Tender For Rates For Material/Equipment Regarding Medical Gas Pile Line System And Modular Operation Theatre For Estimate Preparation. - Rates for Material/Equipmentregarding Medical Gas Pile Line System and Modular Operation Theatre for estimate preparation. 2 Medical Gas Pipe Line (Part-A) 3 Oxygen Manifold 4 SITC of 10 + 10 size main manifold complete with middle frame with chain for individual cylinder along with Non Return Valve for every cylinder.All header racks and cylinder tailpipes should be 230 bar rated. Cylinder header racks for oxygen service shall be provided with connections for bull nose cylinder connections. Cylinder racks shall be manufactured from powder coated steel and shall be designed to securely support cylinders of varying diameters. Tailpipes shall have gas specific connections to the manifold header with threaded connections. Manifold header racks shall incorporate hard-seat, polymer-free non-return integral with each cylinder connection point to maintain system in the event of tailpipe fracture and prevent backflow of gas into the high pressure cylinders. as per specification (Mandatory submission--> 100% technical complaince sheet should be submitted with the technical bid from original manufacturer.)Make- Altos/Aktiv or Equivalent 5 Certifications: ISO 13485:2016,ISO 9001:2015, CE 6 Fully Automatic Oxygen Gas Control System 7 SITC of Fully Automatic Oxygen Control Panel for main Oxygen Manifold having constant flow output of over 2100 LPM or more at 55 to 60 psig Pressure. A test certificate shall be provided with each system detailing the results of the factory tests ,It should have halogen polymers free. It should have Digital 3.5’ colorful display. It should have Integrated & protected test point. Central regulators panel with cylinder headers each side. It should have headers which shall be complete with gas specific cylinder tailpipes. Pre-wired for alarm connection to BMS outputs. All components degreased for oxygen use .Average gas consumption indication (for not liquefied gases). Remaining gas volume indication (for not liquefied gases). It should have general maintenance indicator. It should have Pressure transmitters monitor both banks of cylinders & as per specification. (Mandatory submission--> 100% technical complaince sheet should be submitted with the technical bid from original manufacturer.)Make- Altos/Aktiv or Equivalent 8 Oxygen Flowmeter with Humidifier 9 Essentia medical gas flowmeters are designed to measure and regulate flow.These are calibrated to specific gas & flow range. Oxygen flowmeter is intended for use with various delivery system when bubble/ micro bubble humidifier is attached downstream. These flowmeters are widely used in home care, health centers, district/ general/ regional hospitals, tertiary care, emergency vehicles etc. for administration of supplemental oxygen through nasal cannula, simple face mask,partial rebreathing mask, non re-breather mask, resuscitation mask etc. A passive process to humidify dry therapeutic gas (Category 3 Humidification) Micro Bubble Humidifier for Respiratory Therapy Patient connection port : Tapered hose barb suitable for 6 mm inner diameter plastic tubingMicro bubbles through humidifier for efficient humidificationPossible to integrate into an oxygen concentrator, sleep apnoea therapy equipmentOptimal RH achievable at various flow settingsAutoclavable at 121°C (249.8°F) for 5 minutes (Minimum 5 autoclave cycles)Over pressure safety valveNon-heated and reusableInlet connection port : DISS female adapter with chrome plated Brass nut embedded in ABS for hand-tighteningFlow : Up to 15 lpm @ 4 bar (58 psi)Construction material: Polycarbonate - shatter resistantCapacity - 240ml at max water level (Jar 450ml)Make- Altos/Aktiv or Equivalent 10 Emergency Oxygen Manifold 11 The oxygen cylinder manifold should comprise of two cylinder Banks which can accommodate 6 cylinders in each Bank (means 6+6) complete with copper tail pipes with bull nose fittings of RH External threading suitable for cylinder valves (Oxygen service) and Cylinder support system. Manifold should be suitable to withstand a pressure of 140 Kg/cm2, along with high pressure copper annealed tail pipes with Brass adapter suitable for Oxygen Cylinders and manifold. Top frame comprising of high pressure copper pipes of size 1/2I.D. x 15swg with high pressure brass fittings made of high tensile brass and connections through non- return valves. High pressure copper tail pipes, made of high pressure copper pipe of size 1/4I.D. x 15 swg.The middle and bottom frame to be provided to fit both round and flat bottom cylinders safely. The manifold should be tested (hydraulically) at 250kg / cm sq. The copper tail pipes are fitted to the individual non return valves of the cylinder manifold for easy removal of cylinders without disturbance to system operation. Make- Altos/Aktivor Equivalent 12 Fully Automatic Oxygen Gas Control System 13 SITC of Fully Automatic Oxygen Control Panel for main Oxygen Manifold having constant flow output of over 2100 LPM or more at 55 to 60 psig Pressure. A test certificate shall be provided with each system detailing the results of the factory tests ,It should have halogen polymers free. It should have Digital 3.5’ colorful display. It should have Integrated & protected test point. Central regulators panel with cylinder headers each side. It should have headers which shall be complete with gas specific cylinder tailpipes. Pre-wired for alarm connection to BMS outputs. All components degreased for oxygen use .Average gas consumption indication (for not liquefied gases). Remaining gas volume indication (for not liquefied gases). It should have general maintenance indicator. It should have Pressure transmitters monitor both banks of cylinders & as per specification. (Mandatory submission--> 100% technical complaince sheet should be submitted with the technical bid from original manufacturer.)Make-Altos/Aktiv or Equivalent 14 MEDICAL NITROUS OXIDE SYSTEM 15 Nitrous Oxide Manifold 16 SITC of 4 + 4 size main manifold complete with middle frame with chain for individual cylinder along with Non Return Valve for every cylinder.All header racks and cylinder tailpipes should be 230 bar rated. Cylinder header racks for oxygen service shall be provided with connections for bull nose cylinder connections. Cylinder racks shall be manufactured from powder coated steel and shall be designed to securely support cylinders of varying diameters. Tailpipes shall have gas specific connections to the manifold header with threaded connections. Manifold header racks shall incorporate hard-seat, polymer-free non-return integral with each cylinder connection point to maintain system in the event of tailpipe fracture and prevent backflow of gas into the high pressure cylinders.. as per specification.(Mandatory submission--> 100% technical complaince sheet should be submitted with the technical bid from original manufacturer.)Make-Altos/Aktiv or Equivalent 17 Fully Automatic Nitrous Oxide Gas Control System 18 SITC of Fully Automatic Control Panel for Nitrous Oxide having constant flow output of over 500 LPM at 4.2 Bar Pressure. Digital Fully Automatic Control Panel. It should fully complies and meets with the requirements of the NFPA-99 standards. It should be UL or ETL Listed. The manifold control panel shall consist of two bank regulators (dome bias) used to reduce the cylinder pressure to the two line regulators which in turn controls the final line pressure. The manifold has an intermediate and line relief valve that is internally connected to a common vent port, terminating into a 1/2" FNPT pipe. It should be fully automatic type and shall switch from “Bank in Use” to “Reserve Bank” without fluctuation in the final line pressure. After the switchover, the “Reserve Bank” shall then become the “Bank in Use” and the “Bank in Use” shall become the “Reserve Bank.” The control panel includes a line gauge, two bank gauges and incorporates six LED’s: two green for “Bank in Use,” two yellow for “Bank Ready” and two red for “Bank Empty” on the front of the cabinet. Input power to the manifolds is 110 to 240 VAC, 50-60 Hz& as per specification. (Mandatory submission--> 100% technical complaince sheet should be submitted with the technical bid from original manufacturer.)Make- Altos/Aktiv or Equivalent 19 Emergency N2O System 20 SITC of 2 Cylinder Emergency Nitrous Oxide manifold with All header racks and cylinder tailpipes should be 230 bar rated. Cylinder header racks for oxygen service shall be provided with connections for bull nose cylinder connections. Cylinder racks shall be manufactured from powder coated steel and shall be designed to securely support cylinders of varying diameters. Tailpipes shall have gas specific connections to the manifold header with threaded connections. Manifold header racks shall incorporate hard-seat, polymer-free non-return integral with each cylinder connection point to maintain system in the event of tailpipe fracture and prevent backflow of gas into the high pressure cylinders using a high flow Preset Pressure Regulator as per specification.