Tender For Composite Work To Relocate Sv-06 (Khajod); 1 SECTION-B [MECHANICAL (PIPING & TERMINAL WORKS) WORKS] Complete Carbon Steel Piping Work with painting including all fittings, flanges and supply of all required gaskets, studs bolts & nuts, etc., as described below Transportation of all piping items from Contractor"s storage point to work site complete work of fabrication, erection, painting, testing of pipes, flanges and fittings and making ready for further commissioning / start-up of carbon steel piping of all sizes and ratings including supply of all consumables, equipment, manpower and other resources and execution of, but not limited to, the following works in accordance with relevant specifications indicated in particular job specification & scope of work indicated in SCC, drawings, specification and instructions of EIC and as per all provisions of the Contract Document.Fabrication including cutting, edge preparation, inclusive of grinding the edges of pipes, fittings, flanges, etc. to match with the matching edges of uneven / different thickness wherever required, welding, attachment of all pipe fittings like elbows, tees, reducers. Supply of nipples, couplings, caps, plugs, gasket, stud bolts, nuts, U-clamps, etc. as required for completion of job.All fittings installation shall be paid linear meter basis under this item only.Handling and installation of all types & size of valves including assembly of valve accessories/ Actuator, (if any) by bolting, threading or welding, supply and insertion of gaskets, nuts & bolts, nipples, tubing etc. at all elevations of pipe sleepers, supports or overhead on racks, equipments nozzle, skid & painting etc. supply of all consumables, manpower, equipment, etc. for completion of all works as per scope of work and as per drawings, specifications and instructions of EIC including servicing / cleaning of valve wherever required.Installation of weldolets, sockolets, flanges, vent and drain point connection,Insulating joints, pipes, spool-pieces etc.,as required.Erection including prior cleaning, lifting, placing on pipe sleepers and supports, overhead on racks, skids and at all elevations including installation, design & fabrication of all type of supports / jump-over and carrying out connected activities for all types of valves including supply & fixing of gaskets, studs / bolts, nuts wherever required for all sizes, leveling, aligning, joining of flanges, blind flanges, connecting with equipment, nozzles, strainers, tie-in with existing piping / facilities, etc. tapping for inline instruments like pressure gauges, thermowells, sample connection, etc. 2 Preparation of bill of material (BOM)Preparation of Construction, Fabrication and As-built drawingsCarrying out all Non-destructive testing as required including Radiography.Surface preparation before application of primer by means of sand blasting including supply of approved quality of sand, manpower, machineries, tools & tackles to achieve required roughness as per specification and as per instruction of EIC.Painting of entire system (including aboveground all pipes fittings, flanges & accessories) suitable for Normal corrosive area environment including supply of approved paints & primers, application of primer & paints, identification lettering / numbering, color-coding, etc. as specified including rub-down & touch-up of shop primer or scrapping of shop primer wherever required by Company and providing scaffolding for all heights, etc.Cleaning and flushing by water / compressed air, testing of the systems including hydrostatic, pneumatic and any other types of testing as specified, draining, drying by compressed air / other methods approved by Company.Precommissioning & making operational of all piping system and equipments.Contractor shall provide all necessary assistance in terms of supply of manpower, equipment, tools and tackles, consumables, required amount of nitrogen for purging of entire terminal piping system including equipments etc. to the company during commissioning activities."Completion of all such work in all respects as per scope of work and as per drawings, specifications and instructions of the COMPANY and keeping the system ready in all respects for further commissioning and start-up.@Note: Carrying out all Non-destructive testing as required for 2"" & below lines, are inclusive in this SOR Item." 3 2" and below 4 Above 2" to Below 12" Pipe (various thickness range) 5 12" and Above (various thickness range) Note: For Hook-up works with 30" mainline U/G pipeline,including cutting and welding at tap-off point including making provision for hooking up and carrying out shutdown activities atterminals, if necessary, shall be paid as per SOR number B008000 6 Supply and Application of CoatingSupply and application of pipeline coating(wherever required)/repair including removaling the old/damaged coating/rust, greese, moisutre and all foreign material, surface preparation, supply of coating material, Epoxy primer or any other primer/base required to apply before coating as per relevant coating material, Patch repair kit, holiday testing after coating application/repair etc. as per relevant standard and as per directione of Eingineer In-Charge. 7 Pipeline coating - Raychem Heat shrink sleevs 8 INSTALLATION OF VALVESINSTALLATION OF ABOVE GROUND FLANGED VALVES (BALL / PLUG / GLOBE)AS PER DETAILS GIVEN BELOW: 9 Size - 6.0 Inch, Rating -600# 10 Size - 2.0 Inch, Rating -600# 11 Size - 3/4 Inch, Rating - 800# 12 INSTALLATION OF ABOVE GROUND BUTT WELDED/SOCKET WELDED VALVES (BALL / PLUG / GLOBE / CHECK) AS PER DETAILS GIVEN BELOW: 13 Size - 18.0 Inch, Rating - 600# 14 Size - 2.0 Inch, Rating -600# 15 Size - 3/4 Inch, Rating - 800# 16 INSTALLATION OF UNDER GROUND BUTT WELDED (EXTENDED STEM) ACTUATED SECTIONALIZATION VALVE (SV) AS PER DETAILS GIVEN BELOW: 17 Size - 30.0 Inch, Rating -600# 18 INSTALLATION OFUNDERGROUNDBUTT WELDED / FLANGED (EXTENDED STEM) VALVES (BALL / PLUG / GLOBE) AS PER DETAILS GIVEN BELOW 19 Size - 10.0 Inch, Rating -600# 20 SUPPLY OF ASSORTED PIPE, VALVES , FITTINGS AND FLANGESComplete work of supply of pipes, valves, fittings and flanges including all taxes, duties, transportation and inspection charges but not limited to, the following items in accordance with relevant specifications indicated inscope of work , drawings, specification and instructions of EIC and as per all provisions of the Contract Document.Handling including lifting, transportation from Contractor Stores to Contractor"s workshop / work-site for fabrication of all piping items supplied by Contractor. 21 CARBON STEEL (CS) PIPES(As per attached QAP in Tender) 22 CS Pipes 2" NB Sch XS API 5L, Gr.B, Seamless, BE / A 106 Gr.B. 23 CS Pipes 3/4 " NB Sch 160 , A 106 Gr.B. 24 3 LPE Coated Pipes 2" NB Sch XS API 5L, Gr.B, Seamless, BE / A 106 Gr.B. 25 VALVES - Supply of Butt/Socket Welded- Female (SW) Ends Ball Valves as perPMS and Data Sheet(As per attached QAP in Tender) 26 Size - 0.75 Inch, 800#, SW Ends, DesignStandard - BS EN 1SO 17292, Floating type, Full Bore, Ball Valve, Lever Operated 27 Size - 2 Inch, 600#, BW Ends, Design Standard - BS EN 1SO 17292, Floating type, Full Bore, Ball Valve, Lever Operated 28 VALVES - Supply of Flanged Ends Ball Valves as perPMS and Data Sheet(As per attached QAP in Tender) attached QAP in Tender) 29 Size - 0.75 Inch, 600#, RF Flanged Ends, DesignStandard - BS EN 1SO 17292, Floating type, Full Bore, Ball Valve, Lever Operated 30 VALVES - Supply of Flanged Ends Globe Valves as per PMS, Data Sheet and QAP in Tender attached QAP in Tender) 31 Size - 2 Inch, 600#, Flange Ends, Design Standard - BS 5353 / API 599 32 SUPPLY OF FLANGES 33 Supply of Weld Neck Raised Face Flanges (WNRF) as per details below: (As per attached QAP in Tender) 34 Size - 2 Inch, 600# , Thk/Sch - XS , Material - ASTM A105, Face/Finish - RF/125AARH , Dimn. Std. - ASME B16.5 35 Size - 3/4Inch, 600# , Thk/Sch - 160 , Material - ASTM A105, Face/Finish - RF/125AARH , Dimn. Std. - ASME B16.5 36 Supply of Raised Face Blind Flanges (BLRF) as per details below: (As per attached QAP in Tender) 37 Size - 2 Inch, 600# , Thk/Sch - XS , Material - ASTM A105, Face/Finish - RF/125AARH , Dimn. Std. - ASME B16.5 38 Size - 3/4Inch, 600# , Thk/Sch - 160 , Material - ASTM A105, Face/Finish - RF/125AARH , Dimn. Std. - ASME B16.5 39 SUPPLY OF FITTINGS 40 Supply of R=1.5D 90o BW Elbow as per details given below: (As per attached QAP in Tender) 41 Size - 2.0 Inch, Thk/Sch - XS, Material - ASTM A 105, Dimn. Std. - ASME B 16.11 42 Size - 3/4 Inch, Thk/Sch - 160, Material - ASTM A 105, Dimn. Std. - ASME B 16.11 