 x600 with M.S. frame etc. all epoxy coated and R.C.C. top slab 1:2:4 mix(1 Cement : 2 coarsesand : 4 graded stone aggregate 20mm nominalsize) including necessary excavation, back fillingfoundation concrete 1:5:10 mix (1 cement : 5 fine sand and10 graded stone aggregate 20mmnominal size) leaving a pocket of 30x30 cmwith out concrete and filled with pebbles andinside plastering withcement mortar 1:3(1 cement : 3 coarse sand) 12 mm thick finishedwith a floating coat of neat cement and outside plaster finished rough complete. All as per pre approved by Engineer in charge. 38 SITC of installation control valve of cast iron body and brass/bronze working parts comprising of water motor alarm, bronze seat clapper, and clapper arm, hydraulically driven mechanical gong bell to sound continous alarm when the wet riser/Sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following sizes.All as per pre approved by Engineer in charge. 150 mm 39 SITC ofDewatering Submersible Motor Pump set, motor should be IE2 class as per IEC 60034-2-1: 2007, IEC 60034-30: 2008,& IS12615:2011. with SS Impellor, body, shaft, mechanical seal etc. as required. Pump shall have following HP Rating, phase, Head, minimum Discharge respectively complete in all respect. OEM shall have submitNABL / CPRI / ERDA accrediatedlab type test certificate before execution. All as per pre approved by Engineer in charge. 2.0 HP, 3-Ø, (5 - 18)Mtr, (480 - 66) LPM 40 SITC of ContactorOEM Fabricated DOL/Star-Delta Starter panel with switchgear selection as per Type-2 Cordinatiom Chart andmade out from 1.6 mm thick powder coated CRCA sheet, enclosure comprising of over load protection relay, short circuit & single phasing protection, Illuminated ON / OFFpush buttons,ammeter, voltmeter, indicating lamps etc.suitable for following rating motors complete in all respect. All as per pre approved by Engineer in charge. For Three phase Submersible / Mono block pumpUpto 3.0 HP ( DOL starter ) 41 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have its own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure A attached with this BSR 150.0 Sq.mm (ARM) 3.5 core 42 16.0 Sq. mm (ARM) 3 core 43 6.0 Sq.mm(ARM) 3 core 44 Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. 3 x 16.0 sq.mm 45 3.5 x 150.0 sq.mm 46 Supplying and makingend termination with heavy aluminiumlugs ( Pin / ring type )confirming to IS 8309 -1993 & IS 8337-1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in charge. 6.0 Sq.mm 47 16.0 Sq.mm 48 150.0 Sq.mm 49 Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS C class (Heavy) pipes conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applicationsincluding cutting, screwing, welding etc. & forged steel fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts including cutting hole and chase in brick or RCC walls/ slab and making good the same. complete with painting of one coats of Red Oxide and two or more coats of synthetic enamel paint of requiredshade complete as required. (Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.). All as per pre approved by Engineer in charge. 25 mm dia 50 32 mm dia 51 40mm dia 52 50mm dia 53 65 mm dia 54 80 mm dia 55 100 mm dia 56 150 mm dia 57 200 mm dia, 6.0 mm thick 58 Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS C class (Heavy) pipe conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications in Existing trench with cement concrete block as supportsincluding cutting,welding etc & forged steel fittings like elbows, tees,tapers, reducer with cleaning,wrapping and coating of the pipe with 4 mm thick tar based polymaric corrosion protection tape including applying uniform coat of cold pipekot primer as per IS; 10221 for protection against corrosion complete in all respect. ( Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs. & Excavation of Trench and refilling of trench to be paid extra). All as per pre approved by Engineer in charge. 80 mm dia 59 150 mm dia 60 Supplying and fixing cylindrical air vessel of continuous welded constructionfixed at riser top made of 250 mm dia, fabricated out of 8 mm thick MS sheet, 1200 mm in height withflanged connection, Provision for25 mm dia drain valve,air release valve,safety valve pressure gauge as required accessories and painting with two coats of Red Oxide and two coat of post office red enamel paint including The tank shall be installed on suitable vertical legs. The legs shall be provided with M.S. Angle of size 75 mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement concrete foundation. as required. ( Air Release valve, Drain valve, PRV, Pressure Gauge shall be Paid Extra ). All as per pre approved by Engineer in charge. 