Tender For Addition/Alteration And Special Repair To Godfrey Clinic At Nd Mumbai; 1 SCHEDULE A PART I (B/R WORKS)Demolition of cement concrete (un-reinforced) in ground floors and pavings not exc 15 cm thickness (below or above ground level) and removal of debris out of MD land.Note: The place of disposal shall be find out by the contractor. 2 Demolition of cement concrete (unreinforced) of any description and in any position not otherwise specifically provided for and removing debris out side MD land.Note: The place of disposal shall be find out by the contractor. 3 Taking down chowkat with shutters (without taking off shutters from the frames) area n.exc 1.5 Sqm each complete all as specified 4 Taking down chowkat with shutters (without taking off shutters from the frames) area exc 1.5 Sqm but n.exc 4 Sqm each. 5 Taking down steel tubing 15mm bore with fittings complete all as specified. 6 Taking down steel tubing 20mm bore with fittings complete all as specified. 7 Supplying and fixing 15/16mm bore CPVC pipes SDR 11 including Plain CPVC SDR 11 fittings as required laid in floors or fixed to walls and ceilings with suitable size GI clamps complete all as specified. 8 Supplying and fixing 20mm bore CPVC pipes SDR 11 including Plain CPVC SDR 11 fittings as required laid in floors or fixed to walls and ceilings with suitable size GI clamps complete all as specified. 9 M&L for 100mm thick PCC 1:4:8 type D2 using 40mm graded stone aggregate as in sub base of floos complete all as specified. 10 M&L for 25mm thick cement concrete type B-1, 1:2:4 (using 20mm graded aggregate) as in floor complete all as specified. 11 S&F aluminium anodized snap grid of size 605 x 605 mm with aluminium anodized angle 20mm x 20mm x 1.2mm fixed along the wall and main and cross tees of size 36.5mm x 23.5mm x 1.5mm and 23.5mm x 23.5mm x 1.5mm respectively with ceiling cleats / angle brackets of size 15mm x 15mm x 1.5mmincluding suspended GI wire hangers 6mm dia.upto 1200mm length with adjusting level and fixed to roof slabs by means of ceiling cleats made out of GI flat 40mm x 3mm x 60mm long and expansion hold fasteners 12.5mm dia. 40mm long @ 20cm c/c, cement fiber board 4mm thick of size 6oomm x 600mm inserted in grid including dismantling carefully old false ceiling with ceiling boards, electrical fittings, fan, fire sencers etc and making good disturbed surface as per existing complete all as specified and directed. 12 Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing) and removing debris outside MD land complete all as specified. Note: The place of disposal shall be find out by the contractor. 13 M&L for machine cut machine polished marble slab 18 mm to 20 mm thick of selected quality in flooring laid over and including 20 mm thick screed bed in cement mortar 1:6 set, jointed and pointing the joints with white cement complete as specified and directed . 14 M&L for machine cut machine polished marble slab 18 mm to 20 mm thick of selected quality in skirting laid over and including backing coat 15 mm thick in cement mortar (1:4) set, jointed in white cement paste and pointing the joints with white cement complete as specified and directed . 15 Material & Labour for 20-25mm thick, machine cut, Kotastone slab, as in floors, steps, landing etc. laid over and including 20mm thick screed bed or bedding layer in CM (1:4), set and jointed in neat cement slurry and pointed in white or coloured cement to match the shade of tile including rubbing, cutting and polishing as specified in SSR Part I complete all as specified. 16 S & F 10mm thick coloured acid and alkali resistant tiles laid over and including 15mm thick screed bed or bedding layer in alkali/acid resistent mortar (1:4), set and jointed in neat cement slurry and pointed in white or coloured cement to match the shade of tile complete all as specified. 17 M&L for coloured dark shed vitrified ceramic tiles9 to 10mm thick (Square/rectangular) polished, area of each tiles n. exc. 0.36 sqm laid in floorsover and including 15 mm thick screed bed in cement mortar 1:6 set and jointed in neat cement slurry and pointed in white or coloured cement to match the shade of tile completeall as specified . 18 M&L for coloured dark shed vitrified ceramic tiles9 to 10mm thick (Square/rectangular) polished, area of each tiles n. exc. 0.36 sqm as in vertical surfaces such as skirting/dado etc., laid over and including 10mm thick backing coat in CM (1:3), set and jointed in neat cement paste and pointed in white or coloured cement to match the shade of tile complete all as specified. 19 Material & Labour for Non skid coloured ceramic tiles 7 to 8 mm thick (square/Rectanglar) area of each tiles exc 0.11 Sqm but n exc 0.18 Sqm laid in floor over and including15mm thick screed bed or bedding layer in CM (1:6), set and jointed in neat cement slurry and pointed in white or coloured cement to match the shade of tile complete all as specified. 20 Material & Labour for coloured glazed ceramic tiles 7mm thick, area of each tiles exc 0.15 Sqm but n exc 0.18 Sqm laid on vertical surfaces such as skirting/dado laid over and including 10mm thick backing coat in CM (1:4), set and jointed in neat cement paste and pointed in white or coloured cement to match the shade of tile complete all as specified. 21 M & L for 18 to 20mm thick machine cut machine polished granite stone slab (of any type)machine cut, laid in floor over and including 15mm thick screed bed in cement mortar 1:6, bedded and jointed with grey cement slurry and pointed with white cement mixed with admixture of pigment to match the shade of granite stone including grinding andpolishing complete all as specified. 22 Rounding to edges of stone slabs one edge, such as in steps, cooking platform and other similar sitution complete all as specified. 23 Demolition of brick work or stone/boulder masonry, built in cement mortar, including all quoins, arches, pillars etc, but excluding ashlar facings, dressed stone work & precast concrete articles including copings etc.and removing debris outside MD land complete all as specified.Note: The place of disposal shall be find out by the contractor. 24 M&L for Brickworkwork with old size sub class B bricks, straight or curved on plan exc 6m mean radius built in CM 1:6 complete all as specified. 25 Taking down cement plaster of any description on brick or stone walls etc including raking out joints, hacking for key, scrubbing down with water etc and removing debris outside MD land. Note: The place of disposal shall be find out by the contractor. 26 M&L for rendering 15 mm thick on stone masonry surface or surface other than fair face of brick-work incement mortar (1:6) and finished even and smooth without using extra cement complete all as specified. 27 M & L for rendering 20mm thick in two coats(15mm inner coat + 5mm finishing coat) on fair faces of brick work or concrete surfacesin cement mortar 1:4 mixed with integral water proofing compound @ 3% by weight of cementand finished fair and even including necessary scaffolding and safety arrangement complete all as specified and directed by Engr-in-Charge.Note- Water proofing compound shall be measured and paid for separately. 