Tender For Electrical Work In Vivekanand Youth Hostel At Karauli - Wiring of light point/ fan point/ exhaust fan point/ call bell point as per PWD specification for electrical Works with ISI marked 1.5 sq. mm nominal size FRLS PVC insulated unsheathed flexible copper conductor 1.1 kV grade (IS:694)and1.5 sq.mmnominalsize FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)in recessed ISI markedMMS ( IS:9537 P - III ) vergin material PVC conduit & it"s all accessories( J.B. , Bends etc.) , round tiles,18SWGHotDippedGalvanized ModularBox withearth terminal, 6 A Modular switch, Modular face plate with grid plate, 3 pinceilingrose/lampHolder/3pinconnector,screwsetc, making connections,all as per pre approved by Engineer in charge, testingetc.completeasrequired. Forspecificationofcopper Conductor,Phenolic Laminated sheet"s & Electrical/ Wiring accessories referChapterE-04,E-05&E -07 .Foradditionaltechnicalparametersofproducts/work ,refer Annexure "A" attached with this BSR . 2 Short point (up to 3 mtr.) 3 Medium point (up to 6 mtr.) 4 Long point(up to 10 mtr..) 5 WiringoftwincontrollightpointasperPWDspecificationfor electrical Works with ISI marked 1.5 sq. mm nominal size FRLS PVC insulatedunsheathedflexiblecopperconductor 1.1kVgrade (IS:694) and1.5 sq.mmnominalsize FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI markedMMS ( IS:9537 P - III ) vergin material PVC conduit & it"s all accessories( J.B. , Bends etc.) , round tiles,2 nos. 18 SWG Hot Dipped Galvanized Modular Box with earth terminal 2Nos6AtwowayModularswitch,3pinceilingrose/lamp holder/ 3pinconnector,Modularfaceplatewith gridplate, screws etc,all as per pre approved by Engineer in charge,making connections,testingetc.completeasrequired. Forspecification ofcopper Conductor, PhenolicLaminatedsheet"s&Electrical/ Wiringaccessories referChapterE-04,E-05&E-07. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 6 Long point(up to 10 mtr..) 7 Wiring of 3/5 pin 6 amp. Light plug point as per PWD specification forelectricalWorkswithISI marked1.5 sq.mmnominalsizeFRLS PVC insulated unsheathed flexible copper conductor 1.1 kV grade (IS:694) and1.5 sq.mmnominalsize FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI markedMMS ( IS:9537 P - III ) vergin material PVC conduit&it"sallaccessories(J.B.,Bendsetc.),roundtiles,18 SWG Hot Dipped Galvanized Modular Box with earth terminal, 6 A modularswitch, 3/ 5 pin 6 A modular socket, Modular face plate with grid plate, screws etc,all as per pre approved by Engineer in charge, makingconnections,testingetc.completeasrequired. For specification of copperConductor,Phenolic Laminated sheet"s & Electrical/ Wiring accessoriesrefer Chapter E - 04, E - 05 8 On board 9 Long point (up to 10 mtr..) 10 S&Ffollowingsizes(dia.)ofISImarkedMMS(IS:9537P-III)vergin material PVC conduit as per PWD specification for electrical Works along with its accessories (IS: 3419 ) as requiredinrecess includingcutting the wall, covering conduit and making good the same as required.Foradditionaltechnicalparametersofproducts/work ,refer Annexure "A" attached with this BSR . 11 20 mm 12 25 mm 13 32 mm 14 SupplyinganddrawingFRLSPVCinsulated&unsheathed flexiblecopperconductorasperPWDspecificationfor electricalWorkswithISImarked(IS:694)andasperIS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.99%puritycopper,class5strandinginacc.toIEC 60228for lowerwattloss,oxygenfree(<10ppm)for lesschancesofoxidizationandhighersilvercontentfor givesbetterconductivity,insulationPVCtypeA,flame retardantasperIS10810-53,betteramperageratingas perVDE0298part4, ,inexisting surfaceorrecessed PVC/MSconduit/casingcappingincluding allasperpre approved by Engineer in charge,making connections, etc. asrequired.OEMMusthaveitsowninhouseNABLlab setupforalltestingfacilitiesforwires.Foradditional technical parameters of products/ work, referAnnexure "A" attached with this BSR . 15 3x 1.5 sq.mm 16 2 x 2.5 sq. mm. + 1x1.5sqmm 17 3 x 2.5 sq.mm 18 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. 19 4 x 10.0 sq.mm 20 4 x 6.0 sq.mm 21 1 x 6.0 sq.mm 22 1 x 4.0 sq.mm 23 Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant vergin UV Stabilized Polycarbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating ,minimum width of switch toggle( PUSH PART ) should not less then 20mm, including all as per pre approved by Engineer in charge,making connections, testing etc. as required For additional technical parameters of product / work refer Annexure "A" attached with this BSR 24 10 A bell push 25 25 Amp. 2 Module switch With Led Indicator 26 Providing & Fixing of modular type lockable feature socket duly made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR 27 25 Amp. 2 Module Socket 28 Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR 29 1/2 Module 30 Providing & Fixing of Wiring Accessories OEM fabricated following size GI box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . 