Day To Day Maintenance Of Electrical Systems- 1 Supplying, installation, testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required. 1 output per phase and suitable for single phase supply. 2 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. 3 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.(Group C) 4 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire 5 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire 6 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire 7 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit. 4 X 6 sq. mm + 2 X 6 sq. mm earth wire 8 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit. 4 X 10 sq. mm + 2 X 6 sq. mm earth wire 9 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit.4X 16 sq. mm + 2 X 6 sq. mm earth wire 10 Supply & Fixing of ML 2 AC Contactor ISI Mark Reputed make. (As per direction by Engineer Incharge) 11 Supply, Installation,Testing and Commissioning of 150 watt+ 10% LED lights (reputed make Bajaj/Crompton Greaves/Havells/ Syska/ Philips/ HPL/Surya/ Ledure or Equivalent make) ISI Mark.(As per direction by Engineer Incharge). 12 Erection of steel tubular pole strut in cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling and secured with holding clamps, bolts, nuts, etc. as required. 13 Dismantling and carriage of steel tubular pole strut in cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling and secured with holding clamps, bolts, nuts, etc. and carrriage to different site with in the JMC limits as required(As per direction by Engineer Incharge) 14 Supply, Installation,Testing and Commissioning of 20 watt/ 15 Watt + 10% LED Bulbs (reputed make Bajaj/Crompton Greaves/Havells/ Syska/ Philips/ HPL/Surya/ Ledure or Equivalent make) ISI Mark.(As per direction by Engineer Incharge). 15 Supply & Fixing of Change Over Switch as per IEC 60947 Part 1 & 3 / IS 13947 part 1 & 3 to be enclosed in CRCA Sheet steel 18/20 SWG standard with powder coated, rust protected(if 16/18 SWG/1.62/1.21 mm Nost avilable) with PVC insulated cu wires for interconnection, bus bar, earthing terminal, and all other accessories to complete the work. Changeover switch shall be wall/column mounted. Enclosure shall be weather proof.Colour shade shall be as per IS 5. MS angle iron frame to mount the unit is included.IP for enclosure shall be IP43 for Indoor unit and IP 55 for Outdoor unit100 Amp. 415V TP Changeover Switch with CRCA sheet steel powder coated enclosure. 16 Supply, Installation,Testing and Commissioning ofreputed make RO 50LPH Commercial (Kent / Eureka Forbes) 17 Supply, Installation,Testing and Commissioning of300 mm sweep Exhaust fan (reputed make ISI mark) 18 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch 19 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 A switch 20 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 A socket outlet 21 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 A socket outlet 22 Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delitery minimum 215 CMM, 350 RPM (tolerance as per IS: 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise 75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. 23 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 way (4 + 12), Double door 24 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way (4 + 18), Double door 25 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way (4 + 24), Double door 26 Supplying and fixing following size/ modules, GI box alongwith Modular base & cover plate for modular switches in recess etc. as required. 1 or 2 Module (75 mm X 75mm) 27 Supplying and fixing following size/ modules, GI box alongwith Modular base & cover plate for modular switches in recess etc. as required. 3 Module (100 mm X75 mm) 28 Supplying and fixing following size/ modules, GI box alongwith Modular base & cover plate for modular switches in recess etc. as required. 4 Module (125 mm X 75mm) 29 Supplying and fixing following size/ modules, GI box alongwith Modular base & cover plate for modular switches in recess etc. as required. 6 Module (200 mm X 75mm) 30 Supplying and fixing following size/ modules, GI box alongwith Modular base & cover plate for modular switches in recess etc. as required. 8 Module (125 mm X 125mm) 31 Supplying and fixing following size/ modules, GI box alongwith Modular base & cover plate for modular switches in recess etc. as required. 12 Module (200 mm X 150mm) 32 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole 33 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole and neutral 34 Supply of Bamboo Ladders (20 Ft. Length, Width 1.6’ from upper side, Width 2’ from down side) (As per direction by Engineer Incharge) 35 Supply of Heavy duty 6/10 Amp 5 socket & switch with LED indicator and extra fuse powerextension board,240v,1000 w,spike guard (4 and abovemtr. Long wire) (reputed make)
|