28 S&F powder coated aluminiumsections for partitions, windows, ventilators and doors including fabrication of frame/shutters and fixing to walls/floors with necessary lugs, cleats etc including all accessories such asglazing clips, handles, tower bolts, rollers rubber beadings for fixing glass panes in frame including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required complete all as specifiedNote: - (i) Glass panes will be measured & paid separately. (ii)The rate quoted shall be inclusive of neoprene beading, glazing clips, screws, etc. as requiredbut shall not be measured for arriving of weight.(iii) Minimum thickness of powder coating shall be 25 micron. (iv) The rate shall be inclusive of the locking arrangement including complete packing with silicon gel around contacting surface of aluminium work with matching existing area.(v)The size of aluminium sections shall be as perHQ CE(N) MZ TD drawing No TD/2021/01 to 05 and sill to be provided as per HQ CE(N) MZ TD of sill type A and B respectively if directed. 29 S&F in repairs for aluminium anodized Deco grill 7.5 mm size DG-102, fixed to E/H frames, 1.5mm thick, bar size 6.2mm and 7.5mm thick in required sizes complete all as specified and directed. 30 Supply & Fixing in repairs 12mm thick, toughened glass for door, shutters, partitions, sheves etc with and including fitting and fixtures such as SS handles, SS studs, SS fittings for door, SS pivots etc completeall asspecified and directed by Engineer-in-Charge. 31 Supply & Fixing solid PVC door frame of size 50mm x 47mm made out of 5mm plain colour PVC sheet reinforced with M.S. Square tube, in opening as per specification and drawings shown in SSR Part II.complete all as specified and as directed by Engr-in-Charge. 32 M&L for factory made solid PVC moulded door shutter 28 to 30 mm thick with 2,4 or 6 raised panel design with 2 mm thick moulded PVC sheet on the front face & 2 mm plain colour PVC sheet on back face with particle board core complete all as specified in SSR Part-II. 33 S & F 40mm thick, flush shutters, solid core construction, with block board core and plywood face panelsk, commercial type on both sides.one face is covered with decorative face veneer with lipping/frame to match complete all as specifeid and directed. 34 S&F 100mm size butt hinges extruded aluminium alloy with galvanized mild steel hinge pin anodised and fixed type C-21 complete all as specified . 35 S&F floor door stopper aluminum alloy body and tongue, anodised, with hard drawn steel spring overall length of cover plate 150mm. 36 S&F 75 mm Parliament hinges aluminium alloy anodisedand fixed complete all as specified and directed. 37 S&F 2nd class hard wood (Sal) small fittings such as brackets of any type, latch and hinge blocks, shaped door and window stops and the like, incl all necessary labours, articles n exc 200 cu.cm each. 38 S&F aluminium anodised barrel tower bolts of extruded section, 200 mm length, ISI marked. 39 S&F aluminium alloy, anodised, sliding door bolts with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts & sliding bolts of extruded sections or cast aluminium alloy, 300 mm long , ISI marked. 40 M&L for 4.8mm thick Sheet glass, ordinary quality and glazing with oil putty or rubber beading in square n exc 0.5 sq. m in each panecomplete all as specified. 41 M&L Stainless steel wire cloth. 0.36mm nominla dia or wire and average width of aperture 1.40mm and fixed with stainless steel wire staples complete all as specified 42 S&F 20mm bore PVC coated MS conduit drapery rods, suitablefor door/widows curtain with fancy type dooms as approved by GE,and fitted to each end, including necessary brackets and fixed to wall complete.. 43 M&L 18/19mm thick prelaminated particle board, interior grade, prelaminated one side with decorative choice lamination & other side balancing white lamination, fixed with screws to timber frame work as in kitchen cabinet boxes. 44 M & L for Extra over rates of prelaminated particle board 18/19mm thick for external teak wood lipping, 6mm thick, fixed with nailscomplete all as specified. 45 S&F continuous (piano hinges, mild steel, bright finish or electro galvanised width of flaps (when opened) 40mm complete all as specified and directed. 46 S&F Ball catches with 8mm dia steel ball, and brass body and striking plate incl letting in and fixed. 47 M&L for cutting chases in stone walls for concealed water tubing or concealed conduit wiring pining in, making good to facings where required and pointing in cement mortar (1:3) and making good disturbed surfaces, cutting not exc 10 cm width or girth. 48 S&F 15 mm bore bib tap, cast copper alloy chromium plated, fancy type with crutch or butter fly handle screwed down, screwed for iron pipe complete all as specified. (weight not less than 400gms). 49 S&F 15 mm bore stop valve cast copper alloy, chromium plated, fancy type with long shank screwed down high pressure concealed type with crutch or butterfly handle screwed both ends for iron pipes or union complete all as specified.(weight not less than 400gms). 50 S&F 15 mm bore pillar taps, cast copper alloy, fancy type chromium plated screwed down, high pressure , with letteredHot or Cold with long screwed shanks and fly nuts screwed type with powder coated golden ring, make- Marc/Jaguar or equivalent as approved by the Engineer-in-Charge. (weight not less than 400gms). 51 S&F in repairsvitreous china wash down water closet pan (Pedestal pattern) white, including matching plastic sheet cover, closed pattern with flat bottom and cover and mild steel chromium plated or aluminium anodized hinging device and making all connections complete all as specified. 52 S&F in repairsvitreous china wash hand basin, white,oval shape of size 550 mm x 400 mm including cutting for and pinning in ends of brackets including CI brackets,and making all connections complete all as specified. 53 M&L 32mm dia waste coupling, PTMT for glazed ware sinks, basin (Minimum weight 45gms) complete all as specified. 54 S&F low level PVC flushing cistern (coloured) of heavy duty, 10 Ltrs capacity, syphonic action type complete with inlet, ball valve, float and handle including cast iron bracket and connecting to WC complete all as specified. 55 S&F PVC connections 15 mm size with PTMT nuts of length 450 mm complete all as specified. 56 S&F PVC waste pipe 32mm dia 800mm long with socket sutable for WHB/Sink 57 S&F CI floor trap with grating including jointing to waste pipe fixed in cement concrete 1: 2: 4 type B1 diameter of outlet 75 mm bore. 58 S&F 6mm thick superior quality beveled edge mirror of selected quality glass mounted on 6 mm thick AC building board or commercial plywood and fixed to wooden plugs with chromium plated brass screws and cup washers size 600mm x 450 mm. 59 S&F 20 mm dia brass chromium plated D type towel rail 60 cm long fancy type including necessary brackets and fixed to wall with CP brass screws complete all as specified. 60 Supply & Fixing 110mm bore PVC ( SWR) grade pipes, single socketed in any length with rubber ring joints fixed to walls with dash through fastners and rain water bracketsuitable for 110mm bore pipe spacing 1.5m c/c as per CE (Navy) Mumbai TD No TD/2023/01 or laid in floor complete all as specified. 61 Supply & Fixing 75mm bore PVC ( SWR) grade pipes, single socketed in any length with rubber ring joints fixed to walls with dash through fastners and rain water bracketsuitable for 110mm bore pipe spacing 1.5m c/c as per CE (Navy) Mumbai TD No TD/2023/01 or laid in floor complete all as specified. 