(Mandatory submission--> 100% technical complaince sheet should be submitted with the technical bid from original manufacturer.)Make- Altos/Aktiv or Equivalent 21 MEDICAL CARBON DIOXIDE SYSTEM 22 CARBON DIOXIDE SYSTEM 23 The CO2 cylinder manifold should comprise of two cylinder Banks which can accommodate 4 cylinders in each Bank (means 4+4) for cylinder valves conforming to IS 3234 (CO2@ service) complete with copper tail pipes with fittings. Manifold should be suitable to withstand a pressure of 140 Kg/cm2, along with high pressure copper annealed tail pipes with Brass adapter suitable for Nitrous Cylinders and manifold. Top frame comprising of high pressure copper pipes of size 1/2I.D. x 15swg with high pressure brass fittings made of high tensile brass and connections through non- return valves.High pressure copper tail pipes, made of high pressure copper pipe of size 1/4I.D. x 15 swg.The middle and bottom frame to be provided to fit both round and flat bottom cylinders safely. The manifold should be tested (hydraulically) at 250kg / cm sq. The copper tail pipes are fitted to the individual non return valves of the cylinder manifold for easy removal of cylinders without disturbance to system operation. Each manifold should be provided with one terminal header and a NPT connection for the Automatic control panel. Make- Altos/Aktiv or Equivalent 24 Certifications: ISO 13485:2016,ISO 9001:2015, CE 25 Fully Automatic Carbon DioxideGas Control System 26 SITC of Fully Automatic Control Panel for Carbon dioxide having constant flow output of over 500 LPM at 4.2 Bar Pressure. Digital Fully Automatic Control Panel.The manifold control panel shall consist of two bank regulators (dome bias) used to reduce the cylinder pressure to the two line regulators which in turn controls the final line pressure. The manifold has an intermediate and line relief valve that is internally connected to a common vent port, terminating into a 1/2" FNPT pipe. It should be fully automatic type and shall switch from “Bank in Use” to “Reserve Bank” without fluctuation in the final line pressure. After the switchover, the “Reserve Bank” shall then become the “Bank in Use” and the “Bank in Use” shall become the “Reserve Bank.” The control panel includes a line gauge, two bank gauges and incorporates six LED’s: two green for “Bank in Use,” two yellow for “Bank Ready” and two red for “Bank Empty” on the front of the cabinet. Input power to the manifolds is 110 to 240 VAC, 50-60 Hz& as per specification. (Mandatory submission--> 100% technical complaince sheet should be submitted with the technical bid from original manufacturer.)Micro processor controlled switch-over is accomplished automaticallyAutomatically resets itself for next cycle when depleted bank is replenished. No manual resetting requiredDigital pressure indication for accurate readingPressure unit options: bar, psi & kg/cm Status indicatorsPressure Stabilizer for stable discharge pressure & flowVisual & Audible signalDesigned to suit CO2 for gas specific usageOptimized residual gasMake-Altos/Aktiv or Equivalent 27 Emergency CO2 System 28 The Emergency supply manifold shouldbe connected to downstream of the manifold control panel.The assemblyshould consist of 2 (two) cylinders connection supplying a manually adjusted regulator via a common header assembly. The delivery system is isolated from the main system by an isolation valve. Pressure gauges should indicate cylinder and delivery pressure & valves conforming to ISO 13485Make- Altos/Aktiv or Equivalent 29 MEDICAL VACUUM SYSTEM 30 SITC of MEDICAL VACUUM SYSTEM AS PER SPECIFICATION 31 Vacuum Pump : The arrangement should consist of 2 nos. of oil lubricated imported rotary vane vacuum pump. Each vacuum pump should have capacity of 5000 lpm with IEC Motor rating of minimum 10 HP @ 50 Hz or above. Vacuum pumps shall comprise of air cooled, oil lubricated rotary vane vacuum pumps suitable for both continuous and frequent start / stop operation at inlet vacuum vessels between 525 mm Hg and 700 mm Hg. The ultimate vacuum of pump shall be 0.1 mbar with gas ballast valve closed. The Vacuum Pump should be air cooled and oil lubricated rotary vane vacuum pumps designed for use in the field of high quality vacuum. It should be a robust construction, reliable operation, highly resilient carbon composite fiber vanes, Gas ballast valve. The pump should be having a 4 barriers system that avoids any oil leaks by doubling the 2 lip / shaft seals. Pump vanes shall be lubricated by a fully re-circulated and filtered lubricant supply. Also Pump design should include a lubricant separation system integral to the pump exhaust box consisting of no less than four stages of internally installed lubricant and smoke eliminators through which the exhaust gas stream must pass. This system shall consist of bulk separation, lubricant mist elimination, smoke elimination, synthetic lubricant baffle, and shall be capable of removing 99.9 percent of all lubricant and smoke particles from the exhaust gas stream. The unit should have extremely low vibration as per specification.(Mandatory submission--> 100% technical complaince sheet should be submitted with the technical bid from original manufacturer.)Make- multitech/hitachi/Anistaiwata or Equivalent 32 Vacuum Tank of 5000 liters water capacity.Make- multitech/hitachi or Equivalent 33 Bacterial Filter:Vacuum Filter (Bacteria Filter) of 100 cfm to 105 cfm – 3” Filter housing with drain flask.: It fully complies and meets with requirements of UK HTM medical standards. It should have BS 3928 sodium flame test certificate based on requirements of HTM standards.The bacteria filter should be designed for critical application involving removal of dry and wet dust, particulars, oil aerosol and water droplest, high efficiency glass fiber, fieece media from suction side of vacuum pump system. It should have efficiency of at least 99.995% when tested by sodium flame test and that should be according to BS 3928:1969. The Vacuum filtration efficiency should be in excess of 99.9999% as per HTM0201 & AS 2896 standards. The high efficiency medical grade filter element should have custom engineered filter media and deep pleat element technology provides minimal pressure loss and filtration efficiencies. It should have advanced filtration technology for Low pressure loss borosilicate glass microfiber-media and open cell reticulated foam pre-filtration layer captures particulates, bacteria and liquid aerosols reducing energy consumption and overall system costs. It should have corrosion protection Internal and external electrophoretic painting followed by a tough exterior polyester powder coating.It should have easily removable sterilisable drain flask and differential pressure monitor gauge. It should have push fit element design for quick and easy maintenance with unique push fit element design. It should have element end cap color black. It should have maximum temperature 60 degree centigrade (140 degree F). It should have element of E31140MV grade. It should have pipe size connection 1” = 105scfm and 180nm3/hr FAA. It should have pressure loss clean & dry = < 3kPa (30m/bar/0.44psig). It should have maximum working pressure 0.5barg(7psig. It should have manual drain valves and 250ml sterilisable glass drain flasks.