Tender For 12. Electrical Work Of Power Audit Chc Intalikheda And Gingla Distt. Salumber - 1 Item Description 2 CHC Intalikheda 3 Point wiring 4 Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)inrecessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & itsISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thickHot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws,making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheets & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure A attached with this BSR 5 Short point (up to 3 mtr.) 6 Medium point (up to 6 mtr.) 7 Long point(up to 10 mtr.) 8 Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) inrecessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & its ISI marked (IS:3419-1988)accessories, Hot Dipped GalvanizedModular box of 1.2 mm thick with earth terminal, 10 A modularswitch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheets & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure A attached with this BSR 9 On board 10 S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along withISI marked (IS:3419-1988) accessories as requiredinrecessincludingcutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure A attached with this BSR 11 20 mm 12 25 mm 13 32 mm 14 Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure A attached with this BSR 15 2 x 2.5 sq. mm. + 1x1.5sqmm 16 1 x 4.0 sq.mm 17 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. 18 1 x 6.0 sq.mm 19 4 x 6.0 sq.mm 20 2 x 6.0 sq. mm. + 1 x 2.5 sq. mm. 21 Distribution Board & Accessories 22 Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure A attached with this BSR 23 Single pole MCB (With B/C curve tripping Characteristics) 24 6 A to 32 A rating 25 Four pole MCB (With B/C curve tripping Characteristics) 26 50/63 A rating 27 Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure A attached with this BSR 28 Metal door (Three phase) IK-09 and IP-43with Metal end box 6 Way 29 Providing & Fixing of 240/415 V factory fitted RCBO with overload, short-circuit and earth leakage protectionwith ISI marked (IS12640-2)/ conforming to IEC 61009-1, breaking capacity 10 KA,provision for pad lock, min. Electrical operation 10,000 upto 63 A rating , minimum phase termination capacity of 35sq.mm. , IP 20 contact protection with existing distribution board / sheetincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure A attached with this BSR 30 Four pole 100/300 mA sensitivity 63 A rating 31 P&F metal clad / Plastic industrial plug top & socket unit with pin and sleeve type contact on porcelain/ bakelite base in Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted (without MCB) including making connections, testing etc.as required.For additional technical parameters of product / work refer Annexure A attached with this BSR 32 20 amp, 2 pin + scrapping Earth, 1 Module 33 20 amp, 3 pin + scrapping Earth, 4 Module 34 Electrical Accessories 35 Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printedmade out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating ,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure A attached with this BSR 36 5 step fan regulator 2 Module 360 dgree rotating 37 Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant vergin UV Stabilized Polycarbonatewith brass terminals and captive screws & silver alloy contact tipwith IP-20 rating ,minimum width ofswitch toggle( PUSH PART ) should not less then 20mm,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure A attached with this BSR 38 10 A one way switch 39 10 A two way switch 40 16 A one way switch With LedIndicator 41 25 Amp.2 Moduleswitch With LedIndicator 42 32 Amp. 2 Moduleswitch With LedIndicator 43 Providing & Fixing of modular type lockable feature socket dulymade out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , includingall as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure A attached with this BSR 44 6 A3/5 pin shuttered socket 45 6/16 Ashuttered socket 46 25 Amp. 2 Module Socket 47 Providing & Fixing of following modular accessories as per PWD specification for electrical Works,made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure A attached with this BSR 48 Blanking plate 49 25 Amp. 2 Module Motor Starter with on / off Push button 50 Modular MCB 6 A to 32 ASP 51 Modular MCB 6 A to 32 ADP 52 Providing & Fixing offollowing size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 53 1/2 Module 54 3 Module 55 4 Module 56 5 Module 57 6 Module 58 8 Module 59 Providing & Fixing ofWiring Accessories OEM fabricated following size GI box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 60 1-2 Module 61 3 Module 62 4/5 Module 63 6 / 8 module 64 L T cables 65 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have its own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure A attached with this BSR 66 16.0 Sq. mm 67 4 core 68 25.0 Sq. mm 69 3.5 core 70 50 sqmm 71 3.5 core 72 Earthing 73 Supplyandinstallationofhigh tensile low carbon steel rod molecularly bonded with 99.9 % Copperthickness (250 microns) andconfirming toUL 467, IS/IEC 62561-2of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- 74 (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole 75 (b)filled with anti corrosiveconductivecompounds with the permanent sealings at both the ends, CPRI/ ERDAtested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated labfor lowresistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major contentas per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts 76 © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt 77 (d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. 