62 M&L for 100mm bore cast iron soil waste and vent pipes (sand cast pipes) in any length with or without ears with cement joints fixed to walls with suitable size GI clamps or laid in trenches complete all as specified and directed. 63 M&L for 75mm bore cast iron soil waste and vent pipes (sand cast pipes) in any length with or without ears with cement joints fixed to walls with suitable size GI clamps or laid in trenches complete all as specified and directed. 64 S & F PVC (SWR) Junction single T equal or unequal 110mm bore provided with access door fixed with rubber ring joints. 65 S & F PVC (SWR) Junction single T equal or unequal 75mm bore provided with access door fixed with rubber ring joints. 66 M&L for 75mm thick PCC 1:3:6 type C2 (using 40mm graded stone aggregate) as in plinth protection and finished even and smooth without using extra cementincluding necessary form work to edges complete all as specified. 67 Demolition of RCC shelves, slabs etc of any description including reinforcement cut as required to facilitate demolition and separating, scraping and cleaning of reinforcement and removing debris outside MD land.Note: The place of disposal shall be find out by the contractor. 68 M&L for RCC 1:2:4type B1 (using 20mm graded stone aggregate) as in slab supported on walls, beams and column in floors, roof, landings, balconies, canopies, deck slabs etccomplete all as specified. 69 M&L for RCC1:2:4 type B1 (using 20mm graded stone aggregate) as in beams, cantilevers, bressummers, lintelscomplete all as specified. 70 M & L for Use and waste of formwork to sides and soffits of suspended slabs,landings, shelves, similar work n exc 200mmm thick and beams,horizondal or sloping for rough finished surfaces of concrete flat. 71 M&L for TMT CRS bars 10 mm dia and over cut to length, bent to shape required, including cranking, bending, spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with the clips complete all as specified . 72 Ditto as per item No 71.00 above but 6 to 8 mm dia bars 73 M & L for1st class hardwood (teak) moulding as in cornices, joints of wall, repairing of Arches, decorative pillers, decorative cornices and decorative features on front façade by carefully removing granite cladding, removal of multiple layer of enamel paint from the surface, reconstructing missing details in masonry and plaster as per existingoriginal design. Item to include replacement of damaged wooden member i.e wooden base, decorative columns ,arch,parapet , chatri and railling etc wherever required ,and refixing of new elements which is missing sectional area not exc 6 Sq cm including applying two coats of French polish complete all as specified. 74 Dismantlingtimber scantlings any type and in any position complete all as specified . 75 M & L for 1st class hard wood (Teak) plain, solid, strainght chowkats and frames, wrought, framed rebated on the solid, rounded or chamfered,segmental, purlins, beams, rafters, columns etc put together with glue pinned at joints all as specified and directed.Note - Independent test of teak wood shall be carried out by GE before payment and reports kept on record duly verified, signedand approved. 76 M & L for first class hard wood (teak) full lengthjoists, rafters, purlins, beams, column etc in roof/floor/staircase and where ever required as per siteincluding all fixtures and fastening and apply solignum on the wood surface complete all as specified and directed by GE.Note - Independent test of teak wood shall be carried out by GE before payment and reports kept on record duly verified, signedand approved. 77 Supply and fix in repairs first class hard wood (teak) boarding 30mm thickin flooring including mouldings, chamfers, tongue and grooved including necessary scaffolding where ever required as per site condtion and apply solignum on the wood surface all as specified and directed by GE.Note - Independent test of teak wood shall be carried out by GE before payment and reports kept on record duly verified, signedand approved. 78 M & L for first class hard wood (teak) boarding40mm thick for risers/treads/soffit in staircase including mouldings, chamfers, tongue and grooved includingnecessary scaffolding as per site condition and apply solignum on the wood surface all as specified and directed by GE.Note - Independent test of teak wood shall be carried out by GE before payment and reports kept on record duly verified, signedand approved. 79 M & L for 25mm thick first class hard wood (teak) wrought, decorative wooden facia/eves board and chemically treated with/lattoo, patang patti, ring and kiosk on chajja with complete width as per existing design including necessary scaffolding and safety measuresincluding applying two coats of french polishing over primer as approved by the Engineer In-charge.Note - Independent test of teak wood shall be carried out by GE before payment and reports kept on record duly verified, signedand approved. 80 M&L for Carefully scrapping and removing of multiple layers of white wash, enamel paint, distemper, oil paint, algae, etc. from underside of wooden ceiling gently with care to keep old designs intact using approved brand paint removers, sand papering the surface without damaging the historic fabric of building ( Blow tourch method for cleaning of wooden member not to be used)including antitermite treatment, filling minor cracks by saw dust mixed with approved adhesive applying two coats of french polishing over primer as approvedincluding necessary scaffolding and safety measures complete all as specified and as directed by GE. 81 M&L for complete removal of old paint of any layers from wooden ceilling and existing vertical wooden members or other members as directed and providing anti-termite treatment using cloropyriphos 20% E.C. (in oil or kerosene based solution) and applying two coats of french polishing over primer including necessary scaffolding andsafety measures complete all as specified in SSR Part I and directed. 82 M&L for Stitching of cracks in stone masonry using stone as per existing size, typeand pattern and cement mortar (1:3) in historic structure after raking, cleaning and washing the cracks including all leads, lifts and carriage complete all as specified and as directed by Engineer in -charge 83 Material and Labour for detailing fabricating and fixing built up sections at desired location using MS plates of grade Fe 250 and erecting structural steel members for all heights & at all levels including provision of necessary erection bolts, fixing bolts, nuts, washers, cleats, stiffeners, gusset plate, base plate, and all necessary operations like preheating as per specification, straightening, bending, cutting. drilling, grinding, machining if required, welding, grinding and removing the welding burr and preparing surface with wire brush to remove all dust, rust etcand applying two coats of epoxy red oxide zinc phosphate primer of 30 microns each and two coats of Epoxy Corrosion Resistant Enamel paint of 30 micronsincluding touching up with spray painting after erection complete as directed by Engineer in Charge. 84 M&L for carefully removal of wooden ceiling/ support frame / associated cornices/ beading/ moulding in internal area of room with proper care without damaging historic fabric of building and stacking of ceiling at safe place for refixing of the same, as directed by Engineer in charge, including all leads, lifts and carriage. 