43 Supply of Figure-8 Spectacle Blind as per details given below: (As per attached QAP in Tender) 44 Size - 2.0 Inch, Material - ASTM A 105, Dimn. Std. - ASME B 16.48 45 Size - 3/4 Inch, Material - ASTM A 105, Dimn. Std. - ASME B 16.48 46 Supply of Sockolet conforming to MSS-SP-97, Material - ASTM A105 and as per details given below:: (As per attached QAP in Tender) 47 18" x 3/4", 6000# 48 Supply of Weldolet conforming to MSS-SP-97, Material - ASTM A105 (CHARPY) -As per attached QAP in Tender and as per details given below: 49 18" x 2", Thk/Sch - XS 50 10" x 2", Thk/Sch - XS 51 Supply of Reducer (CONCENTRIC) as per attached QAP in Tender and as per details given below: 52 2" X 3/4", Sch-XS x Sch-XXS, ASTM A 234 GR. WPB, BWxSW, ASME B16.25 & ASME B16.11 53 Supply of Pipe-Nipple 54 Pipe-Nipple, 3/4 inch, ASTM-106, Sch- XXS ( One side Threaded(NPT)-Male, One side socket welded), Length=150MM 55 RADIOGRAPHYPerformance of radiographic inspection by gamma radiation as per scope of work and as per specifications in piping of all types and thickness including providing / hiring of all necessary equipments, supply of all consumables, and whatever else even though not expressly mentioned but required to perform the work as per specifications and instructions of EIC (full circle re-radiography of the repaired joint and additional radiography necessitated due to poor performance of contractor"s welder shall be carried out by the Contractor at his own cost and shall not be paid extra by Company). Radiographs shall be submitted to the EIC for acceptance whose decision shall be final and binding. 56 Radiography 2" NB 57 Radiography 10" NB 58 Radiography 18" NB 59 Radiography 30" NB 60 DISMENTALING, CUTTING, SHIFTING, HANDLING, LIFTING, TRANSPORTATION (INSTALLATION) OF EXISTING PIPELINE FACILITIES AT SV-06 STATION 61 Dismentaling, cutting, shifting, handling, including lifting, transportation from existing SV-06 sttaion to new proposed location of SV-06 station for fabrication or/and to worksite for field fabrication, assembly of parts / sub-assemblies erection for all vessels, equipmentssupplied by company aboveground / underground at all elevation / depth, . Contractor"s scope shall include supply of all material and accessories including but not limited to any fixtures, clamps, gasket, nut bolts, finish coat of painting including rub-down and touch-up of shop primer / paint scrapping of shop primer / paint and further their painting after application of primer as per specification, wherever required by Company. 62 RECEIVING & TAKING OVER, HANDLING, TRANSPORTATION OFPIPES , FLANGES , FITTINGS , VALVESETC (TERMINAL / MAINLINE MATERIAL/ SURPLUS MATERIAL) - ANYWHERE IN INDIAThe Contractor shall receive and take over, Handling including lifting, Owner-supplied bare / 3 LPE Coated line pipe / Ball Valves ,Flanges , Fittings and any other material from GAIL"s designated store, inspection of material at dispatch point as well as destination point and its transportation to work-site(including transit insurance) / return of project surplus / sparable material from Project site / Contractor"s store to GAIL"s store / warehouse including loading on trucks / trailers, transportation, unloading & stacking on wooden sleepers at Contractor"s own stock-yard near work-site(s) / GAIL store (as applicable), including arrangement of truck / trailers / cranes / other material/ machinery / manpower / consumables.Note: (1) Transportation up to 50KM shall be paid by SOR no. B006010/B006020. Beyond 50KM transportation shall be paid by SOR no. B006030/B006040.(2) The quantities given in above item no. are tentative only and shall not be considered to be binding. The quantities may be increased, decreased or deleted as per the actual site requirement and instructions / recommendations of Owner. The unit rate shall be operated to work out the final payment to the Contractor; (3) Above price shall be exclusive GST but inclusive of all type of toll taxes & duties, transit insurance during transportation & other insurance, etc. including all financial & commercial implication as per the tender document.(4) The weightage of material may be varies as part load or full load as per the project requirement, Bidder to be quoted the price accordingly. 63 Transportation by Trailer Fix up to 0-50 KM (Weight up to 18 Ton) per trip 64 Transportation by Truck Fix up to 0-50 KM (Weight up to 10 Ton) per trip 65 Transportation by Trailer CapacIty 18 Ton (40" L X 8.6" W X 7" H) Beyond 50 KM in addition to SOR Item No. 2.14.1. 66 Transportation by Truck (Weight up to 10 Ton) Beyond 50 KM in addition to SOR Item No. 2.14.2. 67 FIRE EXTINGUISHERS (Portable)Supply, installation and commissioning of the following fire extinguishers: 68 CO2 (10 Kg) considered1 no. for each locations 69 10 kg capacity DCP fire extinguisher (portable) considered1 no. for each locations 70 6 kg capacity DCP fire extinguisher (portable) considered1 no. for each locations 71 4 Nos. Sand Buckets with stand & canopy considered 1 set for each location 72 PADDING FOR PIPE SUPPORTS (4 Inch and Above) 73 Preparation, Fabrication and erection of padding for pipe supports (for all sizes/ thickness) by owner supply material(pipes). Welding shall be done by approved welder as per Approved WPS of Station piping with Root 6010 & Hot pass 7018 . 74 NITROGEN SUPPLY 75 Supply of Nitrogen for preservation ofPipeline/ purging of pipeline / hookup & shut downactivities . 76 Mobilization & De-Mobilization Charges 77 This item includes but not limited to mobilization/De-mobilization of Minimum 01 Supervior, 02 No Qualified welder, 02 Nos Fitter, 02 Nos Grinder, 02 Nos Helper, 02 No Rigger along with machine and all tools and tackles as defined in the Scope of work.This is the Minimum requirment, however in any additional requirement in manpower or Manchinery vendor shall provide the same without any seperate charges. 78 Supply of Bend ( Pipe Shall be As Free Issue Material)Note: (1) The quantities given above against individual items are indicative and shall not be considered to be binding. The quantities may be increased, decreased or deleted at site at the time of actual execution. Procurement shall be done as per actual site condition, approved construction drawings and as per instruction of EIC. The unit rate shall be operated to work out the final payment to the Contractor; a(2) Quantities given against individual item may be utilised / used for other consumers in same area. (3) Quantity of Nitrogen for purging may vary subject to confirmation of positive isolation of upstream & downstream SV Station Valves. 79 Bends (R = 6D) 30" NB, 19.1 mm (Or Higher) W.T. X-70 Angle - 15° to 45°(To suit as site requirement) 80 SECTION-C [CIVIL / STRUCTURAL & ARCHITECTURAL WORKS] 81 BARBED WIRE & GATE 82 Supplying, fixing and tensioning in position 2.5mm(12gauge), 2 ply, 4 points, GI Barbed wire designation A-1 conforming to IS:278 in horizontal rows and cross diagonals for compound wall "Y" shaped overhang etc. with necessary GI staples, clips and pins, GI straining bolts and binding wire with all labour and materials etc. complete as per drawings, specifications and directions of Engineer-in-Charge.(The barbed wire shall be measured in linear length of the barbed wire actually fixed). 83 Supplying,fabricatingandfixinginpositionstructuralsteellineposts, straining posts, struts for "Y" shaped overhang etc. conforming to IS:2062 over brick/stone Masonry/ RCC compound walls/ columns, cutting to required size as per drawings and specifications, welding where necessary, embedding in position, holding to correct level and line, any auxiliary structure for dummy supports, drilling holes and painting as per painting specification attached with tender, cutting brick/rubble/concrete surfaces if necessary, grouting with M20 grade concrete including cost of grout with all labour and material etc. complete as per drawings, specifications and directions of Engineer-in- Charge.( All materials including cement shall be supplied by contractor)For Normal Industrial Environment. 84 Providing andfixinginposition Steel Entrance Gatesconsisting ofMC- 75 framework for shutters, 20mm square M.S. vertical bars welded to the framework@100mmc/c,3mmthickM.S.sheetboxing,locking arrangement, 25mm thick, 75mm dia M.S. wheel with ball bearing includingfixingthegatetoRCC/masonrybyM.S.hingearrangement (75mmx75mmx6mm M.S.angles,bolt,washers)andM.S.holdfast groutedwithM-15gradeconcrete,providingandfixingM.S.pivot,50mmx50mmx6mmM.S.Teebenttoshapeandembeddedinroad surfacefor gate openingtrack,gate stopper,paintingthe gate with approvedshadeandqualitysyntheticenamelpaint(twocoats)anda coatofapprovedqualityprimer,ensuringsmoothoperationofthegate etc. all complete as per attached standard drawing. 