78 (d)Testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book. 79 (e) Test certificatesfor confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 80 17.2 mm thick and 3 Mtr. Long 81 Supply & Laying following size earth stripin horizontal or vertical run in surface by means of Earth strip DMC Insulatorincluding riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 82 25mm x 6 mm G.I. ( Hot Dipped) Strip 83 Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95%thimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 84 8 SWG G.I. ( Hot Dipped) Wire 85 Fans 86 Providing & Fixing ofBEEStar rated copper wounded double ball bearing capacitor start, aluminium body & Metallicblade ceilingfanConforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 87 1200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 ) 88 Providing & Fixing of Heavy duty capacitor start, copper woundDouble ball bearing900/1400 RPM single phaseExhaustfan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 89 300 mm sweep(900/1400 RPM) 90 Providing & Fixing ofof Double ball bearing, copper wounded capacitor startsingle phase metallicblade fresh air fan, in existing opening including cost of hardware , flexible 3 core copper conductor ,making connections, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 91 225 mm sweep 92 Providing & Fixing of 450 mm SweepOscillating type Wall mounting / Pedestal typefans with Three speed, ON andOFF position, Sintered Iron bush oil impregnated,with metal front and back 120 or moreribs guard; Three no. Aluminiumblades, minimum Air delivery 100 Cum. / Minute , Minimum Service Value 1.11 Cum./min/watt, noise level should be <= 75 dB, power consumption <= 120 watts, motor protection through thermal overload protection device, including fixing with anchor bolts, making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 93 Wall mounting type with Adjustable Vertical Angle 94 Providing & Fixing ofextra down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steelpipe including cutting, threading, drilling, fixing quarter pin etc as reqd.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 95 INDOOR LIGHTING 96 Providing & Fixing of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminiumhousing with in built driver, System lumen efficacy = 110 lm/Watt output, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.=0.95, CRI >80 , life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 97 1170mm(+/-10%) LED batten with min. lumen output 2200 lm 98 Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / SqaureSMD Mid Power LED Downlight with power coated die-cast aluminum housingwith UV Stabilized non yellowish Diffuser withBIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of = 110 lm / watt, THD < 10 % , Pf.=0.95, CRI >80,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. 99 OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 100 Surface Mounting (with extruded alumn. Housing ) 101 Minimumlumen output 650 lm 102 Minimum lumen output 1300 lm 103 Minimum lumen output 1950 lm 104 Providing & Fixing of IP65 IK08 rated Integrated SMD Mid power LED bulk head type light fixture made from Pressure Die Cast AL housing suitable with integral driver, system lumen efficacy =100 lm/Watt output , THD < 10% ,p.f.=0.95,CRI >80 , life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. surge protection 4 KV. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 105 Minimum lumen output 1000 lm 106 Providing & Fixing of energy efficient /energy saving IP 20 LED direct retrofit Bulbin existing holder or fixture as required with system lumen efficacy =100 lm/Watt output ,pf 0.95 , CRI >70,minimum life time of minimum25000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) certificate / Report from OEM shall be submitted. All as per pre approved by engineer in charge . for additional technical parameters of product/ work, refer Annexure A attacheded with this BSR. 107 2/3 Watt 108 6/7 Watt 109 9 Watt 110 15 Watt 111 18/20 Watt 112 LT Panels & Accessories 113 SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalisedcubical panel as specifications andOther parameters requiredas per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- 114 (a)Thickness of CRCA sheet shallbe 2.0 mm,cable alley compartments having concealed hinged type doors with key type lock with / withoutdetachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided 115 (b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting,pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel.The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. 116 [c)Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar(>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only.All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar/ Flexible wire for Interconnection between Main busbar and Switchgearis to be Paid Extra ) 117 (d)Wiring between components within switchgear and Incoming / outgoing cableshall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. 118 (e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. 119 (f)Floor mounted panel shall be mounted on Base frame of ISMCchannel size 100 x 50 x 5 mm( to be paid Extra ) 120 (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. 