85 M & L forPTMT Bottle Trap for Wash basin and sink 38mm single piece moulded with height of 270mm, effective length of tail pipe 260mm from the centre of the waste coupling 77mm breadth with 25mm minimum water seal, weighing not less than 263gms complete all as specified.. 86 M & L for removing / uprooting of vegetation, grass, bush wood, trees and saplings of all girth and any height above/below ground level and disposal of rubbish outside MD land complete all as directed.Note:- Place of disposal shall be find out by the Contractor. 87 M & L for De vegetation from the monuments by chemical injection of Round Up (arsenic base) compound and subsequently uprooting of all vegation of any girth and height without damaging the historic fabric and structure of the building under strict supervision of Engineer-in-Charge. 88 M & L for repairing of Frames and Shutter of Windows includingdecorative arched panels, wherever frame is damaged/ broken/ deteriorated to be replaced with first class hard wood (teak) chemically treated as per tradional wooden joinery of members and fixed in position with the help of holdfasts/ traditional holdfast/ handmade nails etc.including carving/ engraving of existing patterns on frames, shutters, decorative arched panels wherever missing or damaged and removal of multiple layers of paints/ enamel paints on the frame, shutter, panel as per presrcibed process and specification and finished with primer and red oxide of appropriate shade or polish including all leads, lifts and carriage up to all heights including anti termite treatment before fixing in poisiton and to contact with masonasry. Item to include 40- 50 mm thick fully/partialy glazed openable shutters, panneling of door in wood /glass using 6mm thick Clear float Glass,for doors/windows/ventilator as per the existing original design and pattern including all necessary fitting/ hardware like screws, nails,metal spikes ,ornamentel nails ,metal patterns of flower, metal ribets , parlimentary hinges, tower bolts, handles, traditional handmade MS nails, traditional locking system ,decorative features( butt hinges/tower bolt/ handle /door Aldrop/lock ) of the same design, size and weight, etc . Item to also include making all the mouldings and design of the panels werever missing/ damaged/ latter added is replaced asper original detail with all beading, patti,carving, marking , as per size given/ orignal existing detail/ drawing of shutter /pannel including removal of multiple layer of paint /enamel paint with prescribe process and applying two coats of french polishing over primer as approvedincluding necessary scaffolding and safety measures complete all as specified and as directed by GE ( Area of each shutter not exc. 10 Sqm). 89 M & L for repairing of Frames and Shutter of Doors includingdecorative arched panels, whereevr frame is damage/ broken/ detririorated to be replaced with first class well seasoned chemically treated Teak Wood as per tradional wooden joinery of mebers and fixed in position with the help of holdfasts/ traditional holdfast/ handmade naisl etc. Items inclusive of carving/ engraving of patterns on frames, shutters, decorative arched panels wherever missing or damaged and removal of multiple layers of paints/ enamel paints on the frame, shutter, panel as per presrcibed process and specification and finished with primer and red oxide of appropriate shade or polish including all leads, lifts and carriage up to all heights. Item also includes anti termite treatment of wood before fixing in poisiton, coating/ paitning of section of embedded timber coming into contact with masonasry. Item to include 40- 50 mm thick fully/partialy glazed openable shutters, panneling of door in wood /glass using 6mm thick Clear float Glass ,for doors/windows/ventilator as per the existing original design and pattern /or design including all necessary fitting/ hardware like screws, nails,metal spikes ,ornamented nails ,metal patterns of flower, metal ribets , parliamentary hinges, tower bolts, handles, traditional handmade ms nails, traditional locking system ,decorative features( butt hinges/tower bolt/ handle /door Aldrop/lock ) of the same design, size and weight, etc . Item to also include making all the mouldings and design of the panels werever missing/damage/latter added is replaced as in the original detail with all beading, patti,carving,marking , as per size given/ orignal existing detail/ drawing of shutter /pannel and removal of multiple layer of paint /enamel paint and applying two coats of french polishing over primer as approvedincluding necessary scaffolding and safety measures complete all as specified and as directed by GE ( Area of each shutter not exc. 10 Sqm). 90 M&L for 35 mm thick second class hard wood (Sal) plain, framed panelled shutter (two panel) with lock rail and panel of 9mm B.W.P commercial ply or 12mm veneered partical board with commercial veneering on both faces. The size of rail and stile as per IS: 1003 (Part I),kiln seasoned and chemically pressure treated complete all as specified. 91 S&F first class hard wood (teak) glazed and Skelton shutters, 30mm thick, open rebated and prepared to receive glass gauze etc, divided into squares, with plain, chamfered or rounded mitred and rebated sash bars, any numbers, edges of framing plain, chamfered or rounded, fitted with cut & mitred beads for securing glass, gauze, etc size of members of shutters as specified in SSR part I, section 8, clause, 8.20 (b) complete all as specified. 92 M&L for preparing new wooden surfaces of any description, not otherwise described over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of pink primer complete all as specified. 93 M&L for preparation of old painted wooden surfaces of any description not otherwise described over 10 cm width or girth & applying one coat of synthetic enamel paint complete all as specified. 94 M&L for preparing new steel surfaces of any description over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified. 95 M&L for preparation of old painted steel surfaces of any description not otherwise described over 10 cm width or girth & applying one coat of synthetic enamel paint complete all as specified. 96 M&L for preparing new plastered surfaces of walls/ceilings and applying two coats of weather proof antifungal acrylic exterior paint (100% Acrylic) over a coat of self primer including necessary scaffolding and safety arrangement complete all as specified. 97 Supply & Fixing in repairs rotational moulded polythylene water storage loft tankof 1000 ltr capacityincluding all connections for inlet, outlet, over flow and wash out etc hoisted andfixed in position all as specified in SSR Part-I 98 M&L for preparing new plastered surfaces of wall and applying two coats of oil bound distemper over a coat of alkali resistant primer complete all as specified. 99 M & L for complete removal of existing treatment including washing, rubbing down and stopping of distempered and painted wall surfaces, filling holes and cracks with filling putty on wall and applying one coat ofwall care putty not less than 1mm thickness and makingthe surface even and smooth using emery paperand applying two coats of oil bound distemper over a coat of alkali resistant primer complete all as specified. 100 M&L for preparing old painted surfaces of walls/ceilings/ chajja/ paraper/ facia and applying one coat of weather proof antifungal acrylic exterior paint (100% Acrylic)including necessary scaffolding and safety arrangement upto 15 mtr height complete all as specified. 