31 1/2 Module 32 Providing & Fixing ofISI marked (IS:371) 6 amp surface type 3 pin ceiling rose with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screws including making connection testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 33 Providing & Fixing of ISI marked (IS:1258) batten/angle lampholder with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screwsincluding making connection testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 34 Providing & Fixing of ISI marked surface type buzzer (IS:2268-1994) with CM/L no. printed including making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 35 Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost ofISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. For specification ofWiring accessories refer ChapterE - 07related item & For additional technical parameters of product / work refer Annexure "A" attached with this BSR 36 Providing&Fixingof240/415VACMCBwithpositive isolationofbreakingcapacitynotlessthan10KA(B/C tripping characteristic as per type of load andsite requirement) 4KV impulse withstand voltage,as per PWD specification for electrical Works with ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2,lowwattlosses,tripfreemechanisum,energylimiting of class 3 as per IEC,minimum phase termination capacity of 35sq.mm.,conductorlineloadreversibility,labelholding facility,IP20contactprotectionandfittedwith existing distribution board/sheets, min. operation 20,000 upto 32 A rating and 10,000 upto 63 A, 5000 for 80 A ratingincluding makingconnections,testingetc.asrequired. .OEMshall havesubmit NABL/CPRI/ERDAaccrediatedlabtest reports beforeexecution&Allasperpreapprovedby Engineer in charge.For additional technical parameters of products/work ,referAnnexure"A"attachedwiththis BSR . 37 Single pole MCB 38 6 A to 32 A rating 39 Double pole MCB 40 6 A to 32 A rating 41 Four pole MCB 42 40 A rating 43 50-63 A rating 44 Providing&Fixingof240/415VResidualcurrentcircuit breaker (RCCB) as per PWD specification for electrical WorkswithISImarked(IS:12640-1)/conformingtoIEC 61008-1,ratedconditionals/ccurrentof10KA,truly currentoperatedand shalloperate onCBCT mechanisum, provisionforpadlock, min.operation10,000upto63A rating and5000 for 100 Arating, minimum phase termination capacity of 50 sq.mm. rigid wire, IP 20 contact protectionwithexistingdistributionboard/sheet including making connections, testing etc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab test reports beforeexecution&Allasperpreapprovedby Engineer in charge.For additional technical parameters of products/work ,referAnnexure"A"attachedwiththis BSR . 45 Two pole 30 mA sensitivity 46 32/40 A rating 47 Providing & Fixing of Recessed/surface mounting heavy dutyhorizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheetnot less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work referAnnexure "A" attached with this BSR 48 Metal door (single phase) IK-09 and IP-43 with Metal end box 49 16 Way (16+2) 50 Metal door (Three phase) IK-09 and IP-43 with Metal end box 51 6 Way 52 P&F metal clad / Plastic industrial plug top & socket unit with pin and sleeve type contact on porcelain/ bakelite base in Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted (without MCB) including making connections, testing etc.as required.For additional technical parameters of product / workrefer Annexure "A" attached with this BSR 53 20 amp, 2 pin + scrapping Earth, 2 Module 54 Providing & Fixing of IP20 SMD Mid Power LED batten with integrated box (min.1200mmx40mmx60mm including reflector) with replacable driver fixture made from Powder coated Extruded aluminium housing ,Min. lumen output 4400 lm, System lumen efficacy ≥ 110 lm/Watt output, internal surge protection of 4.0 KV with Short & Open circuit protection,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screenprinting on housing 55 OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached withthis BSR 56 Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / Sqaure SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt, THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.).Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. 