85 EARTHWORK IN SITE GRADING 86 Earthwork in excavation and filling in all types of soil except soft rock and hard rock for general site grading for all heights and depths including clearing and stripping etc. in excavation areas, removing shrubs, grass, bushes, vegetable growth and other objectionable materials, trees upto and inclusive of a girth of 30 cms. (girth measured at a height of one metre above ground level) including uprooting of roots, etc., dewatering, if necessary, sorting out the excavated soil into serviceable and unserviceable materials in excavation areas and including filling in filling areas with serviceable material for general site grading and roads for all heights and depths to proper levels, slopes, grades and camber including clearing and stripping in filling areas as per specifications, consolidating exposed natural soil to 90% of max. laboratory dry density as per IS:2720 Part-VII, cutting of trees of girth upto and inclusive of 30 cms, removal of vegetation, breaking clods, spreading in layers not exceeding 30 cms loose thickness, watering, ramming and compacting with powerroadrollerstogiveatleast90%ofmax.laboratorydrydensity, dressing, leveling, testing, etc. and disposal of unserviceable materials/surplus earth if any, as directed by Engineer-in-Charge including stacking and/or dumping and dressing the same in demarcated areas etc. complete as per specifications, drawings and directions of Engineer-in-Charge. (The leads for the above mentioned operations shall be within the boundry limit of the plant and measurement shall be taken in the cutting area only). 87 PAVER BLOCK Flooring 88 Supplying and placing in position as per approved pattern of Cement Concrete Inter locking paver block 80 mm thick of approved shape, rough finish, M-40 strength of approved brand laid over the sand bed of minimum 100 mm thick. The CC interlocking blocks to be of uniform Grey colour or as approved by EIC complete in all respects , as per technical specifications and directions of the Engineer-in-chargeNote :-1. Rate to include cost of all labour, tools, tackles, equipment, hire charges, supply of all materials such paver blocks,sand,earth work in excavation in cutting earth in all conditions, shutteringwith all bye works and sundry works.2.To be read with in conjunction with Particular Job Specification3.Supply of all materials and providing labour, tools and tackles are in contractor’s scope 89 SAND FILLING 90 Supplying and filling approved SAND of specified quality under floors, in foundations, plinths, tank foundations etc. for all depths and heights including cost of sand,royalties, transportation to site for all leads and lifts,including loading, unloading, spreading in layers of loose thickness not exceeding 150 mm,watering,ramming,compacting with mechanical compactors and/or other equipment to the specified levels to achive 85% relative density as per IS:2720 Part XIV,including preparation of subgrade to the required slope,providing testing apparatus and testing the degree of consolidation all complete as per drawings, specifications and direction of Engineer-in-charge.The rates shall be inclusive of the cost of all labour,material,equipments etc. all complete . 91 DEMOLITION OF R.C.C./BRICKS/STONE MASONRY/STEEL WORK 92 Site clearance by demolition of R.C.C./Brickwork/Stone Masonry/Stone Soling, Flexible pavements etc. along with removing the debris and disposal of unserviceable material to any lead and staking of serviceable materials, handing over serviceable material to concerned department if requiredas per technical specifications and direction of Engineer-in-charge.Note:1. Rate includes cost of all labour, tools, tackles, hire charges, royalties, levies, leads, loading/unloading, transportation, water, electric power, illumination etc. complete in all respects as per scope of work, detailed construction drawings, technical specifications and direction of Engineer-in-charge. 2.Demolition of RCC/PCC/Brick Masonry/Road will be paid in NET CUMas demolished. 93 Site clearance by demolition of STEEL work etc. along with removing the disposal of unserviceable material to any lead and staking of serviceable materials, handing over serviceable material to concerned department if requiredas per technical specifications and direction of Engineer-in-charge.Note:1. Rate includes cost of all labour, tools, tackles, hire charges, royalties, levies, leads, loading/unloading, transportation, water, electric power, illumination etc. complete in all respects as per scope of work, detailed construction drawings, technical specifications and direction of Engineer-in-charge. 2.Demolition of steel work will be paid in NET Kg as demolished. 94 Dismentalting of existing Porta Cabin with proper winding and packing and Shifting at other location as per the direction of EIC. 95 CONSTRUCTION OF PIT/HOLE/TANK ETC 96 SOAK PITConstruction of soak pit conforming to IS:2470 Part-I and as per standard, masonry, filling and hand packing brick bats of size ranging between 40mm to 50, connecting with septic tank with necessary fittings, piping etc.including excavation, back filling and disposal of surplus earth for all leads, complete as per drawings, specifications and directions of Engineer- in-Charge.for following users ( Users -10 NOS ) 97 SEPTIC TANKConstruction,supplying,installation,testingandcommissioningofseptic tank as per standards and IS:2470 Part-I , with all necessary accessories like inlet, outlet vent pipes, manhole covers, rungs etc. including earthwork in excavationinalltypeofsoilexceptsoftandhardrock,backfillingand disposal of surplus earth for all leads etc. complete as per standards, drawings, specifications and directions of Engineer-in-Charge. All material including cement supplied by contractor for( Users -10 NOS ) 98 MANHOLEConstruction as per Standard drawing of brick masonry (brick class shall be as mentioned below) inspection chambers/manholes of 750mmx750mm internal size 1000mm deep(Max.) in cement mortar 1:4 (1 cement: 4 sand) with CI frame and cover 500mm clear dia, (circular Medium duty of grade MD-10) conforming to IS:1726 fixed on RCC slab of M-30 grade, necessary excavation, supplying, fixing 4 Nos. 16mm dia M.S. rungs, M-20 grade foundation concrete 1:3 cement mortar(1 cement: 3 sand) plastering of 13mm average thickness for inside & 16mm avg. thickness for outside exposed surfaces, backfilling, disposal of surplus earth upto a lead of 100M, benching with M-20 grade cement concrete and rendering smooth with a neat coat of cement slurry, painting the C.I. frame and cover with two coats of chlorinated rubberzincphosphateprimer@40µDFTpercoatandfinishpainting consists of two coats of chlorinated rubber paint@40µ DFT per coat etc. all completeasperdrawings,specificationsanddirectionsofEngineer-in- Charge. 99 ERC/IRC 100 Construction of ERC/IRC as per Std. including supplying and laying in position PVC pipes conforming to IS:4985 Class-I for electrical and instrumentation Road Crossings as per standard drawing and its addendum, including cutting the pipes if necessary, lowering, laying in position to proper levels, etc. embedded in M-20 grade concrete, providing proper jointing as per code requirements or manufacturer"s recommendations, etc. including earth work in excavation in all types of soil except soft and hard rock, backfilling and making good the surface, including cutting of new/ existingroadsandmakinggoodthesameincludingsupplyofanyroad material if required, (Back filling with road material shall be done in 150 mm thick layers well watered and compacted), including supplying and providing in the encasement concrete, cable crossing indicator made out of 4 mm thick MS circular plate of dia. 150mm welded to 16 mm dia. MS rod of approximately1.0mlengthandpaintingandletteringwith2coatsof approved enamel paint of approved colour over a coat of red oxide primer etc., supply and fixing of reinforcement as per drawing, including disposal of surplus earth anywhere within plant boundary limit etc. all complete as per drawings, specifications and instructions of Engineer-in-Charge. 