101 Dismantling plain or corrugated steel sheeting, any gauge or thickness including Nainital or similar pattern roof coverings all as specified and directed. 102 Dismantling battens for tiles, shingles etc of any size including tilling fillets exceeding 15 cm space. 103 M&L for roof tiles, Mangalore pattern, interlocking at side joints, laid dry including dismantling old single layer Mangalore pattern or similar tiles in roofing. 104 -Ditto- all as per item No 103.00 above but except tiles in repairs. 105 S & F in repairs Ridge or hip tiles to suit Mangalore pattern of roofing tiles, bedded and jointed in cement mortar 1:6 complete all as specified and directed. 106 M&L for providing water proofing treatment with 2 mm thick APP (Atactic Polypropylene) modified bituminous membrane reinforced with non woven polyester mat of weight not less than 180 gms/Sqm as centre core and without multiple layers of polythene finished on top and bottom with 7 micron thick flammable polythylene applied by thermo fusion using LPG torch on bottom portion of the membrane over a coat of bituminous primer @ 0.25 Kg/Sqm over wooden boarding/ plywood at roof and over the APP membrane provide a polypropylene/ polyester, Non woven geotextile fabric of 150 gsm over the geo textile fabric (An overlap of 100mm at end & 75mm shall be provided on sides ends respectively) complete all as per manufacturers instructions and asdirected by Engineer-in- Charge. 107 Material and Labour for Melamine polish by applying 2 coats of Asian paint Wood tech sealer , one coat of Asian Paints Woodtech exerior wood stain of shade as approved by GE, followed by 2 coats of Asian paints Wood tech Gold melamine clear matt finish complete on old or new wood surfaces including preparing surface by scrapping sand papering and wipe cleaning after every coat, using spray machine for all the coats, adding thinner to every coat, including removing of old synthetic anamel painting including necessary scaffolding if requiredcomplete all as specified and directed by Engineer-in-Charge. 108 S&F pre-painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified 109 S&F pre-painted galvalume aluminium zinc coating GI based plain steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as inridges/ Flashings fixed with self tapping screws complete all as specified. 110 M & L for 12mm thick plywood, grade BWR, type BB, fixed with screws to timber frame work complete all as specified and as directed by Engineer-in-Charge. 111 M & L for 1.5 mm thick galvanized steel sheet as in Valley gutters fixed with rivets or other suitable arrangements over MS brackets Trapezoidal shape of required profile with desired slope complete all as specified and as directed by Engr-in-Charge. 112 M & L for rolled mild steel sections as in main and cross beams, hip and jack rafters; purlins where connected to common rafters and running rails and guides for siding doors; fixed with angle cleats or other connceting plates conforming to Gde Fe 410-W (Gde E-250 quality A) complete all as specified 113 S & F cast iron safty grill, railing, framing as per approved design/size including welding complete all as specified. 114 M&L forremoval of PCC tiles including APP memberane, China mosaic Chips, Stone surface or any other treatment any thickness excluding PCC,cleaning of RCC roof slab with wire brushing, washing out with water and finally remove dirt using air jet and removal of debries out of MD land, identifying the cracks, damaged surface,cutting out cracks to `V sectionin existing roofs or terracing, cleaning out, wetting, grouting with and filling the same with polymer modified mortar/injection grout of approved company complete all as specified and directed.Note: Polymer modified mortar/injection grout will be measured and paid seperately. 115 Material & Labour for PCC 1:2:4 type B-0 (using 12.50 mm graded stone aggregate) as a leveling course / padding on RCC roof top/ chajja surfaces laid to slope and finished fair and even complete all as specified. 116 M&L for cement concrete tiles 250mm x 250mm x 22 mm thick, machine pressed (with grey cement & no pigments)set, jointed and pointed in neat cement slurry laid over and including 15 mm thick screed bed or bedding layer in cm (1:3) over waterproofing treatment complete all as specified. 117 Providing and erecting and dismantling scaffolding with 40 mm dia MS pipe, cup locks( weighing not less than 6.31 kg each) .MS base jacket for fixed or adjustable with necessary MS clamps, clouders, MS brackets for projections , joint pins, pulleys and other accessories including steel angle or tubular pipe bracing at adequate intervals, including wooden planks or metal platforms any type of span, centre to centre, horizontal or vertical tubes joints with cup or locking with MS tubes, MS clamps upto 11 mtr height of bldg.the paymet will be made once only for execution of all items for such work.Note : Scaffolding to be provided till completion of the work. 118 Erection and dismantling heavy duty nylon wire mesh (Jalli) 6mm dia (sample kept in GE Kunjali)to protect all the construction material from the roof/bldgcomplete all as specified and directed by Engineer-in-Charge. 119 Providing and maintaining barricading on the site 2.5m high by using MS pipes or angle iron frame work for verticals at 3 m c/c and horizontals at 0.90 mc/c, Glavalume sheets, struts, MS clamps, etc.The verticals shall be embedded/fixed to concrete pedestals below ground.The rate to include fabricating, cutting and fixing in position MS frame work, painting the same with two coats of approved anti rust paint, etc complete.Contractor shall remove and take away the barricading at his own cost on completion of the works complete all as specified and directed by Engineer-in-Charge. 120 S&F in repairs galvanized 2 strand steel barbed wire 2.24mm dia barbed with 2mm dia barbs at 75mm spacing and straining and fixing to any type of standard rails, straining bolts, including securing or typing at crossing with and provn of galvanized mild steel wire staples or steel pins etc as directed (each line of wire to be measured). 121 M & L for expanded metal, cut to length, bent to shape required and tying with and including annealed mild steel wire not less than 0.90mm dia or fixing with galvanised steel staples, weight n exc 4 Kg per Sqm and fixed to wood or teel members. 122 Supply and fixing in repairs concertina coil wire of 50 turn having core wire of high carbon spring steel of high tensile strength and a carbon steel strip of 20 mm width, 0.5 mm thick having razor sharp barbs punched tape and core wire hot dip galvanised complete all as specified and directed by Engineer-in-charge 123 Supply only integral water proofing compound. 124 M & L for complete removal of existing treatment from wall, ceiling,soffits, roof facia etc including washing, rubbing downand applying two coats of weather proof acrylic based paint (100% acrylic) exterior grade over one coat of self primerincluding necessary scaffolding and safety arrangement complete all as specified and directed. 125 Supply & Fixing 6mm thick superior quality looking mirror of selected quality glassincluding 25mm wide first class hard wood (teak) decorative moulding on all sides duly polished with one or more coats of French polishing over a coat of wood filler and fixed to wooden plugs with chromium plated brass screws and cup washers complete all as specified. 