57 OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR 58 Surface Mounting (with extruded alumn. Housing ) 59 Minimum lumen output 1300 lm 60 Providing & Fixing of IP65 IK08 rated Integrated SMD Mid power LED bulk head type light fixture made from Pressure Die Cast AL housing suitable with integral driver, system lumen efficacy ≥100 lm/Watt output , THD < 10% ,p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing surge protection 4 KV. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR 61 Minimum lumen output 1000 lm 62 Making of hole in wall (brick/stone) of required size for housingexhaustfanandmakinggoodthesame,with cement plaster as required of following size: 63 Up to 457 mm size 64 Providing & Fixing of BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan Conforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR 65 1200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 ) 66 P & F 1.2mm thick M.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length extended on each side . All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A"attached with this BSR 67 Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR 68 300 mm sweep(900/1400 RPM) 69 Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printed made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR 70 5 step fan regulator 2 Module 360 dgree rotating 71 Providing & Fixing of energy efficient /energy saving IP 20 LED direct retrofit Bulbin existing holder or fixture as required with system lumen efficacy ≥100 lm/Watt output ,pf 0.95 , CRI >70,minimum life time of minimum25000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) certificate / Report from OEM shall be submitted. All as per pre approved by engineer in charge . for additional technical parameters of product/ work, refer Annexure "A" attacheded with this BSR. 72 9 Watt 73 Providing & Fixing ofIK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles,of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R numberhaving efficiency more than 85 % and in compliance to BIS certified and Trade markcertificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10%, driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K±355K.Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 74 High Power LED Flood Light Minimum lumen output 12400 lm 75 Providing & Fixing of Street light bracket made out from following size of " B " class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 76 40 mm Dia. 77 Supplyandinstallationofhigh tensile low carbon steel rod molecularly bonded with 99.9 % Copperthickness (250 microns) andconfirming toUL 467, IS/IEC 62561-2of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- 78 (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole 79 (b)filled with anti corrosiveconductivecompounds with the permanent sealings at both the ends, CPRI/ ERDAtested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated labfor lowresistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major contentas per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts 80 © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt 81 (d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. 82 (d)Testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book. 83 (e) Test certificatesfor confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 84 17.2 mm thick and 3 Mtr. Long 85 Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR 86 25mm x 6mm G.I. ( Hot Dipped) Strip 87 Supply & Laying following size earth wire in horizontal or vertical run in ground / surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with thisBSR 88 8 SWG G.I. ( Hot Dipped ) Wire 89 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure "A" attached with this BSR 90 10.0 Sq. mm 91 4 core 92 150.0 Sq. mm 93 3.5 core 94 P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class750 N,Externally corrugated and having smooth surface insidewith HDPE Coupler, Elbow, Teeat required Depth below the ground for laying cable of followingNominal Outer dia.MFR Test reportfrom NABL accrediated is to be submitted.(Excavation of Earth& Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 95 50 mm 96 110 mm 97 Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 98 3.5 x 150.0 sq.mm 99 4 x 10.0 sq.mm 100 Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 101 225mm x 50mm x 1.6mm 102 300mm x 50mm x 1.6mm 103 SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalisedcubical panel as specifications andOther parameters requiredas per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- 104 (a)Thickness of CRCA sheet shallbe 2.0 mm,cable alley compartments having concealed hinged type doors with key type lock with / withoutdetachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided 105 (b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting,pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel.The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. 