Tender for electrification work in shooting range at Sukhadia Stadium - 1 SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalisedcubical panel as specifications andOther parameters requiredas per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-(a)Thickness of CRCA sheet shallbe 2.0 mm,cable alley compartments having concealed hinged type doors with key type lock with / withoutdetachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided(b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting,pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel.The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.[c)Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar(>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only.All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar/ Flexible wire for Interconnection between Main busbar and Switchgearis to be Paid Extra ) (d)Wiring between components within switchgear and Incoming / outgoing cableshall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.(e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.(f)Floor mounted panel shall be mounted on Base frame of ISMCchannel size 100 x 50 x 5 mm( to be paid Extra )(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 2 Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwith standard short circuit withstand capacity, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Electrolytic grade Aluminium bus bar 6010 grade 3 Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .Single Phase Ammeter 4 Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .Single Phase Voltmeter 5 Providing & Fixing of BIS approvedCurrent Transformeras per PWD specification for electrical Works ,ISI marked as perIS 2705-1992/ conforming to IEC 60044-1, with secondary terminalof CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as requiredCurrent transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Ring type tape wound CTC T Class 1, Ratio 200/5 to 300/5, Burden 10 VA 6 Providing & Fixing of selector switch of 10 A for voltmeterusing high grade engineering materialto international standards with cam assemblyinsulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour including making connection etc.as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .Voltage Between Phases with OFF ( 4 Position ) 7 Providing & Fixing of CT linked selector switch of 10 AforAmpere meter (4 position )using high grade engineering materialto international standards with cam assemblyinsulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour , including making connection etc.as required .All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 8 Providing & Fixing of110/220 V, unibody LED Indicatinglamp IEC 60947with integral circuit, IP 65 above panel &IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .Red/yellow/Green colour 9 Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006with one sideanti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 3.3 KV,class A 2 mm thick with proof voltage 10 KV AC (rms) and Break Down Voltage 30 KV AC (rms) 10 SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 3 pole MCCB With Thermal Magnetic releaseup to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting, 11 SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 3 pole MCCB With Thermal Magnetic releaseup to 160 Amp , 25 kA, adjustable O/L & adjustable S/C setting, 12 SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 4 pole MCCB With Thermal Magnetic release 250 Amp , 25 kA, adjustable O/L & adjustable S/C setting, 13 Providing & Fixing of ISO certified company made on load change over switch, front handle operated, four pole 415 V as per PWD specificationfor electrical Works conforming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating.Appropriate type test certificate / OEM test report shall be submitted .All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .Open execution type 250 A 14 Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR Single pole MCB (With B/C curve tripping Characteristics)6 A to 32 A rating 15 Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR Triple pole MCB(With B/C curve trippingCharacteristics) 40 A rating 16 Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .3.5 x 120.0 sq.mm 17 Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .3.5 x 185.0 sq.mm 18 Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 1 x 1.5 sq.mm 19 Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 1 x 2.5 sq.mm 20 Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant vergin UV Stabilized Polycarbonatewith brass terminals and captive screws & silver alloy contact tipwith IP-20 rating ,minimum width ofswitch toggle( PUSH PART ) should not less then 20mm,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR 10 A one way switch 21 Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant vergin UV Stabilized Polycarbonatewith brass terminals and captive screws & silver alloy contact tipwith IP-20 rating ,minimum width ofswitch toggle( PUSH PART ) should not less then 20mm,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR 16 A one way switch With LedIndicator 22 Providing & Fixing of modular type lockable feature socket dulymade out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , includingall as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR . 6 A3/5 pin shuttered socket 23 Providing & Fixing of modular type lockable feature socket dulymade out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , includingall as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 6/16 Ashuttered socket 24 Providing & Fixing offollowing size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .3 Module 25 Providing & Fixing offollowing size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .4 Module 26 Providing & Fixing ofWiring Accessories OEM fabricated following size GI box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 27 Providing & Fixing of following modular accessories as per PWD specification for electrical Works,made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR. Blanking plate 28 Providing & Fixing offollowing size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .8 Module 29 Providing & Fixing of IP20, 2"x2" LED Surface/ Recessedmounting Mid power SMD type LED Light fixture not less than 50mm housing depth made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with 4 KV internal/external surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection(Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt ,THD < 10 % , p.f.