126 M & L for solid PVC Wall Lining consisting of 5mm thickwood grain printed PVC sheet used insead of PVC sheet inclusive of solvent cement and fixing at site on PVC frame as per specifications and drawing shown in SSR Part II and as per manufacturers instructions.. 127 M & L for 5mm thick PVC sheet fillet of width 35mm for wall paneling inclusive of fixing on to wall to make PVC frame as per specification and drawing shown in SSR Part II and as per manufacturers instructions... 128 Taking down shutters of any description exc 1 sqm and n exc 2 sqm each and refixing in the same opening after repair all as directed. 129 Supply & Fixing 3 mm thick aluminium composite panel cladding plain of approved colour/ shade to beam/ column/ slab in circular/rectangular shape including cutting, notching, bending to shape as required jointing with silicon gel of approved colour & aluminium tubular hollow section 25 x 25 mm not exceeding 900 mm C/C on exceeding column/ beam/ slab to hold ACP cladding etc (Note : colour/pattern of ACP sheet shall be approved by Engr-in-charge) 130 Dismantling stone slabs, pavers and tiles of any description or thickness in floors, aprons etc laid, bedded and pointed in any mortar including removal of rubbish out side MD land.Note: The place of disposal shall be find out by the contractor. 131 M&L for machine pressed precast concrete inter locking paver block any shape and size with grey cement and pigment conforming to IS-15658-2006 of 60mm thickness M-35 Grade, glossy finished of approved colour laid over and including 25 mm thick fine sand cushion to a line and slope etc and joined complete including spreading screened river sand over surface for filling the joints and gently rolled with vibrator complete all as specified . 132 Demolition and breaking up of 150mm bore SWG / concrete drain pipes set in cement mortar including demolition of PCC in haunching /benching around pipes and removing debris outside MD land complete all as specified.Note: The place of disposal shall be find out by the contractor. 133 Demolition and breaking up of 200mm bore SWG / concrete drain pipes set in cement mortar including demolition of PCC in haunching /benching around pipes and removing debris outside MD land complete all as specified.Note: The place of disposal shall be find out by the contractor. 134 Excavating in trenches n exc 1.5m wide & n exc 1.5m in depth; for foundation, etc. or for manholes n.exc.10 Sqm on plan and n.exc.1.5m in depth and getting out in hard/dense soil completes all as specified. 135 Excavating in trenches n exc 1.5m wide & exc 1.5m but n.exc 3 mtr in depth; for foundation, etc. or for manholes n.exc.10 Sqm on plan and n.exc.1.5m in depth and getting out in hard/dense soil completes all as specified. 136 Returning filling in , including spreading, leveling, watering and well ramming in layers not exc 25 cm. 137 M&L for PCC 1:3:6 type C2 (using 40 mm graded stone aggregate) in bed to 150 mm bore drain pipe including packing under and haunching against the sides of pipesafter they are laid and tested. 138 M&L for PCC 1:3:6 type C2 (using 40 mm graded stone aggregate) in bed to 200 mm bore drain pipe including packing under and haunching against the sides of pipesafter they are laid and tested. 139 M&L for RCC pipes 150mm dia class NP-2 laid in trenches and jointed complete all as specified and directed. 140 M&L for RCC pipes 200mm dia class NP-2 laid in trenches and jointed complete all as specified and directed. 141 M&L for cutting existing salt glazed stonware/ any type of pipes of 150mm internal dia in postion, including jointing socket end of new pipe to the same with packed spun yarn and cement mortar 1:1 complete all as specified and as directed. 142 M&L for cutting existing salt glazed stonware/ any type of pipes of 200mm internal dia in postion, including jointing socket end of new pipe to the same with packed spun yarn and cement mortar 1:1 complete all as specified and as directed. 143 Refixing teak wood full length new members like joists, rafters, purlins, beams, column etc in roof/floor/staircase and where ever required as per siteincluding all fixtures and fastening and apply solignum on the wood surface complete all as specified and directed by Engineer-in-Charge. 144 Taking down and refixing wooden plank upto 40mm thick any type and in any position inluding cutting, groove, nail, screw, gum etc all as specified and directed by Engineer-in-Charge. 145 Material & labour for taking down, chipping out and removing the loose, spailt, damaged cement plaster from surfaces of brick wall, RCC columns, beams, walls, chajjah, stone wall etc and providing 20mm to 30mm thickpolymermodified ready mixed cement based plasterin two coats (1:5:15, polymer,cement, Quartz sand) and finally finishing the surface even and smooth complete all as specified and directed. 146 SCHEDULE A PART II (E/M WORKS) Taking down carefully old U/s point wiring copper/Aluminium (light/ fan /sockets/ power) complete with switches, sockets, fan regulators, ceiling roses, lamp holders, brackets and making good to disturbed surfaces as directed by Engineer-in-Charge 147 Disconnecting & taking down ceiling fan/ Exhaust fan of any make and size, strip opening, cleaning all parts and packing of& greasing ball bearing with specified quality grease and applyingtwo coats of white paint by spray painting complete all as specified. 148 M&L for hanging/ fixing ceiling fan/Exhaust fan in position after completion of B/R work, making electric connections, tested and making good the distrubed surfaces to matching with existing surface complete all as directed. 149 Dismantling/taking down old serviceable light fittings,and refixing at same location after completion of B/R work, making electric connections, tested and making good the distrubed surfaces to matching with existing surface complete all as directed. 150 Dismantling and taking down old serviceable Security/street light fittings of any wattage or size and refixing at same location after completion of B/R work, making electric connections, tested and making good the distrubed surfaces to matching with existing surface complete all as directed. 151 S&F in repair of double door type SPN DB 4 Way ,240Vwith 200A busbar , double door typeIP-54 protectionsuitable for housing MCBs all as specified and directed by Engineer-in-Charge.Note : MCB DBs shall be concealed in wall including making good the surface to match with surrounding . 152 S&F in repair SPN DB 12 Way ,240Vwith 200A busbar , double door type,IP-54 protectionsuitable for housing MCBs complete all as specified and directed by Engineer-in-Charge.Note : MCB DBs shall be concealed in wall including making good the surface to match with surrounding . 153 S&F in repair vertical type TPN DB 8 Way ,240Vwith 200A busbar , double door type IP-54 protectionsuitable for housing MCCBs complete all as specified and directed by Engineer-in-Charge.Note : MCB DBs shall be concealed in wall including making good the surface to match with surrounding . 154 S&F in repair vertical type TPN DB 6 Way ,240Vwith 200A busbar , double door type IP-54 protectionsuitable for housing MCCBs complete all as specified and directed by Engineer-in-Charge.Note : MCB DBs shall be concealed in wall including making good the surface to match with surrounding . 