101 EARTH WORK IN FOUNDATION 102 Earth work in Excavation below ground level for all kinds of works in ALL TYPES OF SOILas classified in specification for a depth upto 1.5m including removal of vegetation, shrubs and debris, cutting and dressing of sides in slopes, levelling, grading and ramming of bottoms, dewatering of accumulated water from any source and keeping the surface dry for subsequent works and disposal or stacking of excavated material within a lead of 100m, as directed including providing temporary supports to existing service lines like water pipes, sewage pipes, electric overhead and underground cables etc. all complete. 103 For depth beyond 1.5m and upto & inclusive of 3.0m. 104 Backfilling after execution of the WORK to proper grade and level with selected materials from available excavated soil from spoil heaps, including re-excavating the deposited soil excavated earlier, breaking clods, laying at all depths and heights in layers of thickness not exceeding 15 Cms. watering, rolling and ramming by manual methods/ mechanical compactors to achieve 90% laboratory maximum dry density, dressing, trimming etc. in foundations, plinths, trenches, pits etc. all complete. 105 EARTHWORK IN FILLING including supply by excavating the earth from BORROW AREAS arranged by CONTRACTOR for all leads, transporting the earth from borrow area including cleaning & stripping the earth at borrow areas, breaking clods, loading, unloading and laying at all depths and heights in layers of thickness not exceeding 15 cms., watering, rolling and ramming by manual methods/mechanical compactors to achieve 90% of the maximum laboratory dry density, dressing, trimming, levelling the top surface etc. in foundations, plinths, trenches etc. all complete. 106 Transporting and disposing the SURPLUS EARTH AND DEBRIS including shrubs and vegetationsfrom construction area beyond the initial lead of 100M including re-excavating the deposited soil excavated earlier, transportation, loading, unloading, laying at all depths and heights, stacking, levelling and dressing both the area (viz. from where the earth is transported and where it is deposited) to required levels and slopes complete with all lifts as directed.For carting on the basis of truck measurements (volume of truck reduced by 30% for voids)i) Upto 1.0Km. 107 PLAIN & REINFORCED CEMENT CONCRETE: 108 Providing and laying PLAIN CEMENT CONCRETE for all depths below and upto plinth level in foundations,drains, fillings, non-suspended floors, pavements & ramps or any other works etc. including shuttering, tamping, ramming, vibrating, curing, shuttering etc. all as specified in any shape, position, thickness and finishing the top surface rough or smooth as specified and directed all complete for concrete of nominal mix 1:4:8 by volume (1 Cement: 4 Coarse Sand: 8 Crushed Stone Aggregates/Gravels with 40mm and down size graded crushed stone aggaregates. 109 Providing and laying PLAIN CEMENT CONCRETE for all depths below and upto plinth level in foundations,drains, fillings, non-suspended floors, pavements & ramps or any other works etc. including shuttering, tamping, ramming, vibrating, curing, etc. all as specified in any shape, position, thickness and finishing the top surface rough or smooth as specified and directed all complete for concrete grade M20 with 20mm and down size graded crushed stone aggaregates/Gravels. 110 Providing and laying REINFORCED CEMENT CONCRETE OF M-25 GRADE with 20mm and down size graded crushed stone aggregates/gravel in SUB-STRUCTURE of all types e.g. foundations, footings, raft, beams, slabs, pile caps, retaining walls, jambs, counterforts, buttresses, trenches, manholes,pipeencasement, catchpits, drains, RCC pits, equipment/machine foundations, pedestals, pipe sleepers, columns, plinth beams, suspended floors, beams, staircases, landings, steps, brackets etc. (including single pour concreting upto 250m3), including cost of admixtures if used,providing pockets, openings, recesses, chamfering etc., wherever required, vibrating, tamping, curing and rendering if required to give a smooth and even surface etc. all complete (excluding the Cost of Reinforcement and Shuttering) for all depths below and upto plinth level inany shape, position and thickness etc. all complete as specified, shown and directed. 111 Providing and laying REINFORCED CEMENT CONCRETE OF M-25 GRADE with 20mm and down size graded crushed stone aggregates/gravel in SUPER STRUCTURE in suspended floors, slabs, beams, columns, walls including counterforts, staircases, landings, steps, facias, fins, mouldings, gutters, shelves, windowsills, canopies, lintels, girders, ducts, brackets, chajjas with drip moulds, pedestals, posts, struts, equipment/machine foundations, ramps etc. (including single pour concreting upto 250m3) including cost of admixtures if used providing pockets, openings, recesses, chamfering wherever required, vibrating, tamping, curing and rendering if required to give a smooth and even surface etc. all complete (excluding the Cost of Reinforcement and Shuttering) for all heights above plinth level in any shape, position, thickness etc. all complete as specified, shown and directed. 112 CENTERING AND SHUTTERINGProviding and fixing CENTERING AND SHUTTERING in foundations, footings, raft beams, slabs, pile caps, retaining walls, jambs, counter-forts, buttresses, trenches, equipment/machine foundations, pedestals, abutments, pipe sleepers, columns, plinth beams, lintels, suspended slabs, beams, staircases, landings, steps, non-circular tunnels/bunkers/silos/ shafts/ hoppers/liquid storage structures etc. including shuttering for single pour concreting, strutting, bracing, propping etc., keeping the same in position during concreting and removal of the same after specified period etc. for Straight/ Inclined Shuttering, keeping necessary provision for inserts, projecting dowels, anchor bolts or any other fixture etc. all complete and as specified and directed. 113 i)For all depths below and upto & inclusive of plinth level. 114 ii) For all heights above plinth level. 115 REINFORCEMENT 116 Supplying and placing in position HIGH STRENGTH DEFORMED STEEL BARS REINFORCEMENT (conforming to IS:1786, Grade Fe 415), for R.C.C. work including transporting the Steel, straightening, cleaning, decoiling, cutting, bending to required shapes and lengths as per details, binding with contractor"s own 16 SWG black soft annealed binding wire at every intersection, supplying and placing with proper cover blocks, supports, chairs, overlaps, welding, spacers, fanhooks etc. for all heights and depths etc. all complete as directed. 117 STRUCTURAL STEEL WORKS 118 Supplying, transporting, storing, fabricating in position and testing/examining bolted and/or welded STRUCTURAL STEEL WORKS at all levels and locations including all builtup sections/compound sections made out of rolled sections and/or plates/bent plates in trusses, purlins, wind ties, wind girders, columns, portals, racks, frameworks, crane gantries, surge girders, bracings, floor beams, lifting beams, monorails, platforms, staircases (excluding chequered plates and gratings), ladders, stoppers, brackets, side runners, sagrods, supports for equipment and technological accesories and process piping, hand railings, posts, conveyor galleries, trestles, towers, masts, junction houses etc., cutting to required size, straightening/bending if required, edge preparation, cleaning, preheating, bolting/welding of joints, (including sealing the joints of box sections with continuous welding), finishing edges by grinding, fixing in line and level with temporary staging & bracing and removal of the same after erection, grouting with Ordinary Grout or premix free flow Nonshrink Grout as specified, including preparation and submission of detailed fabrication drawings and applying primer after fabrication as perspecification (for normal corrosive environment), etc. as per direction of EIC. 119 Supplying, fabricating, fixing and keeping in position at all levels and locations THREADED ANCHOR BOLTS of all diameters and nomenclature including nuts, washers, anchor plates, pipe sleeves etc. in foundations, columns, pedestals, slabs, beams, walls etc. or any other place as directed including handling & transporting, straightening if required, turning from relevant size M.S. rounds to required diameter, threading, welding, providing necessary templates and auxilliary dummy structures, if any, necessary tying and welding with reinforcement, adjustment of shuttering & reinforcement/any other fixture, greasing exposed metal surfaces, covering bolts and packing the sleeves with jute cloth etc.all complete as specified and directed. 