(Maximum tolearance allowed will be only 10%).Smooth mobility.Sturdy trolley mounted on 5 castor base wheels.Operational when connected to centralized vacuum.Fast connection to the vacuum source.Various Vacuum Connector options.Controllable & Stable vacuum for procedure.Step-less vacuum regulation within the range.Gauge needle with anticlockwise movement .Vacuum trap with bacterial filter in series to protect.system networkDisposable hydrophobic filter element.Quick hassle-free replacement of bacterial filter.Switch toselect collection jar & quicksuction shut-off.Easy access to selector switch.90 degree angular interface connectors to push-fit catheters.Autoclavable Polycarbonate collection jars.Overflow prevention trap on each collection jar.Make- Tridentor Equivalent 34 Ward Vacuum Unit with Regulator, Collection Jar of 1000 ml with Bracket.Make- Altos/Aktiv or Equivalent 35 Theatre Vacuum Unit mounted on Trolley consisting of Vacuum Regulator with Gauge and 2 nos. of 4000 ml Polycarbonate.Make- Altos/Aktiv or Equivalent 36 Bacteria Filter (Plastic) for 100 ml Safety Trap before Vacuum RegulatorMake- Altos/Aktiv or Equivalent 37 COMPRESSED AIR SYSTEM 38 SITC of COMPRESSED AIR SYSTEM AS PER SPECIFICATION 39 Oil Free Scroll Air Compressor: The arrangement should consist of 2 nos.oil free scroll air compressor. It should be rated for 50 Hz, 3 Phase, 415 VAC power supply. Motor rating of each compressor should be 22 Kw & 30 Hp. Each scroll compressor should have a flow capacity of minimum 73 cfm (2070 LPM). The scroll air compressors shall be air cooled. Compressors shall be oil free scroll compressors suitable for both continuous and frequent start/stop operation having outlet pressure control range of 800 to 1000 kPa (8 to 10 bar). Each compressor shall have at least two individual scroll elements. The air quality shall be 100% oil free, certified ISO8573-1. The compressor shall have a sound insulating enclosure. Each scroll air Compressor should have an element consists of a fixed scroll shaped housing and a scroll shaped rotor. Air enters the compressor element through inlet opening. Once the air is drawn in, the orbiting scroll seals the inlet opening and forces the air into a continuously decreasing space. As scroll keeps orbiting, this process of compression is constantly repeated, resulting in discharging of oil free compressed air through outlet opening. Air is drawn through air filter and should be compressed by the compressor element of each compressor module. The compressed air is discharged via the check valve and a common air cooler. The cooling air is blown over the compressor element via a duct. A separate electric fan provides cooling air for the common air cooler. Each set of compressor modules has its own common aftercooler with an electric fan. The separator on compressors without integrated dryer has an automatic condensate outlet and a manual drain valve. The air compressors with integrated dryer, the dryer is equipped with a trap with an automatic condensate outlet and a manual drain valve. Each compressor element is protected by a sensor in the outlet pipe. The sensor is connected to the electronic regulator. Make- multitech/hitachi/Anistaiwata or Equivalent 40 Air Receiver of 5000 Liter Water Capacity (designed to withstand pressure of 10 Bar) with Auto Drain ValveMake-multitech/ hitachi or Equivalent 41 Medical Breathing Air Dryer- 375 SCFM - Medical air dryer heatless with purification modules are intended to provide a continuous supply of medical quality air conforming to the European Pharmacopoeia medicinal air monograph (ref. 1238), for respiratory use in healthcare facilities. The system shall be duplex such that the supply is maintained in single fault condition. Medical compressors shall be provided such that the specified volumetric flow is achieved without standby or backup systems running. Purification Module : The duplexed filter and dryer module shall incorporate high efficiency oil coalescing filters, heatless regenerative desiccant dryers, activated carbon filters and bacterial filters. The performance of the filters shall be according to below specifications: Oil coalescing high efficiency filter: mass efficiency of 99,92%, tested according to ISO 8573-2 & ISO 12500-1; Activated carbon filter: max remaining total oil content of 0,003 mg/m³, tested according to ISO 8573-5 & ISO12500-2;Bacterial filter: particle count efficiency of 99,98% at MPPS=0.06μm, tested according to ISO 12500-3. Dryer Purge Control : The dryer control system shall incorporate a Purge Saver Energy Management system that freezes the regeneration of the desiccant once adequate dew point is reached in the inactive tower. Only when the dewpoint level in the active tower deteriorates to an unacceptable level will the intelligent controller switch towers.Coarse coalescing filter of 375 SCFM (one working and one as stand by) flow capacity: It should have flow-optimized design for advanced filter head design for optimized flow performance. It should have flexible installation Modular design and accessible fixings enable simple close coupling assembly. It should comply with air quality standard ISO 8573-1: 2010. It should have profiled bowl design and push fit elements ensure quick and for reliable maintenance. It should have corrosion protection Internal and external electrophoretic paint finish followed by a tough exterior polyester powder coating. It should have color coded element end caps of red color for easy and accurate grade identification. It should have element of E30612 grade.It should have particle retention of up to 99.999%, and significantly reduced pressure loss. It should have particle removal 1 micron. It should have maximum particle size class 2 micron as per ISO 8573-1: 2010 . It should have maximum oil content 3 micron ISO 8573-1: 2010.It should have maximum oil carryover at 68 degree F (20degree centigrade) = 0.3ppm (0.3mg/m3). It should have pressure loss clean & dry = 0.8psi (55m/bar). It should have pressure loss saturated = 1.8psi (125m/bar). 42 Fine coalescing filter of 375 SCFM (one working and one as stand by) flow capacity : It should have flow-optimized design for advanced filter head design for optimized flow performance. It should have flexible installation Modular design and accessible fixings enable simple close coupling assembly. It should comply with air quality standard ISO 8573-1: 2010. It should have profiled bowl design and push fit elements ensure quick and for reliable maintenance. It should have corrosion protection Internal and external electrophoretic paint finish followed by a tough exterior polyester powder coating. It should have color coded element end caps of blue color for easy and accurate grade identification. It should have element of E30612 grade.It should have particle retention of up to 99.999%, and significantly reduced pressure loss. It should have particle removal 0.01 micron. It should have maximum particle size class 1 micron as per ISO 8573-1: 2010 . It should have maximum oil content 1 micron ISO 8573-1: 2010.It should have maximum oil carryover at 68degree F (20degree centigrade) = 0.01ppm (0.01mg/m3). It should have pressure loss clean & dry = 1.2psi (85m/bar). It should have pressure loss saturated = 1.8psi (125m/bar). Activated Carbon Filter of 375 SCFM (one working and one as stand by) flow capacity: It should have flow-optimized design for advanced filter head design for optimized flow performance. It should have flexible installation Modular design and accessible fixings enable simple close coupling assembly. It should comply with air quality standard ISO 8573-1: 2010. It should have profiled bowl design and push fit elements ensure quick and for reliable maintenance. It should have corrosion protection Internal and external electrophoretic paint finish followed by a tough exterior polyester powder coating. It should have color coded element end caps of black color for easy and accurate grade identification. It should have element of E30612 grade.It should have particle retention of up to 99.999%, and significantly reduced pressure loss. It should have particle removal 0.01 micron. It should have maximum particle size class 1 micron as per ISO 8573-1: 2010 . It should have maximum oil content 1 micron ISO 8573-1: 2010.It should have maximum oil carryover at 68degree F (20degree centigrade) = 0.003ppm (0.003mg/m3). It should have pressure loss clean & dry = 1.7psi (115m/bar). 43 Fine Dust Filter of 375 SCFM (one working and one as stand by) flow capacity : It should have flow-optimized design for advanced filter head design for optimized flow performance. It should have flexible installation Modular design and accessible fixings enable simple close coupling assembly. It should comply with air quality standard ISO 8573-1: 2010. It should have profiled bowl design and push fit elements ensure quick and for reliable maintenance. It should have corrosion protection Internal and external electrophoretic paint finish followed by a tough exterior polyester powder coating. It should have color coded element blue color end caps for easy and accurate grade identification. It should have element of E30612 grade.It should have particle retention of up to 99.999%, and significantly reduced pressure loss. It should have particle removal 0.01 micron. It should have pressure loss clean & dry = 1.5psi (100m/bar). Make- Trident or Equivalent 44 Pressure Reducing Station for 4 Bar: The compressed air system shall be supplied with duplex pressure regulator arrangement to regulate the line pressure from 10 bar to 4 bar for medical air. Adequate number of isolation valves should be provided to isolate each regulator separately during maintenance without shutting down the entire compressed air system. Presssure Regulators should be 28 bar rated. Brass pressure relief valve, 1/4" thread BSP should be provided after the regulator. Pressure Gauge of range 0 to 11 bar to be provided to monitor line pressure. Relief Valve Settings : Nominal 4 bar stations - 5.5 bar relieving.The Pressure Reducing Station should be capable of delivering minimum 10000 LPM flow.It shall be duly CE marked to the Medical Device Regulations and under this regulations, med gas products are classified as Medical Devices. 