155 S & F MCB SP 6-32 Amps,10KA,C series 240V complete all as specified . 156 S & F MCB SP 40 Amps,10KAC series 240V complete all as specified . 157 S & F MCB SPN 63 Amps,10KAC series 240V complete all as specified . 158 S & F MCB SPN 40 Amps,10KAC series 240V complete all as specified . 159 S & F MCB TP 63 Amps,10KAC series 240V complete all as specified . 160 S & F MCB TP 40 Amps,10KAC series 240V complete all as specified . 161 S&F in repair of MCCB100 Amps 4 pole, 415V, 18KA,240V complete all as specified . 162 S & F in repair Single pole and neutral enclosure with a two pin and earth plug and socket complete with one double pole MCB 20A complete all as specified . 163 S & F in repair of single pole & neutral two way DB without bus bar complete all as specified and directed. 164 M&L for sub-main wiring with 2 runs of 2.5 sqmm copperconductor cable (FRLSgrade), 1100 volts grade PVC insulated and unsheathed multi-stranded, drawn in and including heavy grade PVC Casing caping ISI marked not less than 25mm dia (internal width) with all accessories like tees, elbows, junction boxs, reducer etc as required, including one run of 2.5 sqmm dia PVC insulated unsheathed copper conductor cable as earth dolly/mains, with all accessories like PVC elbow, PVC tee, etc including taking up/down old unserviceable sub main wiring and making good the distrubed surfaces/location complete all as specified and directed. Note - (a) Colour coding shall be folowed as (i) Phase- Red (ii) Neutral - Black(iii) Earth - green(b) 2 runs of 2,5 Sqmm cable, One run of 2.5 Sqmm earth cable and PVC casing capping shall be measured and paid as one length only. 165 M&L for sub-main wiring with 2 runs of 4 sqmm copperconductor cable (FRLSgrade), 1100 volts grade PVC insulated and unsheathed multi-stranded, drawn in and including heavy grade PVC Casing caping ISI marked not less than 25mm dia (internal width) with all accessories like tees, elbows, junction boxs, reducer etc as required, including one run of 4 sqmm dia PVC insulated unsheathed copper conductor cable as earth dolly/mains, with all accessories like PVC elbow, PVC tee, etc including taking up/down old unserviceable sub main wiring and making good the distrubed surfaces/location complete all as specified and directed. Note - (a) Colour coding shall be folowed as (i) Phase- Red (ii) Neutral - Black(iii) Earth - green(b) 2 runs of 4 Sqmm cable, One run of 4 Sqmm earth cable and PVC casing capping shall be measured and paid as one length only. 166 M&L for sub-main wiring with 2 runs of 6 sqmm copperconductor cable (FRLSgrade), 1100 volts grade PVC insulated and unsheathed multi-stranded, drawn in and including heavy grade PVC Casing caping ISI marked not less than 25mm dia (internal width) with all accessories like tees, elbows, junction boxs, reducer etc as required, including one run of 6 sqmm dia PVC insulated unsheathed copper conductor cable as earth dolly/mains, with all accessories like PVC elbow, PVC tee, etc including taking up/down old unserviceable sub main wiring and making good the distrubed surfaces/location complete all as specified and directed. Note - (a) Colour coding shall be folowed as (i) Phase- Red (ii) Neutral - Black(iii) Earth - green(b) 2 runs of 6 Sqmm cable, One run of 6 Sqmm earth cable and PVC casing capping shall be measured and paid as one length only. 167 M&L for sub-main wiring with 4 runs of 10 sqmm copperconductor cable (FRLSgrade), 1100 volts grade PVC insulated and unsheathed multi-stranded, drawn in and including heavy grade PVC Casing caping ISI marked not less than 25mm dia (internal width) with all accessories like tees, elbows, junction boxs, reducer etc as required, including two run of 6 sqmm dia PVC insulated unsheathed copper conductor cable as earth dolly/mains, with all accessories like PVC elbow, PVC tee, etc including taking up/down old unserviceable sub main wiring and making good the distrubed surfaces/location complete all as specified and directed. Note - (a) Colour coding shall be folowed as (i) Phase- Red (ii) Neutral - Black(iii) Earth - green(b) 4 runs of 10 Sqmm cable, two run of 6 Sqmm earth cable and PVC casing capping shall be measured and paid as one length only. 168 Supply and fixing in repairLED 90W Street/building security light fittings with high pressure die cast housing with toughened glass and individual LED with secondary optics and IP 66 protection, not less than 100 lumen per watt complete all as specified . 169 S&F MS arms bracket (BEST-Pattern) for mounting one Street/Building security light fitting made out of 40 mm medium grade GI pipe at an angle of 30 degree including clamp/nut/bolts & washers to brace the same properly and applyingtwo coats of synthetic enamel paintin silver colour complete all as specified & directed by EIC. 170 Supply and fixingin repair new generation walll/surface mounted bluk head LEDfitting 10W,not less than 120 lumen per watt provides high quality ecomonic energy saving lightingcomplete with all accessories internally pre-wired and connecting up with three core flexible copper conductor cable of suitable size from ceiling rose including two PVC box of size 75 x 75x 20mm for mounting light fitting complete all as specified. 171 Supply and fixing in repair walll/surface mounted 20W LED batten fitting, not less than 120 lumen per watt made out of engineering plastic with white acrylic cover with all accessories internally pre-wired and connecting up with three core flexible copper conductor cable of suitable size from ceiling rose including two PVC box of size 75 x 75x 20mm for mounting light fitting complete all as specified. 172 Supply and fixing in repair new generation slim recessed LED 2X2 Luminaire 36 watt, not less than 120 lumen per watt and CRCA powder coated body and high translucent diffuser provides high quality ecomonic energy saving lighting to modern offices suitable for 600 x 600 mm modular/POP/Gypsum ceiling with all accessories internally pre-wired and connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified. 173 M & L for 4mm dia galvanised iron Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to DBs or any other indicated situation for loop earthingcomplete all as specified . 174 Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 Sq mm 3½ core laid in trench or along wall,ceilingincluding suitable size MS clamp complete all as specified . 