Construction Of 220 Kv Gis Substation Imt Phase-Iii Rohtak; 1 220kV System245kV, 2000A, single 3 – ? or three 1 –?, SF6 gas insulated, metal enclosed Bus bar arrangement, consisting of 2000Asingle 3 – ? or three 1 –? SF6 gas insulated switchgears, each Bus Bar comprising of :-Bus bar enclosures running the length of the switchgear to interconnect each of the circuit breaker bay modules in double main bus system.Three, 2-core, single phase or single 3 – ?, 2 core voltage transformers/ PTs.2000A, One 3 – ? or three 1 –?, single pole, group operated isolator/disconnector with one, 3 – ? or three 1 –?, single pole, group operated earthing switch with manual and motor driven operating mechanisms.Bus bar enclosures running the length of the switchgear to interconnect each of the circuit breaker bay modules in double main bus system.Three, 2-core, single phase or single 3 – ?, 2 core voltage transformers/ PTs.2000A, One 3 – ? or three 1 –?, single pole, group operated isolator/disconnector with one, 3 – ? or three 1 –?, single pole, group operated earthing switch with manual and motor driven operating mechanisms. 2 245kV, 2000A, single 3 – ? or three 1 –?, Bus coupler bay module, consisting of 2000Asingle 3 – ? or three 1 –? SF6 gas insulated switchgears, comprising of:2000A, One 3 – ? or three 1 – ?, SF6 gas insulated circuit breaker, complete with operating mechanism.Three, 5-core, single phase current transformers (1200-800-400/1-1-1-1-1A)2000A, Two sets of single pole, group operated isolator/disconnector switches each with single pole, group operated earthing switch and complete with manual and motor driven operating mechanisms.Each GIS compartment with gas monitoring device, pressure switch etc. as required.Terminal boxes/ Local Control Cubicle.Interconnecting wiring/ piping.Grounding, support structures and platforms. 3 245kV, 1250A, single 3 – ? or three 1 –?, Transformer feeder circuit breaker bay module,consisting of 1250Asingle 3 – ? or three 1 – ? SF6 gas insulated switchgears, for transformer, each comprising of:-1250A, One 3 – ? or three 1 –?, SF6 gas insulated circuit breaker, complete with operating Mechanism.Three, 5-core, single phase current transformers (450-300/0.577-1-1-1-1A)1250A, One 3 – ? or three 1 –?, single pole, group operated isolator/disconnector without earthing switch, complete with manual and motor driven operating mechanisms.1250A, One 3 – ? or three 1 –?, single pole, group operated isolator/disconnector with one 3 – ? or three 1 –?, single pole, group operated earthing switch, complete with manual and motor driven operating mechanisms.1250A, One 3 – ? or three 1 –?, single pole, group operated isolator/disconnector with two earthing switches each comprising of one 3 – ? or three 1 – ?, single pole, group operated earthing switches complete with manual and motor driven operating mechanisms.GIS Bus compartment with gas monitoring device, pressure switch etc. as required.Terminal boxes/ Local Control Cubicle.Interconnecting wiring/ piping.Grounding, support structures and platforms. 4 245kV, 1250A, single 3 – ? or three 1 –?, Transmission line feeder circuit breaker bay modules, consisting of 1250Asingle 3 – ? or three 1 –? SF6 gas insulated switchgears, each comprising of:-1250A, One 3 – ? or three 1 – ?, SF6 insulated circuit breaker, complete with operating mechanism.Three, 5- core, single phase current transformers (1200-800-400/1-1-1-1-1A)1250A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector without earthing switch, complete with manual and motor driven operating mechanisms.1250A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one, 3 – ? or three 1 – ?, single pole, group operated earthing switch, complete with manual and motor driven operating mechanisms.1250A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one normal and one high speed fault make 3 – ? or three 1 – ?, single pole, group operated earthing switches, complete with manual and motor driven operating mechanisms.Each GIS compartment with gas monitoring device, pressure switch etc. as required.Terminal boxes/ Local Control Cubicle.Interconnecting wiring/ piping.Grounding, support structures and platforms. 