45 Pressure Reducing Station for 7 Bar: The compressed air system shall be supplied with duplex pressure regulator arrangement to regulate the line pressure from 10 bar to 7 bar for surgical air. Adequate number of isolation valves should be provided to isolate each regulator separately during maintenance without shutting down the entire compressed air system. Presssure Regulators should be 28 bar rated. Brass pressure relief valve, 1/4" thread BSP should be provided after the regulator. Pressure Gauge of range 0 to 11 bar to be provided to monitor line pressure. Relief Valve Settings : Nominal 7 bar stations - 9 bar relieving.The Pressure Reducing Station should be capable of delivering minimum 4000 LPM flow.It shall be duly CE marked to the Medical Device Regulations and under this regulations, med gas products are classified as Medical Devices. 46 SITC of Medical Gas Outlets- 47 Probes are crucial for gas specific and stable connection. These are used to connect medical gases and vacuum devices to outlets / terminal units of MGPS distribution network.Make- Altos/Altos/Aktiv or Equivalent 48 FeaturesSmooth quiet action.Safe keying configurations.Gas specific ISO 32 colour coding.Firm locking of connector / probe.Strong, positive and secure connection.Corrosion-free and material compatibility.Reliable and safe dispense of gases & vacuum.Pipe stub end flared to align drop pipe and to avoid butt joint. 49 Oxygen 50 Air-4 51 Air-7 52 N2O 53 AGSS 54 Vacuum 55 CO2 56 Certifications:ISO 13485:2016 – Medical devices,ISO 9001:2015 57 MISCELLANEOUS ITEMS 58 SITC of Common Electrical Control Panel for Compressed Air System, Vacuum System & AGSS as per requirementcomplete with plant room wiring. 59 SITC of Degreased Medical Grade Copper Pipe as per EN 13348 :2018. BSI Kite Mark certified. CE Certified. Third Party Inspection by TUV or Lloyds Registrara AsiaMake- Altos/Altos/Aktiv or Equivalent 60 Installation of piping should be carried out as per international standards with utmost cleanliness. Only pipes, fittings and valves which have been degreased as per International standards should be used . Pipe fixing clamps for upto 28mm diameter. Pipes should be non ferrous suitable for the diameter of the pipe. For the pipes of the sized above 28mm rigid metallic hanging or cemented supports to be used. 61 The main lines to the building to be taken overhead through metallic poles or through underground ductswith inspection removable slabs,All pipe joints should be made using inert gas fluxless brazing method.Alljoints should be of copper to copper and should be brazed by silver brazing filler material without flux while being brazed joints shall be continuously purged with oil free dry nitrogen to prevent the formation ofcopper oxide on the inside surface of the joint.All pipes should be installed without springing or forcing.All pipes shouldprotected against mechanical injury in a manner satisfactory to authorities havingjurisdiction. 62 Test: After erection, all the new pipes cleaned or purged with the help of dry nitrogen gas.Complete system should be tested with dry nitrogen at 2 times of working pressure for 24 hours. 63 Painting: All existing and proposed exposed pipes/should be painted with two coats of Synthetic enamel paint & color codification as per international standards.All concealed pipes to have gas identification bands / labels at appropriate distance.Similarly all pipes which need embedding in the wall should be tested/painted/labeled and properly insulated. 64 Solid drawn, seamless, deoxidized, non arsenical, half hard, tempered and degreased materials conforming to BS: EN 13348. 65 All copper pipes will beUL certified for medical use before dispatch and the pipe will be delivered plugged or capped at both ends. 66 108 mm OD X 1.5 mm thick 67 76 mm OD x 1.5 mm thick 68 54 mm OD x 1.2 mm thick 69 42 mm OD x 1.2 mm thick 70 35mm OD x 1.2mm thick 71 28 mm OD x 1 mm thick 72 22 mm OD x 1 mm thick 73 15 mm OD x 1 mm thick 74 12 mm OD x 0.7 mm thick 75 SITC of Medical Gas Digital Area Alarm System 76 Microprocessor based digital LCD alarmHighly visible 7" (178 mm) LCD screenPressure sensing through piezoresistive sensing technologyAlarms can be monitored audio-visualTouch screen operationComprehensive monitoring of all the medical gas alarm panelsData display at a central monitoring station Features-Alarm status will be visible through ethernet port on master alarmPressure Equipment Directive 2014/68/EUDigital Flow Care Alarm Management of Medical Gas Pipeline SystemReal time updating of statusOperational parameters i.e. high and low level canbe set “in-situ” to suit requirement in an area 2Programmable pressure unit display (bar, kg/cm & mmHg)Audio mute optionDesigned to serve 2, 3, 4, 5 & 6 gases including VacuumNIST connection for Gas inputPowered by 220V AC to 24V DC external adapterMake-Altos/Aktivor Equivalent 77 Conforms to: IS / ISO 7396 - 1 : 2016 + A1 : 2017HTM 02-01 Part A, IS / ISO IEC 60601 - 1 : 2015 + A1 : 2020Certifications:ISO 13485:2016 – Medical devices – Quality Management SystemsISO 9001:2015 - Quality Management Systems 78 6 - Gas (O2, N2O, Med Air-4 Bar, S Air-7 Bar, Vacuum & CO2) 79 5 - Gas (O2, N2O, Med Air-4 Bar, S Air-7 Bar & Vacuum) 80 4 - Gas (O2, N2O, Med Air-4 Bar & Vacuum) 81 3 - Gas (O2, Med Air-4 Bar & Vacuum) 82 2 - Gas (O2 & Vacuum) 83 SITC Of Area Valve Service Unit with Valve & Gauge 84 The importance of full bore ball valves is to reduce pressure drop to almost negligible in the pipeline distribution system so that the designed pressure is available at the outlet point. Ball Valves are used to start or stop a flow. In Medical Gas Pipeline System (MGPS), the valves are normally kept open i.e. allow the gas to flow unless it is required to shut-off the gas supply for scheduled maintenance or emergency situation 85 Features-Operational parameters can be set in-situDigital pressure unit display options -psi / bar or kg/cmDigital & illuminated LED display of “Normal”, “High” & “Low”Microprocessor based moduleHighly accurate “Heavy Duty” pressure transducerPowder coated aesthetically designed enclosureEnclosure separable from the base for ease of installationReusable lock assemblyAudio mute optionPED: 2014/68/EU certified full port Ball Valve (PN 30)Long extension copper pipes to connect MGPS networkFront door opens up vertically for comfortable accessDesigned to serve 2, 3, 4 & 5 gas moduleSuitable for all medical Gases & VacuumMake- Altos/Aktiv or Equivalent 86 6 Gas Service (O2, N2O, Med Air-4 Bar,Air-7 Bar, Vacuum & CO2) 87 5 Gas Service(O2, N2O, Med Air-4 Bar, Air-7 Bar & Vacuum) 88 4 Gas Service(O2, N2O, Med Air-4 Bar & Vacuum) 89 3 Gas Service (O2, Med Air-4 Bar & Vacuum) 90 2 Gas Service(O2 & Vacuum) 91 SITC of Degreased Medical Lockable Ball Valve with Pipe line assembly 92 Pre piped single port) for size upto 2" (for 54mm copper pipe): Pre Piped Degreased Ball Valve with pipe extension. It should be full-port design. It shouldbe blow-out proof stem. It should be lockable valve. The Valve shall be 3 piece ball-type design with a bronze body and chrome plated brass ball for sizes 1/2” to 4”. Seats shall be Teflon (TFE) and seals Viton for 1/2” - 4” valves. A blow-out proof stem shall be used and the valve shall have a maximum pressure rating of 600 psi [4,137 kPa].Valves shall be operated by a lever-type handle requiring only a quarter turn from a fully open position to a fully closed position. Valves shall be designed in such a manner that it can be “swung-out” during installation so as to prevent damage due to heat transfer during the brazing operation. Each valve assembly shall be washed and degreased for medical gas service. The valve shall be supplied in a sealed plastic bag to prevent contamination prior to installation.Make- Altos/Aktiv or Equivalent 93 12mm 94 15 mm 95 22 mm 96 28 mm 97 35mm 98 42 mm 99 54 mm 100 108mm 101 SITC of Bed Head Panel aluminum powder coated with mininum 3 channel and 3 duct with separate partition rows and built in aluminum railMake- Altos/Aktiv or Equivalent 102 Bedhead panel for Low Equity Ward Areas, 1500mm length, with provision of Gas outlets & provided with electrical sockets & accessories complete 103 Horizontal Bed Head Panel – For 2 Gas Service (Oxygen & Vacuum) 104 Horizontal Bed Head Panel – For 3 Gas Service (Oxygen, Med Air-4 Bar & Vacuum) 105 Horizontal Bed Head Panel – For 3 Gas Service (Oxygen, N2O & Vacuum) 106 Horizontal Bed Head Panel – For 4 Gas Service (Oxygen, N2O, Med Air-4 Bar & Vacuum) 107 Special FeaturesInnovative design – Efficient, simple & accessibleVersatility – Configurable & economic adaptation of various servicesAesthetics – High quality surface finish, epoxy coated to RAL 7035(Textured)Smooth profile – Minimize adherence of dust particlesExtruded aluminium frame – Rigidity & ease of interior accessability to serviceSeparate compartments - for LV, ELV and Piped GasNon-disruptive maintenance of BS Outlet - Shut down of line gas is avoidedOption of concealed gas connections and choice of outlet 108 Application AreasInnovative design – Efficient, simple & accessiblityVersatility – Configurable & economic adaptation of various servicesAesthetics – High quality surface finish, epoxy coated to RAL 7035(Textured)Smooth profile – Minimize adherence of dust particlesExtruded aluminium frame – Rigidity & ease of interior accessability to serviceSeparate compartments - for LV, ELV and Piped GasNon-disruptive maintenance of BS Outlet - Shut down of line gas is avoidedOption of concealed gas connections and choice of outletAdult in-patient wards/ General WardsResuscitation RoomsPost-anaesthesia areaEmergency Admission WardsDialysis Stations 109 Configuration : 5 Outlets & 6 Multi Standard 220V AC sockets, 1 each RJ11 Telephone socket & RJ45 Data Socket and provision of protective earth (Earthing) 110 Modular Operation Theatre (Part-B) 111 WALL AND CEILING MODULAR PUF PANEL 112 The panels shall be made of durable and uniform material that shall be easy to clean and extremely hygienic. Operation theatre shall not have any sharp edges, corners and shall not support bacteriological or fungicidal growth and shall be resistant to most chemicals, commonly used in Hospital Departments. Joints in the panels in the operation theatre shall be sealed. The function of sealing shall assure an airtight environment in the room and eliminate services to prevent dust accumulation.PUF Panel with an overall thickness of 50 mm for wall and 30 mm for ceiling, made of 0.8mm (make-Tata/jindal)GI Front sheet and 0.6mm PPGI back wall with infill of PUF at 40 kg/m3 (40D)which is necessary for mechanical strength. Panels shall be mounted on a structure made of galvanized steel and shall enable the distribution of medical gases, electricity, sewerage inside the wall.PUF Panel as above has better thermal efficiency and thus saving on energy cost. Proposed system shall be installed at site without any welding.The partitions shall not have corners; adjacent surfaces shall be molded flush.Upper wall element shall have sufficient height to reach the lower edge of the prefabricated ceiling. All the sharp edges and corners should be chamfered to avoid bacterial contamination.The individual ceiling panels shall use the tongue and groove technology for joining two panels, no welding shall be allowed,provides a seamless sub-structure, which is then sanded smooth finished with Metal Putty and then painted using imported anti-fungal paint to give a smooth, non-porous seamless finish and without corners by providing coving on floor as per standard.It is resistant to chemicals used in Operation Room for moping and fumigation repeatedly.Make-Jindal/Tata or Equivalent 113 WALL AND CEILING MODULAR PUF PANEL-SS304 114 The prefabricated Operating Room should be of SS Sandwich as per its latest standards. SS Sandwich : It should have at least min. 0.8 mm 304 Grade Stainless Steel on front side and 0.5mm PPGI back side . The sandwich panel shall have a core consisting of rigid polyurethane foam, injected under high pressure, with a minimum density of 40 kg/m3. Cladding structure insulated stainless steel wall panels with total panel thickness 50 mm for wall and 30mm for ceiling.The individual wall panels shall use tha tongue and groove technology for joining two panels, no welding should be allowed. The gaps between panels shall be suitably filled with metal filler and sanded flush. Stainless steel plate finished to fine grain surface, treated properly to take antifungal paint panelingshould be easy to maintain, durable, antistatic / conductive and fire retardant. Clearance between inner panel and outer wall should be sufficient to allow the maintenance personnelfor service. This closed space should be flushed continuously to eliminate dust and bacterial accumulation.It should have minimum number of junctions. The junction should be seamless and should be sealed with suitable sealants. Third party test certificate for SS from material testing lab. (Govt. authorized)required.Make-Jindal/Tata or Equivalent 115 ANTI-FUNGAL PAINTING 116 Anti microbial Paint for Different Areas antibacterial Paint on wall and ceiling panels Inside OT work.Anti-Microbial Protection: These product hygiene coatings start the biocidal action as soon as the microorganism land on the surface, and prevents the growth of mould, bacteria and yeasts for at least 5 years.Minimum three coats of Anti Fungal/Bacterial Paint, glaze or equivalent to a minimum dry thickness of 300 microns to give smooth , non-porous finish without any corners.It will also be resistant to the chemicals used in Operation Room for Moping & Fumigation repeatedly. This Hygiene coating are independently tested by leading universities to demonstrate resistance.Make-SKK/ Jotun or Equivalent 117 PLENUM LAMINAR AIR-FLOW 118 Supply and installation of Plenum LAMINAR FLOW- Plenum Box Ceiling mounted systemwith unidirectional airflow, SPECIFICATIONS-PLENUM UNIT - The complete unit factory designed and manufactured with proper air-sealing. It seamlessly integrates with OT ceiling mounted equipment.Plenum size- 2400 x 2400mm with aluminium material.Diffusers are made of SS304 punched/perforated sheet for unidirectional diffusion air. The complete unit factory designed and manufactured with proper air-sealing.It seamlessly integrates with OT ceiling mounted equipment.The material used is non-corossive as per standard guidelines such as Aluminium.Make-Jindal/Tata or Equivalent 119 Hepa Filters- 120 The filter hosing on either side houses provided with HEPA minipleate H13/H14 filters.The system has a reliable filter efficiency, filters are designed to remove particles and germs with the use of H13/H14 filters retaining 99.97 % of the particles and germs.Frame : Aluminium Mini Pleat Size- 610x610x125mmMOC of the Media : Micro Fibre Glass micro drawn grid Separators : continuous Gasket: Food GradeMPPS average efficiency: > 99.95% 3 Micron D Efficiency: 99.97% down to 0.3µ.Maximum Operating Temp : 60 degree CelsiusMake- Thermadyne or Equivalent 121 ANTI-STATIC VINYL FLOORING: 122 SupplyandinstallationofImportedVinylFloor:SeamlessantistaticconductiveESDvinylflooringsystem,2mmthick, with perfectly curved flush covings and copper strips for earthing, all joints welded properly including wall scatting.SPECIFICATIONS:- Flooringinoperationtheaterroomwii beseamless withperfectly curvedflash-covings,resistance tomechanicalstressanddynamicloadsandhavingESD/EMI(Conductive)protectioncharacteristics,2mmthick, washablevinyl.Flooring is a static-conductive,flexible homogeneousvinyl floor covering withan electricalresistance of 5x10^4 123 SELF LEVELLING MATERIAL. 124 The SLC should be of Portland cement-based, It should be self-leveling underlayment formulated with a special blend of polymersusedtolevelandsmoothinteriorconcrete,terrazzo,ceramicandquarrytile,epoxycoatingsystems,metal andnon-watersolubleadhesiveresidueonconcretepriortotheinstallationoffinishedflooring–on,aboveorbelow grade.TheSLCshouldprovideadurable,flat,smoothfloor surfacewithminimumlabor andinstallationtime.Itshould be pourable or pump-able when mixed with water and should seek its own level to produce a smooth, flat, hard surface. 125 OPERATION THEATRE CONTROL PANEL: 126 Supply and installation of Membrane type 6 services OT control panel , with distribution box mounted flush in the theatre wall, comprising of the following:The surgeon control panel should meet Electrical safety codes for high & low voltage system, wired to the current IEE regulations.The room Surgeon’s control panel should be modifiable with changing technology& equipment in operating environments. Control Panel will be user friendly & ease of operating & maintaining purpose.he panel should be “Membrane” type; configured to incorporate all the services that operation room staff required. The fascia should be made with superior quality UV resistance membrane with sterilization feature.The Panel should contain 6 or 9 service tiles as below:1. Time Day Clock. 2. Time Elapse Day Clock. 3. General Lighting System.4. Medical Gas Alarm Panel. 