121 (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 122 Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwith standard short circuit withstand capacity, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 123 Electrolytic grade Aluminium bus bar 6010 grade 124 Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 125 Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 126 Three phase Ammeterwith Inbuilt Selector Switch 127 Three phase Voltmeter with Inbuilt Selector Switch 128 Providing & Fixing of110/220 V, unibody LED Indicatinglamp IEC 60947with integral circuit, IP 65 above panel &IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 129 Red/yellow/Green colour 130 Providing & Fixing of BIS approvedCurrent Transformeras per PWD specification for electrical Works ,ISI marked as perIS 2705-1992/ conforming to IEC 60044-1, with secondary terminalof CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as requiredCurrent transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 131 Ring type tape wound CT 132 C T Class 1, Ratio upto 150/5, Burden 5 VA 133 C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA 134 Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006with one sideanti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 135 11 KV,Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage45 KV AC (rms) 136 SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure A attached with this BSR 137 3 pole MCCB With Thermal Magnetic release 138 up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting, 139 4 pole MCCB With Thermal Magnetic release 140 up to 100 Amp , 10 kA, fixed O/L & fixed S/C setting 141 125 Amp , 25 kA, adjustable O/L & adjustable S/C setting, 142 200 Amp , 25 kA, adjustable O/L & adjustable S/C setting, 143 Providing & Fixing of ISO certified company made on load change over switch, front handle operated, four pole 415 V as per PWD specificationfor electrical Works conforming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating.Appropriate type test certificate / OEM test report shall be submitted .All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 144 Open execution type 125 A 145 Fire protection work 146 Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC typeFire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 147 2 kg 148 4 kg 149 6 kg 150 Supply & Fixing of CO2 type Fire Extinguisher conforming to IS:15683:2018, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.0 Mtr. Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability,including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 151 Capacity 3.0 Kg. 152 Capacity 4.5 Kg. 153 CHC Gingal 154 Point wiring 155 Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)inrecessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & itsISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thickHot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws,making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheets & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure A attached with this BSR 156 Short point (up to 3 mtr.) 157 Medium point (up to 6 mtr.) 158 Long point(up to 10 mtr.) 159 Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)in recessed ISI markedMMS ( IS:9537 P - III ) PVC conduit & its ISI marked (IS:3419-1988) accessories, round tiles, 2 Nos Hot Dipped Galvanized M.S Modularbox of 1.2 mm thickwith earth terminal,2 Nos10 A two way Modular switch, 3 pin ceiling rose / holder / 3 way connector ,Modular face plate with grid plate,screws,making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheets & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure A attached with this BSR 160 Medium point (up to 6 mtr.) 161 Long point(up to 10 mtr.) 162 Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) inrecessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & its ISI marked (IS:3419-1988)accessories, Hot Dipped GalvanizedModular box of 1.2 mm thick with earth terminal, 10 A modularswitch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheets & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure A attached with this BSR 163 On board 164 Short point (up to 3 mtr.) 165 Medium point (up to 6 mtr.) 166 Long point(up to 10 mtr..) 167 S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along withISI marked (IS:3419-1988) accessories as requiredinrecessincludingcutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure A attached with this BSR 168 20 mm 169 25 mm 170 32 mm 171 Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure A attached with this BSR 172 2 x 2.5 sq. mm. + 1x1.5sqmm 173 1 x 4.0 sq.mm 174 4 x 4.0 sq.mm 175 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. 176 1 x 6.0 sq.mm 177 4 x 6.0 sq.mm 178 2 x 6.0 sq. mm. + 1 x 2.5 sq. mm. 179 Distribution Board & Accessories 180 Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure A attached with this BSR 181 Single pole MCB (With B/C curve tripping Characteristics) 182 6 A to 32 A rating 183 Double pole MCB(With B/C curve trippingCharacteristics) 184 40 A rating 185 Four pole MCB (With B/C curve tripping Characteristics) 186 50/63 A rating 187 Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure A attached with this BSR 188 Metal door (Three phase) IK-09 and IP-43with Metal end box 189 4 Way 190 6 Way 191 Providing & Fixing of 240/415 V factory fitted RCBO with overload, short-circuit and earth leakage protectionwith ISI marked (IS12640-2)/ conforming to IEC 61009-1, breaking capacity 10 KA,provision for pad lock, min. Electrical operation 10,000 upto 63 A rating , minimum phase termination capacity of 35sq.mm. , IP 20 contact protection with existing distribution board / sheetincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure A attached with this BSR 192 Two pole 100/300mA sensitivity 193 40 A rating 194 Four pole 100/300 mA sensitivity 195 63 A rating 196 P&F metal clad / Plastic industrial plug top & socket unit with pin and sleeve type contact on porcelain/ bakelite base in Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted (without MCB) including making connections, testing etc.as required.For additional technical parameters of product / work refer Annexure A attached with this BSR 197 20 amp, 2 pin + scrapping Earth, 1 Module 198 20 amp, 3 pin + scrapping Earth, 4 Module 199 Electrical Accessories 200 Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printedmade out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating ,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure A attached with this BSR 201 5 step fan regulator 2 Module 360 dgree rotating 202 Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant vergin UV Stabilized