106 [c)Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar(>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only.All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar/ Flexible wire for Interconnection between Main busbar and Switchgearis to be Paid Extra ) 107 (d)Wiring between components within switchgear and Incoming / outgoing cableshall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. 108 (e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. 109 (f)Floor mounted panel shall be mounted on Base frame of ISMCchannel size 100 x 50 x 5 mm( to be paid Extra ) 110 (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. 111 (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 112 Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwith standard short circuit withstand capacity, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 113 Electrolytic grade (Cu-ETP) Tin Coated annealed copper bus bars IACS 100% grade 114 Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 115 Three phase with universal Auxiliary supply + AMP + HZ + PF + KW + KVA + KVAR + KVARH + KWH + DUAL ENERGY+ ENERGY+THD-I, THD-V & RUN HRS + MD with RS485 116 Providing & Fixing of BIS approvedCurrent Transformeras per PWD specification for electrical Works ,ISI marked as perIS 2705-1992/ conforming to IEC 60044-1, with secondary terminalof CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as requiredCurrent transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 117 Resin cast wound type CT 118 C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA 119 Providing & Fixing of110/220 V, unibody LED Indicatinglamp IEC 60947with integral circuit, IP 65 above panel &IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 120 Red/yellow/Green colour 121 Blue / white Colour 122 Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006with one sideanti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 123 3.3 KV,class A 2 mm thick with proof voltage 10 KV AC (rms) and Break Down Voltage 30 KV AC (rms) 124 SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR 125 4 pole MCCB With Thermal Magnetic release 126 200 Amp , 25 kA, adjustable O/L & adjustable S/C setting, 127 Supply and fixing of following accessories for Moulded case circuit breaker (MCCB)compatible to main MCCB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 128 Extended Rotary Handle 129 Supplying and drawing coaxial cable 75 ohm impedance with foam PE insulated solid bare copper inner conductor, and Ist outer conductor of bonded alum. tape and second outer conductor ofalum. alloy braidin existingsurface or recessed conduit/casing capping including making connections as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR 130 RG - 6 131 Supply and Laying of PE Insulated, PVC Inner Sheathed, armoured & PVC Sheathed Telephone Cable. with 0.5 mm thick Solid Annealed Bare Copper Conductor as per IS: 8130/84 telephone cable confirming to TEC specificationsGR/WIR 06/03, Mar.-2002 in existing pipe / open trench / Cable tray / on surface including making necessary connection, testing etc. as required of size. For additional technical parameters of product / work refer Annexure "A" attached with this BSR 132 5 pair 133 Providing & Fixing of following modular accessories as per PWD specification for electrical Works,made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR 134 T.V. coaxial socket 135 RJ-11 telephone jack singleline 136 Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, UTP (Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected byPVC Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies up to 250 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack &ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 137 Supply and Installation of unsheilded/360 degree sheilded Information outlets made of high impact plastic body with ABS, FR Grade halogen free material with provision for protection against dust in jack, suitable for Cat 6/6A application complying to latest ammendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat.6/6A standards at frequencies of up to 250 to 500 Mhz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have tooless/impact termination on reliable copper tin plated Insulation displacement contact, with easy lock mechanism, It supports IEC 60603-7-4 and complied