5. Hand Free Telephone set with memory.6. Temperature & humidity indicator with controller.7. HEPA Filter Status module. 8. Room Pressure Indicator. 9. Music control. Time day clock should be digital type & clocks having high brightness characters. Time Elapsed Day Clock should be digital type & clocks having high brightness characters.Temperature indicator should indicate the room temperature which should be connected to the local pressure switches of Air-Conditioning System. Indicators should be digitaltype & clocks having high brightness characters, not less than 30 mm in height. Central Lighting system should incorporate all the necessary controls of the lighting. system inside the theatre.The medical gas alarm should indicate High, Normal & Low gas Pressure for each gas service present in the operating system & should have an audible buzzer with mute facility. Pressure sensors should be connected to MGPS for monitoring the pressures.A hand free set Telephone System should be incorporated in the panel with memory type card.The control panel should be designed for front- access only. All internal wires should beMake- Altos/DGline or Equivalent 127 Distribution Board outside OT 128 Electrical Distribution Board will have all high voltage equipment should be installed in a separate enclosure. The remote cabinet should house the operating transformers, light control relays, electrical distribution equipment and circuit protection equipment for all circuits withinthe operating theatre. All internal wiring should terminate in connectors with screw mounted, on a DIN rail. Individual miniature circuit breakers will protect all internal circuits. All high voltage equipment should be installed in a separate enclosure.All internal wiring should terminate in connectors with screw & clamp springConnections of the clip- on type mounted, on a CE/ / ICMED9001/ ICMED13485 approved rail & labeled with indelible proprietary labels.Individual fuses or miniature circuit breakers should protect all internal circuits. 129 LED PERIPHERAL/GENERAL LIGHTS: 130 Recess mounted sealed IP54 Protocol, non-hygroscopic peripheral lights ( 1" x 2" ) having compact high glow low wattage LED lighting system. These lights are having electrical safety code for high & low voltages.The luminaries for recess mounting in operation theatres should flush with the ceiling based on LED, with optical anti- glare system for individually adjustable light distribution.Luminaries cover made of highly-resistant, disinfectant-proof acrylic diffuser with white coated steel frame.Closing devices are integrated automatically in the electrical safety control without lines having to be connected to the luminaries housing. Luminaries’ body made of sheet steel, white, powder-coated, supplied ready for connection optionally for individual or group with power saving technology. Luminaries with protection IP 65, and protection class I,230 V,50 Hz.Recess frames for the gas-tight installation of clean-room luminaries in IP 65 in suspended ceilings.Frame made of extruded aluminium profile, white, powder-coated, able to be put together to form a rigid, continuous frame by means of plug and screw connections.Control equipment for the general lighting and the light dimming should be provided in the theatre Control Panel.Make-Altos/DGline or Equivalent 131 LED X-RAY VIEW PANEL: 132 TwoPlateX-RayViewScreenwithflickerfreeilluminationhavingimportedLEDsystemforuniformilluminationand operated by X-ray film .Thesystemhavingelectricalsafetycodesforhigh&Lowvoltagesystem.Itshouldbedesignedtoprovideflickerfree luminance for the film viewing purpose.It should be installed flushed with the theatre wall for hygiene and ease of cleaning.Make-Altos/DGline or Equivalent 133 MAGNETIC LISTING WRITING BOARD: 134 MagneticWritingBoard of size940x 640x50mmcomprisesof aflushmounted,1.50mmthick,whitelaminate board, bonded toa 10 mm high density fibreboard sheet for additional rigidity.The writing unit should comprise of flush mounted white laminate board, be opened to create a wall mounted writing surface within the operating room. The white board should be constructed from white laminate board.Make- Altos/Dgline or Equivalent 135 AUTOMATIC HERMETICALLY SEALING SLIDING DOOR -1500mmX2100mm 136 Automaticoperated Hermettically Slidingdoor with High Pressure Laminate on both side, Door size (1500mm wide2100mmheight)completewithdoubletoughnedglassvisionwindowof300mmx300mm withinanaluminum extrusionhighqualityframecompletewithrequiredaccessories.Thedoorframesconsistofreinforcedplasterboard panelsfacedwiththesamelaminateasthedoorandwillbeedgedwithanaluminiumextrusionandwithconcealed fixings that are adjustable during installation to ensure sealing.• Environment temperature should be -20°C to +55°C.The doorframe should be made of high quality anodize aluminum and the door panel should be made of compact laminate that can withstand high abrasion. To ensure efficient sealing of the doors frames should be provided. They will consist of reinforced plasterboard panels faced with the same laminate as the doorsVision panels, 300mm X 300 mm should be provided in the doors.The Door should be mounted and should complete with all necessary accessories i.e.Door closer, D type SS Door HandleMake-Metaflex/Doormedor Equivalent 137 HERMETICALLY SEALING HING DOOR-900mmX2100mm 138 Manually operated Hermettically Semi- sealed Hing door with HighPressure Laminateon bothside, Door size (900mm wide x 2100mm height) complete with double toughned glass vision window of300mm x300mm andsmooth effortless doorcompletewithrequiredaccessories,fixedfirmlytothewall.Thedoorframesconsistofreinforcedplasterboard panelsfacedwiththesamelaminateasthedoorandwillbeedgedwithanaluminiumextrusionandwithconcealed fixings.• Environment temperature should be -20°C to +55°C.The doorframe should be made of high quality anodize aluminum and the door panel should be made of compact laminate that can withstand high abrasion. To ensure efficient sealing of the doors frames should be provided. They will consist of reinforced plasterboard panels faced with the same laminate as the doorsVision panels, 300mm X 300 mm should be provided in the doors.The Door should be hinge mounted and should complete with all necessary accessories i.e.Door closer, D type SS Door Handle. The door track is constructed from an aluminium extrusion, fixed firmly to the wall. Nylon runner guides are fixed to the floor in such a way that they do not obstruct trolley movement through the door.Make-Metaflex/Doormed or Equivalent 139 CORNER GRILLS 140 Aluminium corner grills are used to air exhaust at all four corners.size of grill will be 600mmX400mm.Duly powder coated extruded aluminium linear horizontalfixed bar with normal 15 deg. blade having pitch of 13 mm.Exhaust Gril for return air-The exhaust air cabinets should be openable and cleanable. These cabinets should have suction from bottom.Distribution of exhaust air volume should be divided between fluff strainers to maintain the required pressure within the theatre without causing turbulence.The Exhaust air cabinet should be manufactured and supplied by the supplier of wall and ceiling system supplies. Also it should match perfectly with the ceiling system aesthetically.Make-conair/Bala ji engineering or Equivalent 141 ALUMINIUM DUCTING: 142 Aluminium Ducting ( 22 gauge ) with curves & bends where indicated for easy flow of air tight by applying silicon sealant after fabrication.Hangers will be provided to ducts & will be suspended be means of G.I. coated rod & these will not be more than 2.5 mtrs apart.Thermal insulation with 9/13mm XPE with aluminium foil for supply & return air ducts.Joints will be lapped with Nitrile tape for better insulation. (Laminar to AHU & Return air in all four corners) AHU to be placed near OT, not more than 6 meter.SITC OF Hand fabricated rectangular Aluminum Ducting in accordance with the approved ducting lay out drawing, complete with all accessories , dampers, guide, vanes, support, etc.Make-Hindalco/Virgo or Equivalent 143 AIR HANDLING UNIT 144 AHU System & Condensing Unit with consistingDOUBLE SKIN CASING: Outer Skin 0.6 mm Pre- Coated GI Inner Skin 0.6 mm Plain GI Frame Work Hollow Extruded AL Profile Thickness of Insulated Panels 25 mm thick, CFC Free PUF injected (Density: 40 kg / Cu. m.) Material ofDrain Pan 20 G SS-304 Tray duly insulated with 13 mm closed cell Nitrile insulation. Unit Base G.S.S Base Channel DX COIL: Make Of Coil ZECO Coil Casing / Blank offs GI Material Of Tube Copper (IGT) Tube Dia (mm / inch) 9.52 mm / 3/8” O.D. Thickness of tube (SWG / mm) 25 SWG / 0.5 mm Header Material Copper Thickness & Material of fins 0.15 mm Plain Aluminum No. of Fins per inch (FPI) 11 / 12 FILTERS: Media of Filters Synthetic (non