61 Supplying and Fixing of PN 16 Flanged Y strainer fabricated out of cast iron body, SS 304 strainer with perforated screen with 3 mm. dia holesin existing MS / GI pipe complete with 2 no. Matching Flanges (Minimum 16 mm thick),nuts, bolts, washers, gaskets etc as required of following sizes. All as per pre approved by Engineer in charge. 200 mm dia 62 Supplying and Fixing of PN 16 Flanged sluice valve with non rising spindle, bronze /gun metal seat confirming to IS:14846 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following sizes. All as per pre approved by Engineer in charge. 150 mm dia 63 Supplying and Fixing of PN 16 Cast Iron Dual Plate Wafer Type Check Valve / Non return valve with SS / Bronze flap complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following sizes. All as per pre approved by Engineer in charge. 64 80 mm dia 65 100 mm dia 66 150 mmdia 67 200 mm dia 68 Supplying and Fixing of PN 1.6Butterfly Valve (Wafer Type) with S.G Iron Disc and confirming to IS:13095 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 69 80 mm dia 70 100mmdia 71 150mm dia 72 200mm dia Gear Operated 73 SITC of UL listed / FM Approved Brass Test and drain valve assembly for sprinkler system comprising of 3-position ( off, test and Drain ) ball valves with drain orifice having K-factor 5.6 and maximum working pressure 300 PSI and Inbuilt sight glass etc. as required of following size. All as per pre approved by Engineer in charge. 74 25 mm Dia. 75 50 mm Dia. 76 Supplying and fixing of SS 304 Single / Double headed oblique pattern hydrant landing valve (internal/external) with 75 / 100 mm dia flanged inlet & 63 mm dia instantaneous type female outlet coupling with cast iron wheel complete with ABS cap and chain and all accessories as per IS:5290-93 (Type-A) in cluding matching flange (14 mm thick),nuts, bolts, washers, gaskets,etc as required. All as per pre approved by Engineer in charge. 77 Single Headed with 75 mm Dia. Flanged Inlet 78 Supplying and fixing orifice plate made of 6 mm thick stainless steel with orifice of required size in between flange & landing valve of external and internal hydrant to reduce pressure to working pressure of 3.5 kg/cm2 complete with rubber gasket, GI bolts, nuts, washers etc. as required. All as per pre approved by Engineer in charge. 79 Supplying and fixing of flexible hose made with 100% polyester, black EPDM internal rubber lining with External coat of synthetic elastomer (IS:636, type-A)63 mm dia, 15 mtr. Long RRL hose pipe with instanteneous type 63 mm dia SS-304male and female couplings(IS:903) duly bound and riveted to hose pipes with copper rivets and SS wire etc. as required.Appropriate Test Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. 80 Supplying & fixing SS-304 Short Branch Pipeconforming to IS: 903:93 fitted with 20mm (nominal internal diameter)bore nozzle, for projecting water in form of solid jet. The Branch shall have 63mm Male Instantaneous Inlet, suitable for use with 63 mm size Fire fighting hoses. H.P. tested to 21 kgf/cm² for 2.5 minutes. All as per pre approved by Engineer in charge. 81 Supplying and fixing first -Aid Fire hose reel Drum wall mounted swinging type with MS construction powder painted in post office Red, conforming to IS 884-1985 with upto date amendments, complete with the following as required.(A) Thermoplastic / Rubber Hose(B)20 mmdia UL, FM Bronze / SS nozzle with 5mm orifice (C)Drum and brackets for fixing the equipments on wall.(D) Connections from riser with 20/25 mm dia Brass/GM gate valves with screwed end and conforming to IS:778 Class-1through Forged steel Screwed Union & M.S. pipe. Etc. as required. All as per pre approved by Engineer in charge. 82 With 30 m x 20 mm High Pressure Braided Rubber Hose as per IS:5132 - 1969and Bursting pressure 42 Kg/sqcm 83 Supplying and fixing Inlet Breeching Connection of CI body with Gun Metal male instantaneous inlet couplings with Inbuilt NRV, Drainage Connection with 50 mm Brass gate valvecomplete with PVC blank cap and chain as required for 150mm dia Outlet with 1 no. Matching Flange (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following Ways. All as per pre approved by Engineer in charge. 