with ANSI/TIA/EIA 568 C.2 standard. jack should be RJ11,RJ12 & RJ45 compatible. Should support Ethernet 1.2 Gb/s ATM,Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP) Specifications in existing modular/MS Boxes along with necessory connections as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 138 Cat 6, Un-sheilded Information Outlet 139 Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets Single/Dual or Quad Aperture ,material should bePC+ABS body, Suitable for RJ45 unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should be 86mm X 86mm as required complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 140 Single Aperture 141 Supply, Installation, Testing and Comissioning of Rack mounted 19" 1U, Cat6 24 Port loaded, 1.5-1.6 MM CRS chasis, powder coated, sheet steel, made of plastic (ABS), Modular Patch Panelswith Rear Cable management system and mounting hardware to mount the patch panel. Should have port identification numbers printed/engraved on front of the panel. Etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 142 Modular Patch Panel Loaded with Cat -6 I/O 143 Supply , Installation and Testing of 4 pair, 100 Ohm impedance, Cat 6/6A /Class E/Ea patch cords should be constructed of minimum 23/24 AWG, stranded bare Copper cable with FRPVC/LSZH Jacket, with an enhanced performance by factory moulded RJ45 connectors with strain relief boots as per ANSI/TIA/EIA 568-C.2 suitable for Cat 6/6A application complying to latest ammendments Category 6/6A Standards, According. to TIA568C.2, ISO/IEC 11801, EN 50173, IEC 60603-7-51, EN 60603-7, IEEE 802.3an minimum requirement for 1G BASE-T to 10G BASE-T performance. Patch cords shall be straight thru cable compatible with both T568-A and T568-B wiring schemes, should support IEEE 802.3af / IEEE 802.3at for POE applications, Minimum 750 to 1000 mating cycles in plug contacts for long durability, Should support Ethernet 10GBASE-T, 1.2 Gb/s ATM, Token ring 4/16, Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP).All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 144 Cat 6, U/UTP (Unscreened/Un-sheilded Twisted Pair) Patch Cord 145 1 Mtr 146 2 Mtr 147 Supply & Installation of IP-20 & IK-08 , UL ListedWall mounted Double Section Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet, front sturdy sheet steel frame folded from one piece and welded with minimum 5mm toughened glass door,Vertical Mounting Rail 1.6 MM with "U"Marking , with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, 2 pair of 19" angles with wall mounting provision on wall. Accessories like: 1 No of 19" 1U Horizontal Cable manager, 1 No of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 1 No of 19" 1U, mountable socket strips with 5 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable. fixing on wall with Suitable Anchor fastneretc as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 148 9 U Rackwith Width 600 mm & Depth 400 mm + 100 mm 149 Supply , Installation, Testing and Comissioning ofManaged Layer-2 Intelligent 10/100 Ethernet Switch providing 24 x 10/100/1000 MBPS Giga Ethernet ports / with min 2 SFP Giga Ports (provision for Fiber Giga connectivity) with related LAN Base Software including making connections etc as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 150 System Certification & Documentation by OEM for 20 Years as required 151 Supply & Fixing of CO2 type Fire Extinguisher conforming to IS:15683:2018, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.0 Mtr. Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability,including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 152 Capacity 4.5 Kg. 153 Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC typeFire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 154 4 kg 155 SITCof EN / LPCB/ UL listed / approved conventional type Manual call point resettable complete with Glass, hammer and chain etc.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 156 SITC of EN / LPCB/ UL listed / approved conventional type Hooter cum strobe including the cost of all accessories,Etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 157 SITC of wall type following zone (each zoneaccessing minimum 20 units (detectors/ devices )) Conventional Type microprocessor based with LCD display EN / LPCB/ UL listed / approved main control panel fabricated from 16 SWG CRCA sheet steel sealed maintenance free (SMF) batteries of min2X7AH of 12 V or as required.including the cost of all accessories, Etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 158 4 zone 159 Supplying and drawing Fire Resistant flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existingsurface or recessed PVC/ MS conduit/casing capping/ Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 160 2 x 1.5 Sq.mm Unarmoured With Outer Sheath in Red Color 161 Supply , Installation, Testing and Comissioning of Inverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R- 410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and 50 hz , single phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in charge. For additional technicalparameters of products/ work , refer Annexure "A" attached with thisBSR . 