175 M & L for point wiring with 1.5 sqmm (nominal area) PVC insulated and unsheathed multistranded FRLS copper conductor cable ISI marked 1100 volts grade drawn through and including25mm wide PVC casing caping (ISI marked) with all accessories and terminated in and including PVC modular box with modular cover plate and frame of sutable size and module including 1.5 sqmm size PVC insulated, unsheathed, multistranded FRLS copper conductor cable ISI marked for continuous earth conductorand connecting to earth dolly for the following :- Note: a) Colour coding shall be folowed as (i) Phase- Red (ii) Neutral - Black(iii) Earth - greenb) Electrical wiring above false ceiling shall be drawn through medium grade PVC conduit of suitable size. 176 One light point controlled by one 5 Ampsswitch 177 One Fan point controlled by one 5 Ampsswitch 178 One 5 Amps flush type switch socket point on same boardwith other switches 179 One5 Amps flush type switch socket point on independent board 180 One Bell point controlled by one bell push 181 M & L for point wiring with 2.5 sqmm (nominal area) PVC insulated and unsheathed multistranded FRLS copper conductor cable ISI marked 1100 volts grade drawn through and including25mm wide PVC casing caping (ISI marked) with all accessories and terminated in and including PVC modular box with modular cover plate and frame of sutable size and module including 2.5 sqmm size PVC insulated, unsheathed, multistranded FRLS copper conductor cable ISI marked for continuous earth conductorand connecting to earth dolly for one 5 pin, 15 Amps switch socket combination on the independent board complete all as specified and directed.Note: a) Colour coding shall be folowed as (i) Phase- Red (ii) Neutral - Black(iii) Earth - green 182 M & L for point wiring with 2.5 sqmm (nominal area) PVC insulated and unsheathed multistranded FRLS copper conductor cable ISI marked 1100 volts grade drawn through and including25mm wide PVC casing caping (ISI marked) with all accessories and terminated in and including PVC modular box with modular cover plate and frame of sutable size and module including 2.5 sqmm size PVC insulated, unsheathed, multistranded FRLS copper conductor cable ISI marked for continuous earth conductorand connecting to earth dollyfor 02 Nos 6A sockets and 01 No 15A socket on one board complete all as specified and directed.Note: a) Colour coding shall be folowed as (i) Phase- Red (ii) Neutral - Black(iii) Earth - green 183 S & F ceiling rose surface bakelite 65 x 50mm, flush type, 3 terminals complete all as specified . 184 S & F modular switch 1 way 6A,1 module complete all as specified . 185 S & F modular switch 1 way 16A,1 module complete all as specified . 186 S & F Bell push, 5/6 Amps,1 module 240 volts complete all as specified . 187 S & F modular socket, 6A - 2/3 pin combined 2 modules complete all as specified . 188 S & F modular socket 6/16A,2/3 pin, combined 2 module complete all as specified . 189 S&F for modular fan step regulator, 120W - 2 modular complete all as specified . 190 S & F bell, DING DONG, 240 volts, SP complete all as specified . 191 S & F in repairs LED gate light post top lanterns 20 W decorative robust and reliable LED post top light with transparent diffuser and IP 65 protection with all accessories including tapper plug, bolts, nuts, screws etc complete all as specified and directed by Engr-in-charge. 192 Removing the existing window type Air conditioner 1.5/2 TR capacity including all accessories and closing opening of wall with brick work in cement mortor 1:4, rendering 15mm thick in CM (1:4) , apply two coats of oil bound destemper to match with surroundings and fixed in other location, making all connections, topping up gas including making suitable size opening in existing wall , fixing wooden frame made out of not less than 50x75mm second class hard wood runners, apply two coats of synthetic enamel paint over pink primerand making good disturbed surfaces as perexisting and testing after completion complete all as specified & directed by Engr-in-Charge. 193 S&F galvanised iron strip 25 x 4 mm fixed to wall with clamps or recess or buried in ground or drawn in conduits/pipe or fixed to poles or any other indicated situationfor loop earthing as required complete all as specified and directed by Engr-in-Charge. 194 Supply , fixing, testing in repairsof JEF ECO SAFE Maintenance Free Grounding Solution set comprising of High tensile low carbon steel rod of 3 Mts length & 25 mm dia with 250 micron ( avera Schneider ) molecularly bonded copper on the outer surface to confirm with requirements of UL467 along with Back-fill compound strictly be a Carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm Mtr as per Clause 14.5D of IEEE : 80 standard. Back-fill compound should be electronically conductive ( Like in metals ) and should not depend on moisture for conduction. JEF Powerfill Loresco compound shall be supplied in 50 Pound Bag. ( 1 Bag of 50 Pounds required per earthing set). Back-fill comound should be environment friendly, should solidify when mixed with water and set like concrete and should not leach / diffuse into the ground. A suitable earth terminaton clamp should also be supplied along with the set alongwith earth pit weatherproof incl all as specified .Note : Back-fill compund shall not be mixed with any soil while pouring in the bore hole. 195 SCHEDULE A PART III (EXTERNAL ELECTRIFICATION) Supply, laying,connecting & testing 50 Sqmm x 3.5 core XLPEinsulated armoured heavy duty1100 volts grade, aluminum conductor cable laid in trenches / pipes / fixed on wall with suitable size GI clamps including taking out old cable complete all as specified and directed.Note :-(i)PCC cable cover, sand cushioning , excavation and earth work shall be measured and paid separately .(ii) Rate quoted shall be deemed to be included for necessary aluminium lugs,cable glands etc complete. 196 S& F in repairs GI cable tray perforated type 2 mm thick of size 250mm x 50mm (includingpre fabricated GI clamp suitable for fixing/supporting )with 0.71mm thick aluminium sheet cover, alloy 31000 H4 in ridges, Hips vally gutter cable trucking fixed onany wall (brick/stone) vertically/horizontally including all accessories and bending,shaping,drilling,welding, cutting & all fixing arrangement complete etc all as directed 197 Supply, laying,connecting & testing 25 Sqmm x 4 core XLPEinsulated armoured heavy duty1100 volts grade, aluminum conductor cable laid in trenches / pipes / fixed on wall with suitable size GI clamps including taking out old cable complete all as specified and directed.Note :- (i) PCC cable cover, sand cushioning , excavation and earth work shall be measured and paid separately .(ii) Rate quoted shall be deemed to be included for necessary aluminium lugs,cable glands etc complete. 198 Excavating in trenches n exc 1.5m wide & n.exc 1.5 mtr in depth; for laying cables and getting out in soft/ loose soil complete all as specified. 199 Returning filling in , including spreading, leveling, watering and well ramming in layers not exc 25 cm. 200 Removing excavated material n.exc 50 m and depositing where directed at a level n.exc 1.5 m above the starting point. 201 M & Lfor dry river sand ascushioning for protection of UG cable including punning of sand in layers all as specified.Note: Thickness after punning down shall be measured and paid 202 Supply & laying sub class B bricks laid across the cablefor protection complete all as specified & directed. 203 S & F in repairs GI pipe 80 mm bore light grade for protection of cablelaidin trenches or fixed to poles/wall with and including suitable size GI clamps complete all as specified. 204 Supply and fixing in repairs LED flood light fittings 50 watt ( green colour light) 230 V, AC, not less than 100 lumen per watt with high pressure die cast housing with toughened glass and individual LED with secondary optics thermal management in equipped with IP66 protection with driver and lamp and connecting up with and including three core flexible copper conductor cable of suitable size complete all as specified. 205 S & F LED bollard lights 10W230 V, AC, not less than 100 lumen per watt with high efficiency PMMA diffuser ensuring maximum illumination aspect in surronding and IP66 protection with driver and connecting up with and including three core flexible copper conductor cable of suitable size complete all as specified.
|