84 4 Way 85 Providing and fixing of 100 mm Dia. Flanged Gun Metal Fire brigade Suction hose coupling (draw out connection)for female coupling as per IS:902-1974 complete with Matching Flange (Minimum 14 mm thick), nuts, bolts, washers, gaskets,etc as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 86 Supplying and fixing of 750 mm x 600 mm x 250 mm Outdoor application Fire Hose Cabinet made of 1.6 mm thick MS sheetDuly powder coated in red color externally and white internally with 6 mm thick glazeddoors with Expanded Metal 2 mm thick Jali including necessary locking arrangement suitable to accommodate 2 Nos 15 Mtr. Long RRL Hose and 1 No. branch pipe on Existing Wall / Angle Iron Frame as required. (Cost of MS structure for mounting Frame is to be Paid Extra) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 87 Supplying and fixing of 1000 mm x 600 mm x 500 mm Outdoor application Fire Hose Cabinet made of 1.6 mm thick MS sheetDuly powder coated in red color externally and white internally with 6 mm thick glazeddoors with Expanded Metal 2 mm thick Jali including necessary locking arrangement suitable to accommodate External hydrant with butterfly valve, 2 Nos 15 Mtr. Long RRL Hose and 1 No. branch pipe on Existing Wall / Angle Iron Frame as required. (Cost of MS structure for mounting Frame is to be Paid Extra). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 88 Providing and Fixing of 15 mm dia Bronze quartzoid bulb type sprinkler headswith Maximum working pressure 11.6 Kg / Sqcm and suitable for 68 degree centigrade rating standard response (UL Listed) chrome plated complete in all respect of the following type. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 89 Pendant/ Upright type 90 Extended Throw Sidewall type . 91 Providing & fixing of UL listed 1.5 mm thick chrome plated Dual type MS Escutcheon platesfixed at junction of Sprinkler piping with the false ceiling. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 92 Supply & Fixing of Fire Mans Axe with carbon steel head & rubber moulde handel usable upto 20 KV and confirming to IS :926 with length approx 0.4 M & weight 3.0 Kg. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 93 Providing & fixingsprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. All as per pre approved by Engineer in charge. 94 1000 mm Long 95 Supply & Fixing of Water + AFFF 6%Mechanical Foam typeFire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 25 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. 96 Capacity - 9 Ltrs. 97 Supply & Fixing of CO2 type Fire Extinguisher conforming to IS:15683:2018, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.0 Mtr. Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability,including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. 98 Capacity 4.5 Kg. 99 Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC typeFire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. 100 4 kg 101 SITC of UL 10th edition / EN54 / VDS certifiedAutomatic Floating Sensitivity type Analog addressable Multi criteria (two optical/Smoke sensor to reduce false alarm) detector with mounting base & LED etc. as required. All as per pre approved by Engineer in charge. 102 SITC of UL 10th edition / EN54 / VDS certified Rate of Rise Heat Detectors (Thermal Detectors):GRADE-I Analouge Addressable type Heat Detectors with solid state design with sensing element combination of fixed type and rate of rise of temperaturemounting base & LED etc. as required. All as per pre approved by Engineer in charge. 103 SITC of UL 10th edition / EN54 / VDS certified Addessable Manual Call point (MCP) with LED/ FIRE Indication Etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . All as per pre approved by Engineer in charge. 104 SITC of Response Indicatorfor indicating the activation of the Remotely located Detectorfor Addressable type Detectors Etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 105 SITC of UL 10th edition / EN54 / VDS certified Addressable type fault isolator with base for isolating shorted, dewired and loose circuits between two successive fault, isolators with automatic resetting arrangementetc. as required. All as per pre approved by Engineer in charge. 106 SITC of UL 10th edition / EN54 / VDS certified Addressable sounder with strobe light,Loop Powered / Direct powered from FACP with sound level 90 dB and programmablefrom the panel etc. as required. All as per pre approved by Engineer in charge. 