Polycarbonatewith brass terminals and captive screws & silver alloy contact tipwith IP-20 rating ,minimum width ofswitch toggle( PUSH PART ) should not less then 20mm,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure A attached with this BSR 203 10 A one way switch 204 10 A two way switch 205 16 A one way switch With LedIndicator 206 25 Amp.2 Moduleswitch With LedIndicator 207 32 Amp. 2 Moduleswitch With LedIndicator 208 Providing & Fixing of modular type lockable feature socket dulymade out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , includingall as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure A attached with this BSR 209 6 A3/5 pin shuttered socket 210 6/16 Ashuttered socket 211 25 Amp. 2 Module Socket 212 Providing & Fixing of following modular accessories as per PWD specification for electrical Works,made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure A attached with this BSR 213 Blanking plate 214 25 Amp. 2 Module Motor Starter with on / off Push button 215 Modular MCB 6 A to 32 ASP 216 Modular MCB 6 A to 32 ADP 217 Providing & Fixing offollowing size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 218 1/2 Module 219 3 Module 220 4 Module 221 5 Module 222 6 Module 223 8 Module 224 Providing & Fixing ofWiring Accessories OEM fabricated following size GI box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 225 1-2 Module 226 3 Module 227 4/5 Module 228 6 / 8 module 229 L T cables 230 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have its own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure A attached with this BSR 231 16.0 Sq. mm 232 4 core 233 25.0 Sq. mm 234 3.5 core 235 70 sqmm 236 3.5core 237 Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 238 4 x 16.0 sq.mm 239 3.5 x 25.0 sq.mm 240 3.5 x 70.0 sq.mm 241 Earthing 242 Supplyandinstallationofhigh tensile low carbon steel rod molecularly bonded with 99.9 % Copperthickness (250 microns) andconfirming toUL 467, IS/IEC 62561-2of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- 243 (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole 244 (b)filled with anti corrosiveconductivecompounds with the permanent sealings at both the ends, CPRI/ ERDAtested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated labfor lowresistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major contentas per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts 245 © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt 246 (d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. 247 (d)Testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book. 248 (e) Test certificatesfor confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 249 17.2 mm thick and 3 Mtr. Long 250 Supply & Laying following size earth stripin horizontal or vertical run in surface by means of Earth strip DMC Insulatorincluding riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 251 25mm x 6 mm G.I. ( Hot Dipped) Strip 252 Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95%thimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 253 8 SWG G.I. ( Hot Dipped) Wire 254 Fans 255 Providing & Fixing ofBEEStar rated copper wounded double ball bearing capacitor start, aluminium body & Metallicblade ceilingfanConforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 256 1200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 ) 257 Providing & Fixing of Heavy duty capacitor start, copper woundDouble ball bearing900/1400 RPM single phaseExhaustfan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 258 300 mm sweep(900/1400 RPM) 259 Providing & Fixing ofof Double ball bearing, copper wounded capacitor startsingle phase metallicblade fresh air fan, in existing opening including cost of hardware , flexible 3 core copper conductor ,making connections, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 260 225 mm sweep 261 Providing & Fixing of 450 mm SweepOscillating type Wall mounting / Pedestal typefans with Three speed, ON andOFF position, Sintered Iron bush oil impregnated,with metal front and back 120 or moreribs guard; Three no. Aluminiumblades, minimum Air delivery 100 Cum. / Minute , Minimum Service Value 1.11 Cum./min/watt, noise level should be <= 75 dB, power consumption <= 120 watts, motor protection through thermal overload protection device, including fixing with anchor bolts, making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 262 Wall mounting type with Adjustable Vertical Angle 263 Providing & Fixing ofextra down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steelpipe including cutting, threading, drilling, fixing quarter pin etc as reqd.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 264 INDOOR LIGHTING 265 Providing & Fixing of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminiumhousing with in built driver, System lumen efficacy = 110 lm/Watt output, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.=0.95, CRI >80 , life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 266 1170mm(+/-10%) LED batten with min. lumen output 2200 lm 267 Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / SqaureSMD Mid Power LED Downlight with power coated die-cast aluminum housingwith UV Stabilized non yellowish Diffuser withBIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of = 110 lm / watt, THD < 10 % , Pf.=0.95, CRI >80,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. 268 OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 269 Surface Mounting (with extruded alumn. Housing ) 270 Minimumlumen output 650 lm 271 Minimum lumen output 1300 lm 272 Minimum lumen output 1950 lm 273 Providing & Fixing of IP65 IK08 rated Integrated SMD Mid power LED bulk head type light fixture made from Pressure Die Cast AL housing suitable with integral driver, system lumen efficacy =100 lm/Watt output , THD < 10% ,p.f.