162 1.5 TR ISEER not less then 4.6 163 Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge. For additional technical parameters ofproducts/ work , refer Annexure "A" attached with this BSR . 164 Un Armoured 165 4 core x 2.5 Sq.mm 166 Supply, Fixing and testing of following capacity ISO certified company made wall mounted stabilizer having output voltagevariationfrom200Vto250V(+/-5%)withinput voltagevariationfrom170Vto260V,timedelayfacility from 2 to 4 minute and high cutoff at 270 V with providing of16Ampplugtopmaking connectionetc completein all respect.NABL accredeated/ CPRI/ ERDA lab testing reports with OEM certificate must submitted to engineer in charge. All as per pre approved by Engineer in charge.For additionaltechnicalparametersofproducts/work ,refer Annexure "A" attached with this BSR . 167 3 kVA 168 Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR 169 Supply , Installation, Testing and Comissioning of Interconnectingrefrigerant copperpipefor split ofDHE GradeC12200-ASTMB68,B75,chemicalcompositionof copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealedcoppertube:-Tensilestrength=210Mpawih elongation%=40Min.InkMark BrandPrintingonHard Tubes should be present. Material TestCertificaterequired witheachsuppliedmaterial. Pipingbetweeneachsetof indoor & outdoor units of different sizes as per OEM requirement&specificationsincludingchasecutting, supports,making good thesamewith sand cement plaster etc.asrequired.AllasperpreapprovedbyEngineerin charge. Foradditionaltechnicalparametersofproducts/ work, refer Annexure "A" attached with this BSR . 170 Supply & fixing of external thermal closed-cell Nitrile rubber Insulation material FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified "Class O" in Fire Propagation as per BS 476 Part 6 in form of sheet on duct including cost of adhesive (CPRX Compund) complete as required. All as per pre approved by Engineer in charge 171 9mm thick for indoor Application 172 Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping withfittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing,support with MS hanger on ceiling or recessed in wallwith chasing & plastering with 6 mmthickclosedcellelastomeric nitrile rubberinsulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 173 25 mm 174 Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia 175 50 mm dia per running inch length 176 100 mm dia per running inch length 177 150 mm dia per running inch length 178 NON BSR ITEMS 179 SITC of DOME IP IR CCTV Cameras: Network H.265 2MP (FULL HD) Megapixel High Frame Rate Mini dome camera with Built in Microphone:2MP IR Dome Camera with Built in Mic: 1/2.8" Progressive Scan CMOS; Resolution: 1920 × 1080@30fps or better; Colour: 0.01 Lux @(F1.2, AGC ON) or better, H.265+ Compression or better; 120 dB true WDR or better; Fixed 2.8/4mm lens; Built in Mic; 3D DNR; 40m IR Range or better, triple streams; BLC, 3D DNR, HLC; Line crossing detection, intrusion detection; Scene change detection; Face Detection; Anti-flicker, heartbeat, mirror, password protection, privacy mask, watermark, IP address filter; ONVIF (PROFILE S, PROFILE G), ISAPI; Built-in micro SD/SDHC/SDXC slot, up to 128 GB or better; Operating Condition: -30 °C to +60 °C; IP67; 12DC & PoE; Certificate of Compliance: UL, CE/FCC, BIS, ROHSApproved Make: SAMSUNG / HIKVISION / PANASONIC / INFINOVA/CP PLUS/DAHUA/HONEYWELL 180 SITC of IP IR CCTV BULLET OUTDOOR CAMERA: Network H.265 4MP (FULL HD) Megapixel High Frame Rate IR Bullet Camera (Outdoor), 4MP Full Frame Low Light IR Bullet Camera: 1/2.5" Progressive Scan CMOS; Resolution: 2688 × 1520 or better; Color: 0.008 lux @(F1.2, AGC ON) or better; slow shutter; Fixed 4/6mm lens; triple streams; 3D DNR; 120db WDR; 80m IR Range or better; Line crossing detection, intrusion detection, object removal detection, unattended baggage detection, Scene change detection; Face Detection; Anti-flicker, heartbeat, mirror, password protection, privacy mask, watermark, IP address filter; ONVIF (PROFILE