120 Supplying, transporting, storing, fabricating and fixing in position M.S. METAL INSERT (with lugs) of any shape made out of flats, plates, rolled sections, pipes etc. providing necessary templates, staging, cutting, straightening, if required, bolting, welding as required and embedding in position on both Plain and Reinforced Cement concrete members inclusive of adjusting shuttering & reinforcement/any other fixture, welding where necessary, tying and holding to correct level, line and position, any auxilliary dummy structures to support the heavy inserts, painting exposed surfaces with a coat of Red Oxide Zinc Chromate Primer etc. all complete for all depths and heights as specified and directed. 121 Supplying, fabricating and erecting in position at all levels and locations bolted, clamped and/or welded GRATING (fabricated as perstandards) made out of M.S. flats/M.S. flats with M.S. rounds in walkways, platforms, stair treads etc. including cutting to required size, shape, making holes, notches, openings of required size, nosing, straightening if required, making the edges smooth, removing the burrs, fabricating clamps, fixing, welding, preparation and submission of fabrication drawings and preparing the surfaces for painting, surface cleaning, wire brushing, removal of mill scale, dust, rust, oil or grease and applying one shop coat of Red Oxide Zinc Chromate Primer after fabrication etc. all complete as specified and directed. 122 BRICK MASONRY 123 Providing and laying BRICK MASONRY WITH BRICKS OF CLASS 7.5 in cement mortar 1:6 (1 Cement : 6 Sand) in one or more brick thickness and in any shape (excluding circular/curved brick masonry) at all depths and height including the cost of materials, labour, scaffolding/ staging, sampling & testing, soaking of bricks, cutting and laying of bricks, providing recesses, making openings of any shape & size, finishing the joints flush below ground level and raking out the joints above ground level, sealing the gap between masonry and soffit of beam/slab, embedding the fittings & fixtures, curing, etc. all complete as per specifications. 124 External WallsProviding and laying of ordinaryplaincementplasteraverage15mmthick1:4(1cement: 4 sand) in single / two layers over brick wall / concrete surfaces, including hacking the concrete surface (RCC Wall / Column / Beam etc.) in foundation / superstructure. Rate to include cost of all labour, material, scaffolding curing, hacking the concrete surface etc., all complete. Cement supplied by the Contractor at their cost. 125 Internal WallsProviding and laying of ordinaryplaincementplasteraverage12mmthick1:4(1cement: 4 sand) in single / two layers over brick wall / concrete surfaces, including hacking the concrete surface (RCC Wall / Column / Beam etc.) in foundation / superstructure. Rate to include cost of all labour, material, scaffolding curing, hacking the concrete surface etc., all complete. Cement supplied by the Contractor at their cost. 126 CeilingProviding and laying of ordinaryplaincementplasteraverage6mmthick1:4(1cement: 4 sand) in single / two layers over brick wall / concrete surfaces, including hacking the concrete surface (RCC Wall / Column / Beam etc.) in foundation / superstructure. Rate to include cost of all labour, material, scaffolding curing, hacking the concrete surface etc., all complete. Cement supplied by the Contractor at their cost. 127 Painting of WallsExternal walls:- Providing & applying 3 coats of waterproof decorative cement paint of approvedmakeandapprovedshade,cleaning, includingpreparationof surfaces,base primer, curing etc. all complete 128 Internal walls:- Providing & applying 2 coats of waterproof decorative cement paint of approvedmakeandapprovedshade,cleaning, includingpreparationof surfaces,base primer, curing etc. all complete 129 ROOFING TREATMENT 130 Providingandapplyingpolyetherbasedpolyurethane(PU)waterproof coatingconsistingof2components(resin+hardener)infourcoats consistingofaprimeradhesioncoatandthreesealingcoatsappliedby brushevenlytoperfectlevel@min.160gm/sq.MpercoatoverR.C.C. slab including sprinkling the last coat of P.U. with a layer of clean sand (300 micron) and laying min. 50mm thk. PCC (1cement :2coarse sand:4 aggregate) over the fully cured coating in panels of max. 1.2M x 1.2M with 24 SWG chicken wiremeshfinishedsmooth and sealing joints between panels with Polysulphide sealant as per approved manufacturers spec. and including preparing the base surface (levelling, cleaning, filling upcrackswiththinpasteofPolyurethanefillingcompound)providing fillets of 75mm radius with PCC (1 cement : 2 coarse sand : 4 aggregate) atjunctionsofhorizontalandverticalsurfaces,continuingthewater proofing on vertical face to a minimum ht. of 150mm over finished roof surface,terminatingit incontinuousgrooveof 10mmx 20mmand filling with polyurethanesealent putty, continuing the treatmentinto rainwateroutlets by,providing 450mm x450mm khuras atalloutlets, levelled down by min. 25mm, finishing all complete.Cement supplied by the Contractor at their cost. 131 110mm dia O.D. Size. exposed PVC rain water pipe jointed with bonding solution of approved quality and make with pressure rating of 4kg/cm2 includingclamps,connectionsetc.allasperapprovedmanufacturer"s details. 132 Providing andapplyingtwocoatsofsynthetic enamelpaintofapproved make and shade to give an even shade including cleaning and preparation of surfaces, providing 2 coats of primer, stopping and filling etc. complete. 133 DOORS/VENTILATOR/WINDOWS 134 Aluminiumglazeddoors with cup pivots of aluminiumalloyto IS designationNS-4ofIS-737andISdesignationofA-5-MofIS-617, Heavy duty hydraulically operated, adjustable floor mounted door closer conformingtoIS:6315(single/doubleaction),250mmand150mmlong, 10mm dia anodized. Aluminium tower bolts as per IS : 204 one each for eachshutter,brassbodymorticelock(6levers,asperIS:2209)with aluminium handleonbothsides,etc.allcomplete foreachshutter,with plainanodized aluminium sections and5mm thk.toughened glassasper IS:5437 . 135 Aluminium glazed window/ventilator with approved make sections, frictionhinges,castaluminiumhandle,etc.allcompletewithapproved shade electrostatically powder coated aluminium sections and 6.3mm thk. laminated glass as per IS:2553. Openable type. 136 VITRIFIED TILESProviding and laying Vitrified tile flooring of size 600mm x 600mm of approved make (Marbonate or approved equivalent) set in cement slurry over 1:4 cement mortar bed of 35mm average thickness at all levels. Joints between tiling to be filled with grout of approved shade as per manufacturers specifications. Rate to include cost for laying tiles to approved pattern, design as directed by Architect, including surface cleaning, cement mortar, curing, acid wash, etc., and protecting the flooring with polythene sheet and pop overlay till hand over. 137 ACID RESISTANT TILESProviding and laying acid resistant, vitrified tiles of approved size as per manufacturer"sspecs.infloor/skirting/Dadolaidoverandincluding bitumenpriminglayer, 12mmthick Bitumenmastic layer and 6mm thick resin type chemical resistant mortar conforming to IS: 4443 including raking out and flush pointing of joints with resin type chemical resistantmortar,preparationofbackgroundsurface,finishingetc.all complete. Minimum 10mmthk. tiles of approved size for flooring 138 CERAMIC TILE FLOORINGProviding and laying Ceramic tile flooring of approved shade of premium quality of Kajaria make or approved equivalentset in cement slurry over 1:4 cement mortar bed of 35mm average thickness. Joints between tiling to be filled with grout of approved shade as per manufacturers specifications. 139 CERAMIC TILE SKIRTING Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. 140 KOTA STONE FLOORING Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :25 mm thick 141 PLINGTH PROTECTIONMaking plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth 142 VITRIFIED SKIRTINGProviding and injecting approved chemical emulsions as specified for pre-constructional ANTI-TERMITE TREATMENT and creating a chemical barrier under and around column pits, wall trenches, basement excavations, top surfaces of plinth filling, junction of wall and floor, along the external perimeter of building, expansion joints, surrrounding of pipes and conduits etc. all complete as specified and directed. (Plinth area of the building at ground floor only shall be measured). 143 DPCProviding and laying 40mm thick DAMP PROOF COURSE with plain cement concrete of nominal mix of 1:1.5:3 with 10mm & down size graded crushed stone aggregates in two layers of 20mm thick with two coats of hot bitumen (Grade A90/S90 conforming to IS:73) applied @ 1.7 Kg/sq.m. over each layer as per specifications including cleaning, watering the top surface of walls, centering, shuttering, placing, tamping, curing, sprinkling an even layer of dry & sharp sand over the hot bitumen etc. all complete as specified and directed. 