woven type) Efficiency of Pre-filters (EU-4) 90 % down to 10 micron. Efficiency of Fine-filters (EU-5) 99 % down to 05 micron FAN & MOTOR: Fan make Nicotra Motor make CG Motor type TEFC Squirrel Cage IP 55 Protected VFD Compatible induction motor VFD: VFD make DELTA DOUBLE SKIN FLOOR MOUNTED HORIZONTAL AIR HANDLING UNIT SHALL HAVE:(WITH 25MM THICK PANEL) ◻ Mixing box with manually operated FA & RA damper in GI constructionDOUBLE SKIN CASING: Outer Skin 0.6 mm Pre- Coated GI Inner Skin 0.6 mm Plain GIFrame Work Hollow Extruded AL ProfileThickness of Insulated Panels 25 mm thick, CFC Free PUF injected (Density: 40 kg / Cu. m.) Material of Drain Pan 20 G SS-304 Tray duly insulated with 13 mm closed cell Nitrile insulation. Unit Base G.S.S Base ChannelDX COIL: Dx type coils having suitable number of distributors for connecting expansion valve with condensing unitsMake-Zeco//VTS or Equivalent 145 Make Of Coil Casing / Blank offs GI Material Of Tube Copper (IGT)Tube Dia (mm / inch) 9.52 mm / 3/8” O.D. Thickness of tube (SWG / mm) 25 SWG / 0.5 mm Header Material CopperThickness & Material of fins 0.15 mm Plain Aluminum No. of Fins per inch (FPI) 11 / 12FILTERS: Media of Filters Synthetic (non woven type)Efficiency of Pre-filters (EU-4) 90 % down to 10 micron. Efficiency of Fine-filters (EU-5) 99 % down to 05 micron VFD: DOUBLE SKIN FLOOR MOUNTED HORIZONTAL AIR HANDLING UNIT SHALL HAVE: (WITH 25MM THICK PANEL)Mixing box with manually operated FA & RA damper in GI constructions.Filter section with 50 mm thick (EU-4) box type pre filter with 305 mm thick (EU-5) bag type fine filter mounted on common filter frameCoil section with 6 row deep DX cooling coil with suitable distributor. Heater Section with GI strip Heater.Fan section with SISWbackward curved plug fan & Motor (IE-2). Manually operated SA damper in GI construction.Tonnage TR 8.5 Air Qty (CFM) 3500SP (mm wg) 125 UnitFan Type Plug Fan-355Fan model RLC E6-3135-23-19 Fan RPM 3400Motor RPM 2880Shaft Absorbing Power 3.2 Motor Rating (kw) 3.7 Motor pole 2Coil area (Sq.Ft.) 7.0 DX Cooling Coil RD 6 Distributor 1Heater KW3Filter area (Sq.Ft.) 8.0 Length (mm) 2500Width (mm) 1400 Height (mm) 945 146 AIRCONDITIONING: (8.5 T AC ) 147 Nominal Cooling Capacity-8.5tr,102000Btu/hr,29894watt Nominal Air Quantity-6250CFMPower Supply (V-ph-Hz)-400 ± 10% -3-5 Fan-PropellerDischarge-HorizontalFan Motor-Permanent Split Capacitor Type Power (watt)-470Control Type-LED DisplayOverall dimensions (mm)-982 X 610 X 1100 mm- Compressor- Scroll CompressorRefrigerant-R-410A (5.6) Liquid Line-5/8"Suction Line-1-1/8"Make- Carrier or Equivalent 148 ELECTRICAL WIRING INSIDE THE OT 149 Electrical Wiring as per requirement of OT, Wiring With OT distribution electrical Panel. ( Power cable at OT with Main distribution Panel will be provided by customer) Operation theatre shall be installed in the remote cabinet.All electrical wiring should be terminated to the connectors mounted on DIN/CE approved rail and labeled with indelible labels.Individual fuse and miniature circuit breakers should protect all internal circuits.Complete schematic diagram drawing description should be enclosed with the equipment. Makes:Scheinder/PolyCab/ Schematic.Supply, Installation, Testing and Commisnoing of Electrical Distribution Board with required MCB : It should be installed in a separate enclosure.Transformers,Mains,Relays,Circuitprotectiveequipment,forallcircuitsofOperationtheatreshallbeinstalledinthe remote cabinet. 150 MEDICAL GAS PIPE-LINE SYSTEM INSIDE OT 151 Medical Gas Pipe Line inside the OT above ceiling as required, complete with valve box and other required fitings. Medical Gas copper pipeline inside the OT and the Provision to connect to Pendant Systems (inside OT only).It should be confirm and meets with BS:EN:13348:2008 copper pipes.All medical grade degreased copper pipes must be inspected and duly Third Party Certified by Lloyd’s Registered Asia. Medical Grade Copper pipes manufactured from Phosphorous de-oxidized non-arsenical copper to BS:EN: 1412:1996 grade CW024A (Cu-DHP) manufactured to metric outside diameters and having mechanical properties in accordance with BS:EN: 13348:2008 & 250 or 290 (Half hard).Degreasing of pipe shall be such that there is less than 20 mg/m2(0.002mg/cm2) of hydrocarbons on the degreased surface when tested by the method specified BS:EN:13348:2008.Make- Altos/Aktiv/Mandev tubes/Mehta tubes or Equivalent 152 PASS BOX SIZE-2FTX2FTX2FT 153 Pass Box to remove the waste materials from the Operation Room to the Dirty Linen Area. Each box is equipped with two doors and the door should be operated electronically.. It is designed in such a way that only one door can be opened at one time. UV light is so installed that it is kept on while both the doors are closed and turned off automatically when the doors are opened. Indicators on both side of the Operation Room for Door Open/Close status. It is made of SS-304 Grade.Make- Jindal/Tata or Equivalent 154 STORAGE UNIT 155 Storage Unit of size 850x1600x350 mm has made of 1.6mm galvanised steel sheet. The exterior glass doors has lockable with magnetic push-button for easy opening. Removable toughened glass shelves of thickness 5 mm will be provided with the storage units.Make- Jindal/Tata or Equivalent 156 Pressure Relief Dampers 157 Pressure relief dampers should be provided in each room to prevent contamination of air from clean and dirty areas. Suitably sized air pressure relief damper should be strategically placed, enabling differential room pressure to be maintained and ensure that when doors are opened between clean and dirty areasCounter- weight balancing system should be provided in the PRD to maintain positive pressure inside the operation room.Air pressure stabilizers should have unique capability of controlling differential pressure to close tolerance.The PRD should remain closed at pressure below the set pressure and should open fully at a pressure only fractionally above the threshold pressure.The body of PRD sleeve and Grill should be epoxy powder coated as per standard High grade SS304 Stainless steel plate should be used for body and for bladesMake- Jindal/Tata or Equivalent 158 OT Pendant –Single Arm Anesthesia(Modular) 159 Anesthesia Pendent Systems should have the facility to provide convenient positioning of medical equipment.The support arms should be extremely robust and revolve on high quality bearings, so that the pendant head glides smoothly and quickly to any desired position.The Support arm should have atleast 10 mm thickness throughout to prevent any unnecessary deflection in Arms at given load.Arm Caps should be Aluminum Die casted Powder coated that allows its opening and closing a number of times as compared to ABS/Plastic end caps.High quality bearings shall be used to provide smooth and free movement, minimizing the force required to overcome static friction forces during repositioning. Bearings shall be permanently lubricated and sealed, withno maintenance or replacementPendant arms other than the cantilever lift arm shall be manufactured from extruded aluminium sections and available in various lengths. External surfaces of all arms shall be polyester powder coated in a RAL 9002/9003 finish. Tandem pendants for critical care areas shall be designed so that the consoles can readily swap sides within the bed bay to maximize the flexibility of the workspace.Non-return valves shall be fitted downstream of the connection to the medical / surgical air pipeline to prevent back-flow in the event of low distribution system pressure.Each arm should be capable of 330 – 340 degrees of rotation and be fitted with stops which can be easily adjusted to suit the desired mode of operation.Infinitely variable rotational stops should be available from 0-330 degree which shall enable precise of limits travel to be set to ensure maximum freedom of movement, whilst protecting walls and ancillary equipment.The rotational stops shall be dampened such that when limit of travel is reached, sensitive suspended equipment is not subjected to shock or vibration as the kinetic energy is absorbed.The arms may be fitted with pneumatic brakes or electromechanically breaks to prevent inadvertent movement.It should be possible to replace all medical gas hoses without the need for onsite crimping of ferrules. All medical gas hoses shall be colour coded to as per standard.The Pendant Service Heads / Column should be capable of accepting a range of shelves, drawers and infusion poles or other accessories. The Pendant Heads / column should support the range of Physiological Monitor Mounting Solutions. Service head should designed to host, Base, Gas Module, Electric Module and shelves.Make- Altos/Aktiv or Equivalent 160 The Pendant Service Heads / column should be supplied with medical gas terminal units. The medicalgas outlets fully comply with ISO 7396-1 and DIN 13260-2 standards. Medical gas hoses fully comply with thestandard BS EN 739 and are provided with NIST connectors to this standard. 