S, PROFILE G), ISAPI; RoI; Support micro SD/SDHC/SDXC card (128G), local storage and NAS (NFS,SMB/CIFS), ANR; Operating Condition: -30 °C to +60 °C; IP67; 12DC & PoE; Metal Body; Built in Junction box for Cable management; Certificate of Compliance: UL, CE/FCC, BIS/ROHSApproved Make: SAMSUNG / HIKVISION / PANASONIC / INFINOVA/CP PLUS/DAHUA/HONEYWELL 181 SITC of RAID 5 Supported 32 channel NVR with upto 48 TB HDD Support 32 channelIP inputs; Dual OS for redundancy; Support ANR technology;320mbps incoming bandwidth, supports up to 12MP full channel recording; support H.265 compression; 16ch syncronised playback @1080p; support RAID 5; N+1 hot spare system; support 3rd party cameras; 4K output; minimum 8 SATA HDD Slots; each slot should suppport upto 6TB HDD; e-Sata interface; Dual gigabit self adaptive Ethernet interface; serial interace; USB interface; Alarm in/out;Dual Power Supply(all cameras and Storage-NVR should be of same make for the smooth functioning of the system). Certificate of Compliance: UL, CE/FCC, BIS/ROHSApproved Make: SAMSUNG / HIKVISION / PANASONIC / INFINOVA/CP PLUS/DAHUA/HONEYWELL 182 SITC of 3.5" 6TB Surveillance Hard Disk (Makes: Seagate / WD / Toshiba) 183 Supply, Installation, Testing & Commissioning of Managed Layer-2 Intelligent Ethernet POE Switches providing 08 x 10/100/1000 Fast Ethernet POE ports- 67W or better and 2 dual purpose uplink ports (provision for Copper / Fiber Giga connectivity) all switches & related Fiber modules should be of same make & category for seamless integration with each other of Approved Makes: Cisco Catalyst Series or Equivalent in Avaya, Juniper ) 184 SITC of 55"" Flat Smart Screen HD Profesional LED with remote control and wall mount unit / floor stand complete with making connections etc of approved Makes: LG, Samsung, Panasonic. 185 SITC of 1 KVA Line interactive, 160-260 V50 Hz ON-Line UPS with lsolation transformer suitable for single phase A C input and single phase AC output having enclosure degree of protection as per IS:13947 Part-I/1993/2004 complete with all protection with SMF VRLA (12V, AH-2 nos) Batteries, charger, switching Device etc. Make- Numeric/APC /Emerssion . 186 SITC ofRO water system with Filtration stage = Particulate filter-Membrane life enhancer filter - sediment filter - Pre carbon filter -RO Membrane filter - Post carbon filter,Input power Rating - 230 V AC , 50 HZ, Percentage of Rejection TDS - 90% or better having following Features (a) Double purification by RO with ESS or latest technology with TDS indicator (b).Spin welded RO Membrane Housing to prevent tempering (c). Push fit components for leak proof performance (d). Fully automatic operation with auto start and auto off (e). SS/ABS construction for corrosion free lifespan (f). Equally suitable for water from all bore wells,,overhead storage tanks,water tankers and even municipal taps (g) RO Membrane Flushing - Auto Flush @ Every Start , Every Stop and every One Hourof working for one minute. complete in all respect with following capacity. 187 Purification capacity- 50 LPH,Duty Cycle 270-500 liters/day, Make- Eureka Forbes/ Kent/Voltas/ Ion exchange. 188 Supply , Installation, Testing and Comissioning of IS:1475 marked self contained drinking water cooler withhermeticallysealed compressor,non CFC refrigerent suitable for operation on 230V/1pH/50Hz AC supply,Full stainless steel (SS304)body (0.8 mm thick)and tank (0.5 mm thick) , stainless steel water tray,minimum two nosBrass Chrome plated faucets and suitable drainage system complete in all respect with requiredheight MS fabricated and Painted Angle iron frame( Cost of frame to be paid Extra )complete in all respect of the following capacity.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 189 cooling capacity 60 Ltr./Hr. and storage capacity 120 Ltrs 190 Providing & Fixing of Vertical(BEE 5 star rated) / Horizontal( BEE 3 star rated) storage water heater with outer casing made of Engineering Plastic sheet (Upto 25 Ltr) / Metal rust proof Body (35 & 50 Ltr), Glass - line / Titanium Enamel coated Pressure Pump Compatible 8 bar pressure Inner tank, Glass Line Coated , mineral filled heating element, stem type, snap actionadjustable thermostat , Dual indicating lampsInjected PUF insulation, Multi Function Valve etc. as required held in position with 2/4 no. 10/12 mm anchor Fastener, duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top with Portable Residual Current Device ( PRCD ) , including making inlet, outlet Flexible alloyconnection, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 191 15 Ltr. 192 50 Ltr.
|