144 Providing and injecting approved chemical emulsions as specified for pre-constructional ANTI-TERMITE TREATMENT and creating a chemical barrier under and around column pits, wall trenches, basement excavations, top surfaces of plinth filling, junction of wall and floor, along the external perimeter of building, expansion joints, surrrounding of pipes and conduits etc. all complete as specified and directed. (Plinth area of the building at ground floor only shall be measured). 145 FALSE CEILINGProviding and fixing suspended false ceiling consisting of 12.5mm thick Gypsum plaster board suspended on GI framework with staggered joints. GI framework to consist of GI perimeter channels 0.55mm thick 20mm x 30mm along perimeter of false ceiling of ceiling, screw fixed to wall/partition with nylon sleeves and screws @ 600mm c/c. Suspending GI intermediate channels of size 0.9mm thick 45mm x 15mm from the soffit at max dist 1220mm c/c with ceiling angle 0.55mm thick 25mm x 10mm fixed to soffitusing proprietary supplied GI cleats and steel expansion fasteners.Ceiling section 0.55mm thick web size 51.5mm and flanges 26mm each and 10.5mm lips are fixed to perpendicular to intermediate channel @ 457mm c/c using connecting clips.12.5mm thk. tapered gypsum plasterboard(IS 2095-1982) is screw fixed to ceiling section with 25mm drywall screws @ 230mm c/c. Boards to be finished with proprietary supplied jointing tape and jointing compound and sand papered to achieve a smooth and seamless finish. and 2 coats of primer suitable for plasterboard applied and two coats of soft sheen enamel paint to be applied as per manufacturer specification.Rate quoted to include vertical drops of 250mm and all cut-outs required for light fixtures, smoke detectors and other services cut-outs complete as directed by Architect. (Vendor to account for additional supports as required).Rate quoted to include cost of providing support framework formed of perimeter channels for fixing light fixtures, AC grills/diffusers etc., Also to provide concealed perimeter channel support as required to support modular grid ceiling sections at junction between gypboard false ceiling and modular grid tile ceiling. 146 SANITARY WORKS 147 Cost of providing and fixing cera / hindware wall mounted EWC with power flush with seat cover etc, (Ivory colour) set in 1:2:4 concrete and doing necessary angles, connections.etc., 148 Cost of providing and fixing wash basin of cera/hindware make(Ivory colour) fixed to existing wall using necessaryangles, connections, including all SS accessories like waste coupling, bottle trap, inlet connection tube etc., complete. 149 Orissa Pan Type wall mounted ceramic urinals of approved ivory colour with all SS accessories like waste coupling, bottle trap, inlet connection tube etc., complete, Cera/ HINDWARE. 150 PILLAR COCKCost of providing and fixing pillar cock long neck with aerator. Jaguar or approved equivalent fixed with necessary accessories. 151 ANGULAR STOP COCKCost of providing and fixing ½" dia Jaquar angle stopcock. 152 HEALTH FAUCETCost of providing and fixing Health faucet CP Jaquar are approved equivalent. 153 CONCEALED STOPCOCKCost of providing and fixing concealed stopcock Jaquar or approved equivalent 154 NAHANI TRAPCost of providing and fixing CI Nahani trap/ "P" trap set in 1:2:4 concrete and jointed with spun hemp & doing necessary lead caulking and making necessary 1:2:4 concrete cistern, when req. and plastering with water-proof compound to a smooth finish . 155 C.P TRAPCost of providing and fixing C.P. cockroach trap, floor drains of Chilli / equivalent make 156 SS jaliCost of providing and fixingSS Jali of Jaquar /equivalent make 157 MIRRORSupplying and fixing mirror for wash basin of standard make as per standard specifications 158 TOWEL RODSupplying and fixing Towel rod of standard make as per standard specifications 159 INTERNAL PLUMBING WORKSInternal Plumbing work P/f 1/2" G.I."C" class Tata / Zenith or equivalent pipe and50mm & 75mm dia. PVC Pipe outlet( prince or equivalent ) including G.I. & PVC assorted fittings, such as elbow,tees ,bends,& unions including applying creosote and wrappingwith hessin cloth, including chasingthe walls for concealing the pipe lines and making good the same. This includes providing & fixing3/4" dia "C" class G.I. Pipe for inlet & outlet of Water Tank connection 160 EXTERNAL PLUMBING WORKS 161 supply, transportation and erection of 500 liters SINTEX / Equivalent water tanks 162 Providing & fixing of external plumbing consisting of CPVC or equivalent pipes varying from dia 3" to 6" with all fittings like bend, tees,gate valves, NRV"s, y"s etc which Nani traps,special pieces and accessories for layingjoiniting including testing & commissioning of all Pantry/toilets. 163 Providing and fixing concertina coil fencing with punched tape concertina coil 600 mm dia 10 meter openable length (total length 90 m) , having 50 nos. rounds per 6 m length, upto 3 m height of wall/chain link fencing with existing "Y" shaped angle iron placed 2.4 m or 3 m apart and with 9 horizontal R.B.T. reinforced barbed wire , stud tied with G.I. staple and G.I. clips to retain horizontal, including necessary bolts or G.I. barbed wire tied to angle iron , all complete as per the direction of Engineer In-charge, with reinforced barbed tape(R.B.T.) /Spring core( 2.5 mm thick) wire of high tensile strength of 165 kg/sq.mm with tape (0.52 mm thick) and weight 43.478 gm/meter (Cost of M.S. angle & CC block to be paid seperately) 164 Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. 165 External Water Supply System / Bore Well 166 Supply, laying and commissioning GI water supply piping (Heavy Duty, Tata / Jindal / Indus make) with all fitting such as garden irrigation fittings, water meter, water connection, and all other fittings including earth cutting, filling, disposal of surplus earth, bore well 150 mm dia, 50 meter depth and submersible pumps CRI make 3 h.p.including all accessories, panel, wiring all complete in all respects as per scope of work, detailed drawings, technical specificationsand directions of the Engineer-in-charge.Rate to include cost of all labour, tools, tackles, equipment, hire charges, supply of all materials including pipes, water meter (Class – B I.S Approved, Cresent / Kranti Make, 9999 Kilo. Lts. Reading capacity), valves, boring, priming, cabling, pumps, clearing, earth work, etc with all bye works and sundry works and consumables."ORConstruction, testing and commissioning of Bore-Well as per the Scope and attached Drawing." 167 Providing and fixing chequered plate 6mm thk. In approved panel or over steel structure including cutting, welding, hoisting, fixing in position and applying two or more coats of approved quality synthetic enamel over a priming coat of steel primer complete as per drawing and specifications and directions of Engineer-in-charge. 168 Distempering with 1st quality Acrylic Distemper (Ready Mix) having VOC content less than 50 gram/liter of approved manufacturer and of required shade and colour on new work (two or more coats) over and including water thinnablwe priming coat. 169 SURVEY WORKS 170 Conducting topographical ground/land survey in the specified area as shown in the tender drawings by conventional/GPS or any other standard method, covering details of physical features likeNallahs, pits, Forest, Trees, Roads, culverts, transmission lines, telegraph/ telephone and electric poles, underground or any other services, cross drainage works including cross sectional details of nallahetc.including establishing high flood level with source of information, identification of any monument, historical structure, wild life sanctuary in the vicinity, storm water disposal pointwithlevels,cross-sectiondetailsofnallah,recordingspotlevels, including providing in tabulation girth wise no. of trees etc as specified, plotting and developing topographical contour maps, showing true north including establishing survey reference stations, key plan etc. including all equipment"s, instruments, personnel"s, clearing of bushes as per requirement for intervisibility to carry out survey work etc. , complete work in all respects as per drawings, specifications and directions of Engineer-in-Charge including submitting hard copies of drawings/map and supply of electronic files.Note: Survey work shall be carried out by survey agency approved by Contractor and shall be submitted to PMC/EIC for review. 