=0.95,CRI >80 , life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. surge protection 4 KV. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 274 Minimum lumen output 1000 lm 275 Providing & Fixing of energy efficient /energy saving IP 20 LED direct retrofit Bulbin existing holder or fixture as required with system lumen efficacy =100 lm/Watt output ,pf 0.95 , CRI >70,minimum life time of minimum25000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) certificate / Report from OEM shall be submitted. All as per pre approved by engineer in charge . for additional technical parameters of product/ work, refer Annexure A attacheded with this BSR. 276 2/3 Watt 277 6/7 Watt 278 9 Watt 279 15 Watt 280 18/20 Watt 281 LT Panels & Accessories 282 SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalisedcubical panel as specifications andOther parameters requiredas per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- 283 (a)Thickness of CRCA sheet shallbe 2.0 mm,cable alley compartments having concealed hinged type doors with key type lock with / withoutdetachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided 284 (b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting,pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel.The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. 285 [c)Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar(>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only.All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar/ Flexible wire for Interconnection between Main busbar and Switchgearis to be Paid Extra ) 286 (d)Wiring between components within switchgear and Incoming / outgoing cableshall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. 287 (e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. 288 (f)Floor mounted panel shall be mounted on Base frame of ISMCchannel size 100 x 50 x 5 mm( to be paid Extra ) 289 (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. 290 (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 291 Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwith standard short circuit withstand capacity, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 292 Electrolytic grade Aluminium bus bar 6010 grade 293 Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 294 Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 295 Three phase Ammeterwith Inbuilt Selector Switch 296 Three phase Voltmeter with Inbuilt Selector Switch 297 Providing & Fixing of110/220 V, unibody LED Indicatinglamp IEC 60947with integral circuit, IP 65 above panel &IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 298 Red/yellow/Green colour 299 Providing & Fixing of BIS approvedCurrent Transformeras per PWD specification for electrical Works ,ISI marked as perIS 2705-1992/ conforming to IEC 60044-1, with secondary terminalof CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as requiredCurrent transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 300 Ring type tape wound CT 301 C T Class 1, Ratio upto 150/5, Burden 5 VA 302 C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA 303 Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006with one sideanti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 304 11 KV,Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage45 KV AC (rms) 305 SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure A attached with this BSR 306 3 pole MCCB With Thermal Magnetic release 307 up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting, 308 4 pole MCCB With Thermal Magnetic release 309 up to 100 Amp , 10 kA, fixed O/L & fixed S/C setting 310 125 Amp , 25 kA, adjustable O/L & adjustable S/C setting, 311 200 Amp , 25 kA, adjustable O/L & adjustable S/C setting, 312 APFC 313 Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks) conforming to IS:13340-41 /IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min over current capacity 1.8 times rated current & peak inrush current min. 300 times of rated current, llife expectancy greater than 100000hrs(temp class - 25 D)in 440 V/480 V Capacitor and for 525 V should life expectancy minimum 1,65,000 hrs (temp class - 25 D)including making connections, testing etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 314 Heavy dutyThree phase 480 V, 50 Hzcylindrical type capacitor (Bank) 315 Providing & Fixing of IP54 microprocessor based 3 CT’s for all 3 phasesensing compensationpower factor correction relay Size 139mm x 139 mm, Operating Voltage 415/440 V, IEC / EN 61000-6-(2&4)having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall havedigit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485,indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR, RMS Value, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and3 no. Class- 0.5 Cast ResinCT ( refer CT specs in this chapter )for sensing the relay including making coonection with 1.5 Sq.mm copper wire etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR .6 to 8 stage 316 Providing & Fixing of440 Volt 3 pole capacitor(AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current as per PWD specification for electrical Works,IS/IEC 60947-4-1 : 2000, insulation voltage 1000V, impulse withstand voltage 8 KV,Din rail mounting type including making connections, testing etc. as required. suitable for following capacity capacitor bank.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 317 up to 6 KVAR 318 Fire protection work 319 Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC typeFire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 320 2 kg 321 4 kg 322 6 kg 323 Supply & Fixing of CO2 type Fire Extinguisher conforming to IS:15683:2018, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.0 Mtr. Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability,including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 324 Capacity 3.0 Kg. 325 Capacity 4.5 Kg.
|