≥0.95,CRI >80 ,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Surface MoutningMinimum lumen output 4200 lm 30 Providing & Laying XLPE insulated three core ArmouredAluminiumcable for working voltage 11 K.V.(E) confirming IS :7098 P - 2withH4- Grade electrolyticaluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 3 core 185.0 Sq.mm 31 Supply and fixing of LT Distribution Kiosk confirming to IS:13947/1993/ IEC 60947 Pt.3 amended up-to-date and as per DISCOMspecifications made of 2 mm thick powder coated CRCA sheet of 415 volts 3 phase 4 wire triple pole and neutral type, complete in all respect as required. Including Incoming Switch Disconnector Fuse unit, Aluminium Busbar with copper one piece U contacts base, brass studs and nuts, copper busbar for main and interconnection, MS Channel frame of 75 mm x 40 mmgrouted with C.C. of M-10 grade to achieve the height of 1.5 feet above the road level suitable for required no.outgoing. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure "A" attached with this BSR 400 Amp. LT Distribution Kiosk for 250/315 KVA Transformer 32 Plate Earthingas per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying3 to 4 mtr. below the ground level with 20mm dia. G.I. "B" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. and embodying the pipecomplete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 33 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 185.0 Sq. mm. 3.5 core 34 S I T C of star ratedAluminium wound distribution Transformerof following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled & as per BEE star - 1 & BIS approved as per IS 2026- 1977 & lossesas defined as per 2014 (Fourth Revision) Level-1 . including standardaccessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise in winding/oil 35-40 degree C upto 200 KVA & 40-45 degree C for above 200 KVA, ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953, Epoxy based paint,including carrying of pre-commission Testing & Charging of Transformer complete in all respect . The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) including testing from CTLof discombefore charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 160KVA 35 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %,Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810. For additional technical parameters of product / work refer Annexure "A" attached with this BSR 120.0 Sq. mm 3.5 Core 36 Supply and erection of P.C.C. pole as per REC manual no 15/1979 (ammended upto date) and as per latest Discom specifications with factor of safety 2.5including excavation of pit upto pole planting depth 1/6th of pole length. and back filling with stone aggregate/boulders and soil by ramming and watering etc complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 9.0 Mtr long PCC pole of 200 Kg Working Load 37 Supplying and drawing overhead steel core Aluminium conductor (ACSR) ISI marked(IS 398 part II-1996) on existing cross arms through insulator with all necessary T&P required including binding and twisting etc. complete in all respect as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 50 Sqmm of (6+1) 3.35 mm (Insulated Rabbit) for LT 38 Supply and fixing of 100 Amp, 11kV Horn gap fuse set IS 9385 on existing DP structure with 6 nos 24kV/22kV post insulator (IS:5350 part III), hot dipped hard ware,fuse wire of required size etc. complete in all respect as per Discom specification etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 39 Supply and fixing of 11kV, 400 Amp 3 pole, central pot rotating double break type isolator (IS:9921 part I toV) without earth blade operating mechanism with GI spring loaded reverse loop type fixed contact, solid hard drawn electolytic copper tubular moving contact with silver/ nickel plated at end points, 9 nos post insulator of 12 kV (IS:2554 & IS 5350 part III), hot dipped galvanising hard ware, nut, bolts etc complete in all respect as per Discom specification etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 40 Supply and fixing of distribution type Lightening arrestor ( Set of 3 Nos.) 9 kV, 10 kA (IS:3070) with mounting breaking to be installed on existing DP structure etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 41 Supply and fixing Substation structure for mounting 11/0.4 Kv Transformer on Double poleas per DISCOM specification complete in all respect as required including nuts and bolts etc (excluding the cost of poles) made of MS channel of 4 nos 100 x 50 x 6mm and 4 nos 75 x 40 x 6mm and MS flat 50 x 6mm etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 42 P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class750 N,Externally corrugated and having smooth surface insidewith HDPE Coupler, Elbow, Teeat required Depth below the ground for laying cable of followingNominal Outer dia.MFR Test reportfrom NABL accrediated is to be submitted.(Excavation of Earth& Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .160 mm 43 Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95%thimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 8 SWG G.I. ( Hot Dipped) Wire 44 Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kitsuitable for11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streightthrough joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Crosslinking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. includingtesting etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .11 KV End Termination Kit Indoor type3 core 120/150/185 Sq.mm 45 Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kitsuitable for11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streightthrough joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Crosslinking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. includingtesting etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . 11 KV End Termination Kit Outdoor type3 core 120/150/185 Sq.mm 46 Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure "A" attached with this BSR. 2 x 2.5 sq. mm. + 1x1.5sqmm 47 Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure "A" attached with this BSR.2 x 4.0 sq. mm. + 1 x 2.5 sq. mm.
|