171 SECTION-D [ELECTRICAL WORKS] 172 Supply, installation, testing, commissioning of Street Lighting Fixture suitable for 250W HPMV or Equivalent LED Lamps on Lighting Poles (4mtr Height) with aluminium paint complete with mounting bracket, flameproof control gear box, internal cable from fitting to junction bo+B211+B208:B215+B208:B217+B208:B218+B208:B219+B208:B220+B208:B222+B208:B223+B208:B222+B208:B221+B211+B208:B215+B208:B222+B208:B223+B208:B224+B208:B225+B208:B226+B208:B225+B208:B228+B211+B208:B215+B208:B230+B208:B233+B208:B236+B208:B239+B211+B208:B215+B208+B208:B251 173 Supply, installation, testing, commissioning of Indoor Lighting Fixtures suitable for 18/26/36W LED Lamps ( including Lamps) for including all fixing arrangements and all material ( PVC duct pipe, clamps, etc.) and labour as per specifications, drawings and instruction of EIC. Work to be completed in all respects. 174 Supply, installation, testing, commissioning of Exhaust fans (safe area) for including all fixing arrangements and all material ( PVC duct pipe, clamps, etc.) and labour as per specifications, drawings and instruction of EIC. Work to be completed in all respects. 175 Supply, installation, testing, commissioning of Exhaust fans (Corrosion Proof Type) for including all fixing arrangements and all material( PVC duct pipe, clamps, etc.) and labour as per specifications, drawings and instruction of EIC. Work to be completed in all respects. 176 Floor mounted MEDB consisting of busbar chamber, cable alley, Incomer - 1 no.100 Amp FP MCCB, Auto healthy phase selector & Outgoing - 2 nos. 60 Amp FP MCB, 9 nos. 63 Amp FP MCB, 3 nos. 32 Amp FP MCB(as per technical specification, data sheet & SLD enclosed with this tender), complete with ammeter, voltmeter, energy meter, voltage selector switch, indicating Lamps etc. 177 Recess/Surface mounted Indoor Lighting Panel(ILP) Consisting of 40 Amp FP MCB+ELCB as incomer and 12 nos. 10A DP MCBs as out goings. 178 Recess/Surface mounted Power Panel(PP) Consisting of 63 Amp FP MCB as incomer and 9 nos. 20A DP MCBs as out goings. 179 Recess/Surface mounted Outdoor Lighting Panel OLP (For External Lighting) Consisting of 40 Amp FP MCB+ELCB as incomer, Contactor, timer, A/M switch, PB, indication Lamp etcOutgoing Through Timer:6 Nos. 16 Amp DP MCB 180 Supply, installation, testing, commissioning of Solar Power Package of rated power of 5.0 KWp Hybrid solar invertor with roof top Solar Panels, Charger Panels with Ni-Cd Battery Bank (48 hours Backup), Battery Rack, Support Structures for including all fixing arrangements, Earthingand earthing materials, Lighting Arrester, AC/DC cables, AC DB/DC DB,Civil Works and all material and labour as per specifications, drawings and instruction of EIC. Work to be completed in all respects.@Note: Bidder shall consider the scope as per details given in SOW (Typical SLD) 181 Recess/Surface mounted UPS DB Consisting of 63 Amp DP MCB as incomer, MFM with ON/OFF indicator, fuse, 60A DP, Cu Bus Bar and 13 nos. 10A DP MCBs as out goings. 182 Design, Engineering, supply, erection, termination, earthing and commissioning of Guard room DB complete in all respects.16 Amp DP MCB as incomer, 30A SPN, Cu Bus Bar and 2nos. 6A DP MCBs and 4 nos. 16 A DP MCBs as out goings. 183 Supply, installation, testing, commissioning of Flameproof Flood Lighting Fixtures suitable for 250/400W HPMV or Equivalent LEDLamps for including all fixing arrangements on top of terrace of container and all material ( PVC duct pipe, clamps, etc.) and labour as per specifications, drawings and instruction of EIC. Work to be completed in all respects. 184 Supply, installation, testing, commissioning of Modular Switch Board for including all fixing arrangements and all material ( PVC duct pipe, clamps, etc.) and labour as per specifications, drawings and instruction of EIC. Work to be completed in all respects. 185 Supply, installation, testing, commissioning of 5/15A Switch Socket for including all fixing arrangements and all material and labour as per specifications, drawings and instruction of EIC. Work to be completed in all respects. 186 16 A plug socketMCB for AC 187 Supply, installation, testing and commissioning of Ceiling Fan230V AC 1200 mm sweep with regulator work to be completed in all respects. 188 Supply ,Installation and testingof 1.5 Tr. 5 star inverter base Indoor & Outdoor unit of split AC including all labours and materialsfor Typical SV station refer General specification of Erection, Installation, Testing & commisioning of Electrical Equipments, General Specification for Air conditioningSystem and directions of OWNER / CONSULTANT. 189 Supplyand Installation of Hardware and other accessories including all labours and materialsas perGeneral specification of Erection, Installation, Testing & commisioning of Electrical Equipments , Electrical Design Basis , General Specification for Cable and accessories anddirections of OWNER / CONSULTANT. 190 Rubber Mat 191 CAUTION Board& Shock treatment chart 192 Rubber hand gloves 193 Cable route marker 194 Ladder type Cable tray- Galvanized steel fabricated out of hot rolled sheet steel with rigid welded ladder type 450 mm widestraight run 195 Supply, installation, testing & commissioning of the complete earthing system, earth electrodes/pit, earth main ring, earthing of metering skid, electrical equipments, instrument panels, field instruments, process equipments & pipes / flanges including all associated civil work with all material & labour as per specification & drawings approved by the company. Each earthing system shall include the following. 196 65mm dia 3 Mtr. Long GI PIPE Electrode with 6mm thick chequered plate cover, display board etc 197 600x600x3mm copper plate Electrode with 6 mm thick chequered plate cover, display board etc 198 GI Strip (50X6) mm 199 GI Strip (25X6) mm 200 1C 25 Sq.mm PVC insulated Cu Conductor 201 10 SWG GI wire 202 GI Wire, Copper wire, wire rope and all balance earthing material including copper strip (50 mmX 2 mm thick) jumper for flanges etc.as per the specification. 203 300mmlong 50x6GI earth busbar 204 25mm dia 1500mm long GI rod for lightning protection 205 25x6mm GI strip for building roof & down conductor for lightning protection 206 PVC Conduit including bend,tee, clamps,JB and other required assesories 207 Supply, laying, installation, termination, testing, commissioning of 1100 Volt PVC insulated, PVC sheathed and armoured / unarmoured cables in trenches, excavated underground / trays, pulling through pipes and its proper sealing including underground trench and supply of hume pipes for road crossing, etc. as required as per specifications and drawings approved by the company. 208 4C x 95 sqmm AL FRLS XLPE 209 4C x 35 sqmm AL FRLS XLPE 210 4C x 16 sqmm CU FRLS XLPE 211 3C x 6 sqmm CU FRLS XLPE 212 3C x 16 sqmm CU FRLS XLPE 213 4C X 6 Sqmm Cu conductor XLPE Insulated Armoured Power Cable of 1100V Grade 214 3C X 2.5 Sqmm Cu conductor XLPE Insulated Armoured Power Cable of 1100V Grade 215 2.5 sqmm CU Wire 216 4.0 sqmm CU Wire 217 6.0 sqmm CU Wire 218 SECTION-E [INSTRUMENTATION WORKS]Supply, Calibration and Installation of instrumentation items listed below:(For details, refer instrumentation specifications) 219 Pressure Gauge of different Range and rating as per site requirementEngineering , Design, Supply, testing, installation, erection and commissioning. Also supply of erection material like SS316 tube, SS316 fittings, manifold, mounting stand and all other required material. Bourdon type with 2-way manifold, direct mount, 150mm dial, wetted part SS316, IP 65 rated, blow out protection and shatter proof heavy duty glass. 220 Pressure Transmitter of different Range and rating as per site requirementEngineering , Design, Supply, testing, installation, erection and commissioning. Also supply of erection material like SS316 tube, SS fittings, manifold, mounting stand and all other required material. Smart HART, Ex"d", IP-65, 24 VDC 2-wire loop powered. 221 Temperature Gauge - skin type, direct mount as per site requirementEngineering , Design, Supply, testing, installation, erection and commissioning. Also supply of erection material like SS armoured capillary, mounting stand and all other required material. Skin type, direct mount, 150mm dial, wetted part SS316, IP 65 rated and shatter proof heavy duty glass. 222 Temperature Transmitter of different Range and rating as per site requirementEngineering , Design, Supply, Installation, Calibration, Testing &Commissioning ofTemperature Transmitters including mounting of Instrument on yoke, supply of yoke, supply and erection of supports for impulse lines wherever required, supply, fabrication & installation of SS manifolds/ SS impulse lines & SS valves & fittings with supports, testing and painting of supports. 