161 Each anaesthesia pendant should be Single arm having rotational movement with load carrying capacity of minimum 120 kg having following facilities:movable Arm with total coverage of minimum 1000 mm and 330 degree.The Pendant Service Head/column should be modular with minimum 1200 mm head. Gas outlets: O2 – 2 nos, N2O – 2 no, Air (4 Bar) – 2 no, Vac – 2 nos, AGSS – 1 no. Medical rail with brake buttons fitted. - 1 No.Shelf with Drawer – 1 no. Infusion set – 1 no.Electrical Sockets – 10 nos. 6/16 Amp. 6 pin sockets. Pendants should comply with applicable standard:The terminal units must be according to ISO 7396-1 and DIN 13260-2 standards.Medical gas hoses shall be compliant to ISO 5359:2009 colour coded throughout its lengt 162 OT Pendant -SURGICAL PENDANT : 163 Surgon Pendent Systems should have the facility to provide convenient positioning of medical equipment.The support arms should be extremely robust and revolve on high quality bearings, so that the pendant head glides smoothly and quickly to any desired position.The Support arm should have atleast 10 mm thickness throughout to prevent any unnecessary deflection in Arms at given load.Arm Caps should be Aluminum Die casted Powder coated that allows its opening and closing a number of times as compared to ABS/Plastic end caps.High quality bearings shall be used to provide smooth and free movement, minimizing the force required to overcome static friction forces during repositioning. Bearings shall be permanently lubricated and sealed, withno maintenance or replacementPendant arms other than the cantilever lift arm shall be manufactured from extruded aluminium sections and available in various lengths. External surfaces of all arms shall be polyester powder coated in a RAL 9002/9003 finish. Tandem pendants for critical care areas shall be designed so that the consoles can readily swap sides within the bed bay to maximize the flexibility of the workspace.Non-return valves shall be fitted downstream of the connection to the medical / surgical air pipeline to prevent back-flow in the event of low distribution system pressure.Each arm should be capable of 330 – 340 degrees of rotation and be fitted with stops which can be easily adjusted to suit the desired mode of operation.Infinitely variable rotational stops should be available from 0-330 degree which shall enable precise of limits travel to be set to ensure maximum freedom of movement, whilst protecting walls and ancillary equipment.The rotational stops shall be dampened such that when limit of travel is reached, sensitive suspended equipment is not subjected to shock or vibration as the kinetic energy is absorbed.The arms may be fitted with pneumatic brakes or electromechanically breaks to prevent inadvertent movement.It should be possible to replace all medical gas hoses without the need for onsite crimping of ferrules. All medical gas hoses shall be colour coded to as per standard.The Pendant Service Heads / Column should be capable of accepting a range of shelves, drawers and infusion poles or other accessories. The Pendant Heads / column should support the range of Physiological Monitor Mounting Solutions. Service head should designed to host, Base, Gas Module, Electric Module and shelves.The Pendant Service Heads / column should be supplied with medical gas terminal units. The medical gas outlets fully comply with ISO 7396-1 and DIN 13260-2 standards. Medical gas hoses fully comply with thestandard BS EN 739 and are provided with NIST connectors to this standard.Each anaesthesia pendant should be Single arm having rotational movement with load carrying capacity of minimum 120 kg having following facilities:movable Arm with total coverage of minimum 1000 mm and 330 degree.The Pendant Service Head/column should be modular with minimum 1200 mm head. Gas outlets: O2 – 2 nos, N2O – 1 no, Air (4 Bar) – 1 no, Vac – 2 nos.Medical rail with brake buttons fitted. - 1 No.Make- Altos/Aktiv or Equivalent 164 Shelf with Drawer – 1 no. Infusion set – 1 no.Electrical Sockets – 10 nos. 6/16 Amp. 6 pin sockets. Pendants should comply with applicable standard:The terminal units must be according to ISO 7396-1 and DIN 13260-2 standards.Medical gas hoses shall be compliant to ISO 5359:2009 colour coded throughout its length. 165 UV LIGHT INSDIE OT FOR CLEAN/STERILIZE PERPOSE SIZE-2FTX1FT 166 Recess mounted sealed IP54 Protocol, non-hygroscopic UV peripheral lights ( 1" x 2" ) having compact high glow low wattage LED lighting system. These lights are having electrical safety code for high & low voltages.The luminaries for recess mounting in operation theatres should flush with the ceiling based on LED. Ultraviolet (UV) lamps are commonly used in operation theatres for disinfection.Luminaries cover made of highly-resistant, disinfectant-proof acrylic diffuser with white coated frame.Closing devices are integrated automatically in the electrical safety control without lines having to be connected to the luminaries housing. Luminaries’ body made of sheet steel, white, powder-coated, supplied ready for connection optionally for individual or group with power saving technology. Luminaries with protection IP 65, and protection class I,230 V,50 Hz.Recess frames for the gas-tight installation of clean-room luminaries in IP 65 in suspended ceilings.Frame made of extruded aluminium profile, white, powder-coated, able to be put together to form a rigid, continuous frame by means of plug and screw connections.Make- Altos/Dgline or Equivalent 167 Surgical Scrub Station – Two Bay 168 Compact surgical scrub sink should be designed for use in OT complex providing for pre – OT scrub up. Each fixture should be fabricated from heavy gauge type 304 stainless steel and should be seamless welded construction, polished to a satin finish.The washing faucet shall be made of Chrome plated brass hand. The station shall be equipped with soap dispensers made of SS 304 grade.The scrub sink should be provided with a front access panel which should be easily removed for access to the water controlled value, waste connections, stoppers and strainers.Hands free operation should include infra red sensors with built-in range of adjustment.The scrub station shall be made of high-grade stainless steel 304 with stain polish finish and wired to the current IEE regulations & BS 7971.Thermostatic mixing, valve control should be located behind the access panel and maintain constant water temperature. User defined setting of 1,3,6 & 10 min should be available. This timing should be adjustable to meet individual application requirements.All units should have reduced anti- splash fronts.The scrub stations control system shall be based on advanced microprocessorThe scrub station shall be sensor-activated 24VAC and should have the provision to operate it manually in case of power failure by using foot switch or knee switchimported thermostatic mixing valve for Hot & Cold water, Strainers, Spouts & manual foot operated valve system.Make- Jindal/Tata or Equivalent 169 AUTOMATIC PHASE SEQUENCE CONTROLLER 170 PMC Based (Pre magnetic Contractor)63A Double interlock & time Delay systemAuto/Manual Operation Sie- 140 x 275 x 320 mm Smooth and fasr Switchingworks well even at high & low voltages. Wide Current r\nge.Voltage Range-130-280Vac Temperature- 55 Degree Celsius Auto mode Selector switchDigital micro Control relay for sequence management.LED Indicator for complete status of power.Make- Subtech or Equivalent 171 Operation Theatre Light - LED type, Camera Ready (Triple Arm) 172 Operating Room Surgical Lighting system should provde an ideal combination of broghtness, maneuverability, and shadow resolution without sacrificing color accuracy throuh a consistent LED technology. Such Lighting System should have the following technical specifications: 173 a. Number of light heads : Two per suspensionb. Colour Temperature range : 3800k-5000 (±10%) - Variable color temperature. c. Field Size Diameter : 20 to 28 cm (+/- 10%)d. Working range : 750 to 11100 mm (+/- 10 %)e. Illumination Level : 160000Lux (major Dome & Minor dome )f. Rotation : 360 - 330 degree g. Sterilizable Handle : 02 Nos h. Mounting type : Ceiling i. Supply Voltage : 230 VAC 50 Hz j. Bulb Type : LEDk. Dimming Range : 50% - 100%l. Operating / Storage Humidity : 10 - 95 %m. Life of Light source : > 40,000 Hrs n. Should be provision to mount the camera in 1 dome . o. Surgical Light System Should be compliant with relevant European CE / US FDA standardsMake- HillRom/Steris orEquivalent 174 GST Extra as applicable
|