107 SITC of UL 10th edition / EN54 / VDS certified Addressable control (input/output) modules/ Relay Module for shutting down lifts, Hooters, AHUs, Acknoledgement of Sprinkler system with potential free contact monitoring Etc. as Required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 108 SITC of UL 10th edition / EN54 / VDS certified Microprocessor based inteligent, Analogue addressable,modular, expandable networkableloop Fire Alarm Control Panel with each loop capacity of min 125 detectors per loop with total of 125 detectors & devices with Loop length up to 1 KM as per NFPA 72 approval. The Panel shall be able to give pin point location of addressable units via the address code for each unit. The Panel shall also be able to automatically switch off all control switches when-ever any Alarm is triggered. . The panel shall have 230 + 5 % volts power supply, Automatic battery charger 24V, sealed lead acid maintanence free battries sufficient for 24 hours normal working and then be capable of operating the system for 30 minutes during emergency condtion. Loop interface cards, communication module,LCD/LED unit to indicate Fire / Fault Signal of individual unit,inbuilt networking port(both RS485&Ethernet),Serial port for printer,two supervisory inputs,two position key switch and USB port for programming.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR .2 - Loop Panel 109 Add Extra for per Loop expansion beyond Two Loop 110 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured Coppercable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withelectrolytic gradeCopper made of copper rodsconfirming to IS 613-1964, of purity >99.7 %,Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) includingtesting etc. as required of following size. OEM must have its own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure A attached with this BSR 1.5 Sq.mm 2 core 111 8 core 112 Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, UTP (Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected byPVC Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies up to 250 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack &ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. All as per pre approved by Engineer in charge. 113 S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along withISI marked (IS:3419-1988) accessories as requiredinrecessincludingcutting the wall, covering conduit and making good the same as required. 25 mm 114 NON BSR 115 Supplying, Installation, Testing & Commissioning of floor mounted dust and vermin proof compartmentalised cubical type main fire pump Control Panel made out of CRCA sheet , required hardware ,dulytreated for derusting in 7 tank process with dephosphating and with powder coating on both side of panel in desired shade Thepanel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel ,hinged door with locking arrangement for equipment/switchgear . Thickness of sheet shall not be less than 1.6 mm up to 600 mm length / width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors and having accessories / switch gear (as per Specf Ch-06 & 08) as below:- complete in all respect. All as per pre approved by Engineer in charge. 116 Incomer:- 117 400 Amp. TPN MCCB (adj.O/L) with Extended ROM, 36 kA, with Thermal magnetic release,Analouge Ammeter, Voltmeter, Selector switches,CT, Indicating Lamps, 500 Amps FP Alum. Bus bar with with heat shrinkable sleeves. 118 Out going:- 119 (a) 200 Amp. TPN MCCB(adj.O/L) with Extended ROM, 36 kA, with Thermal magnetic release, Analouge Ammeter, Voltmeter, Selector switches,CT, Indicating Lamps for ON, OFF, TRIP 1 no. DOL Starter of rating upto 75 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 2 Sets 120 (b) 63 Amp. TPN MCCB (adj.O/L) with Extended ROM, 16 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, Selector switches, CT, Indicating Lamps for ON, OFF, TRIP 1 no. DOL Starter of 5 - 15 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 1 Set 121 (c) One no. Diesel Engine Auto Starting kit with Auto Manual selector switch & 3 attempt starting device, timers, relays, Indicating lamp for High / Low Lub. Oil pressure, High water temperature and engine ON indication, DC ammeter & voltmeter 122 (d) System controller to control Operation Main Electric pumps, Diesel pump, jockey pump in sequence consisting of relays, timers, sensors, annuciation window for fault indication. 123 (e) Appropriate Test Certificate/ report of product/accessories from OEM/Panel Manufecturer shall be submitted.
|