223 RTDEngineering , Design with wake frequency calculation, Supply , Installation, Calibration,Testing &Commissioning of RTD Flanged type thermowell (as per approved Piping GAD & Hookup drawings) inclusive of installation of thermowell on thepiping nozzle and installation of instrumentsas per General Specification-Instrumentation 224 Valve Junction Bob - Gas Over Oil Actauted Valve (GOOV) and or HOV of different size and rating as per site requirementInstallation ofvalve junction box and their accessories inclusive of supply of necessary cable glands, terminals and complete with cabling, glanding, termination and earthing followed by testing and commissioning of complete gas over oil actuated valve. 225 Gas Detection System (GDS)Supply, configuration, testing, installation, erection and commissioning of gas detection system including point gas detectors,control unit and junction boxes.Gas detector control unit shall be installed inside the local control panel.Supply, Laying of cable inside the cable trench, cable tray for hardwired signals and power cables from gas sensors to gas detectors control unit including glanding, termination, ferruling, dressing etc. at both ends.Supply of cable trays, installation and erection of cable trays and, supply of erection materials, cable ferrules, cable lugs, cable tie. 226 IR type, Flame proof, IP-65, housing material SS316 without display, range 0-100% LEL point hydrocarbon gas detector. 227 Hooter, electronic multi-tone,IP-65, Ex"d" and epoxy coated aluminium housing material. 228 Beacon, electronic stroboscopic type,IP-65, Ex"d" and epoxy coated aluminium housing material. 229 Manual Call Point (MCP), electronic, 24 VDC power, IP-65, Ex"d" and GRP/aluminium housing material 230 Junction box 231 Cables, Cables Trays and Junction boxesSupply, laying, installation, erection of signals cable from pressure transmitters, temperature transmitter to junction boxes, junction boxes to existing local control panel (LCP)/FC. including glanding, termination, ferruling, dressing etc. at both ends.Laying of cable from remote operated valve junction box to existing local control panel (LCP)/FC ncluding glanding, termination, ferruling, dressing etc. at both ends.Supply of cable trays, cables glands, junction boxes, erection materials, cable ferrules, cable lugs, cable tie.Installation and erection of cable trays and junction boxesPreparation of cable trench for burying cable, excavation, restoration of trench and compacting. Supply and laying of bricks and sand, pipes at all the crossings etc. 232 1P X 1 .5 Sq. mm Over all Screened 233 1 P x 2.5 Sq. mm Over all Screened 234 2 P x 1.5 Sq. mm Over all Screened 235 1Q X 1 .5 Sq. mm Over all Screened 236 12P X 0 .5 Sq. mm Individual Screen & Over all Screened 237 6 P x 1.5Sq. mm Over all Screened NIS cable 238 12 P x 1.5 Sq. mm Over all Screened NIS cable 239 1 T x 1.5Sq. mm Over all Screened NIS cable 240 8 T x 1.5 Sq. mm Over all Screened 241 4 P x 2.5 Sq. mm (For power supply) 242 3C X 2 .5 Sq. mm Power cable 243 2C X 1 .5 Sq. mm Power cable 244 Serial communication cable, Modbus RS - 485, PVC Sheathed, 4 pair 245 Junction Box"Flameproof Junction box as per specification with Plug and suitable forcable entries of single pair and multi pair cable as per the Instrument cable schedule 246 Cable Trays (60 mm wide x 30 mm height) 247 Cable Trays (100 mm wide x 30 mm height) 248 Cable Trays (300 mm wide x 30 mm height) 249 Multi cable Transit (MCT) block with stay plate and module as per the approved datasheet 250 Canopy 251 FIRE DETECTION CUM ALARM SYSTEM AND CLEAN AGENT FLOODING SYSTEM 252 Design , Engineering , Volume calcualtion, Power consumption Calculation, Supply, manufacturing, inspection, delivery, Installation,Testing and comissioning of Fire Detection cum Alarm System and Clean Agent Flooding System for control room building as per technical specification, Scope of Work of tender document and completion of work in all respects.Control Room building consists ofInstrumentation, Scada / Telecom Room of size 5m X 4m X 4m (h),Electrical Room of Size3m X 5m X 4m (h) and Battery Roomof Size 5m X 3m X 4m (h).Contractor"s scope of supply and installation of all the required material, manpower, machinery to complete the system in all respects or as per direction of EIC. 253 Inert Gas SystemThe System shall comprise of Filled Cylinders including reserved cylinders (300Bar Working Pressure) with Valves, Inertech Pressure Controllers, Inertech Check Valves, Pressure Switches, Pneumatic Actuators, Solenoid Actualtors, Discharge Hoses, Actuation Hoses, Discharge Pressure Swithces, Inertech Nozzles, Selector Valves, Piping, Manifolds, Gas Release Panels, Battery & Battery Charger, Warning Signs etc. including Dump Test by One Cylinder in smallest area and Including Mandatory & Commissioing Spares 254 For SV-06 255 SECTION-F [TELECOM WORKS]System design, Inspection & factory testing, FAT, SAT, training, installation, commissioning, Trial run, pre-factory tests, packing, forwarding and supply of all goods including commissioning spares & documentation, pre-commissioning activity for telecom 256 Supply of 24 Fibre Composite armoured Optical Fibre Cable drum (6 fibre G-655 & 18 fibre G-652) of 4 km +/-5% Cable drum length. 257 Supply of jointing closure 24 Fiber, 2 way including all accessories (3M, Siemens, Raychem make only) 258 Supply of 40mm OD permanently lubricated HDPE telecom duct as per technical specifications including manufacturing, factory testing, inspection, packaging, forwarding, transportation, insurance, receipt and storage at site. 259 Telecommunication Site WorkNote: (1) The quantities given above against individual items are indicative and shall not be considered to be binding. The quantities may be increased, decreased or deleted at site at the time of actual execution. Procurement shall be done as per actual site condition, approved construction drawings and as per instruction of EIC. The unit rate shall be operated to work out the final payment to the contractor; (2) In each area, quantities given against individual item may be utilised / used for other consumers in same area. 260 Laying of HDPE Telecom Duct: Laying of 40mm HDPE Ducts in same pipeline trench direct buried or cased crossing through CS / HDPE conduit in all type of soil & terrain, excavated as required, padding, backfilling, etc. including supply of HDPE Duct accessories required including plastic couplers, end plugs, cable sealing plugs, end caps, etc. suitable & sufficient for above supplied ducts, cleaning and sealing of ducts at the end laid drum lengths, preparation and supply of cable blowing pit at each Km jointing of HDPE conduit, testing OD HDPE Duct and accessories after laying preparation of report and final drawing and documents as per specification, joint location marking, erection accessories, as-built, etc. 261 Blowing of Optical Fibre Cable inside HDPE Duct: All activities pertaining to Blowing of Optical Fibre Cable in same pipeline trench directly (after testing drum at site), through CS / HDPE conduits along the pipeline also at crossing cable, sealing using all materials required, including laying of warning mats, etc. as per direction of EIC 262 Supply and laying of GI Pipe (4") at crossings for protection of OFC / HDPE duct 263 Splicing, Jointing of Optical Fiber Cable (Including Supply and Installation of jointing pits including sand, etc. & joint markers) 264 Supply of FTC with pig tails other accessories for termination of OFC - 24 Fibre in the Telecom Room 265 Installation of FTC & Wire mesh, termination of OFC on FTC / DDF inside telecom room, splicing with steet fibre, fibre test, OTDR test, power testing of laid OFC, identification of fault, rectification, earthing, final testing and commissioning, preparation of reports, etc. work complete in all respect with all necessary accessories for all location till final Handing Over and Taking Over by Owner of laid OFC. 266 Dismantling and Re-Installation of Telecom System, Electrical panel, RTU, Scada Etc. tonew Proposed location of SV Staion -06 as per General specification of Erection, Installation, Testing & commisioning of Telecom system, Electrical and Other Equipments and as per the direction of OWNER / CONSULTANT. Completion of job in totality to the satisfaction of EIC. No separate charges shall be paid for manpower, consumables, lifting equipments, handling, tools & tackles used during execution of this activity.
|