5 220kV XLPE Copper cables (4X1CX500mm2) to connect 220kV side ofeach 160MVA Transformer with GIS (approx) 6 Termination kit at both ends for 220kV XLPE Copper cables (1CX500mm2).(Termination Kit for (GIS/AIS) both ends along with all accessories constitute a set) 7 220kV XLPE Copper cables (4X1CX400mm2) to connect 220kV side ofeach 100MVA Transformer with GIS (approx) 8 Termination kit at both ends for 220kV XLPE Copper cables (1CX400mm2).(Termination Kit for (GIS/AIS) both ends along with all accessories constitute a set) 9 220kV XLPE Copper cables (4x1CX1000mm2) to connect 220kV transmission line feeders with GIS. (approx) 10 Termination kit at both ends for 220kV XLPE Copper cables (1CX1000mm2).(Termination Kit for (GIS/AIS) both ends along with all accessories constitute a set) 11 Ventilation system (AHU) to accommodate in designated room in GIS hall as per Annexure-V as it is already an integral part of the ventilation system. 12 132kV system145kV, 2000A,single 3 – ? or three 1 –?, SF6 gas insulated, metal enclosed bus bars arrangement, consisting of 2000Asingle 3 – ? or three 1 –? SF6 gas insulated switchgears, each Bus Bar comprising of :-Bus bar enclosures running through the length of the switchgear to interconnect each of the circuit breaker bay modules in double main bus system.Three, 3-core, single phase or single 3 – ?, 3 core voltage transformers/ PTs.2000A One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector and one, 3 – ? or three 1 – ?, single pole, group operated earthing switch with manual and motor driven operating mechanisms.2000A, One high speed fault make 3 – ? or three 1 – ?, single pole, group operated earthing switches, complete with manual and motor driven operating mechanisms.Each GIS compartment with gas monitoring device, pressure switch etc. as required.Terminal boxes/ Local Control Cubicle.Interconnecting wiring/ piping.Grounding, support structures and platforms. 13 145kV, 2000A, single 3 – ? or three 1 –?, Bus coupler bay module, consisting of 2000Asingle 3 – ? or three 1 –? SF6 gas insulated switchgears, comprising of:2000A, One 3 – ? or three 1 –?, SF6 gas insulated circuit breaker, complete with operating mechanism.Three, 2-core, single phase current transformers (750-500/1-1A).Two sets of isolator/disconnector switches each of 2000A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector switches each with 3 – ? or three 1 – ?, single pole, group operated earthing switch and complete with manual and motor driven operating mechanisms.Each GIS compartment with gas monitoring device, pressure switch etc. as required.Terminal boxes/ Local Control Cubicle.Interconnecting wiring/ piping.Grounding, support structures and platforms. 14 145kV, 1250A, single 3 – ? or three 1 –?, Incomer transformer bay modules, consisting of 1250Asingle 3 – ? or three 1 –? SF6 gas insulated switchgears, for 220/132kV transformers, each comprising of: -1250A, One 3 – ? or three 1 – ?, SF6 gas insulated circuit breaker, complete with operating mechanism for incomer bay from 220/132kV transformer.Three, 4-core, single phase current transformers (750-500/0.577-1-1-1A)1250A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector without earthing switch, complete with manual and motor driven operating mechanisms.1250A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one, 3 – ? or three 1 – ?, single pole, group operated earthing switch, complete with manual and motor driven operating mechanisms.1250A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with two earthing switches each comprising of one 3 – ? or three 1 – ?, single pole, group operated earthing switches complete with manual and motor driven operating mechanisms.GIS Bus compartment with gas monitoring device, pressure switch etc. as required.Terminal boxes/ Local Control Cubicle.Interconnecting wiring/ piping.Grounding, support structures and platforms. 15 145kV, 1250A, single 3 – ? or three 1 –?, Transmission line feeder circuit breaker bay modules, consisting of 1250Asingle 3 – ? or three 1 –? SF6 gas insulated switchgears, each comprising of:-1250A, One 3 – ? or three 1 –?, SF6 gas insulated circuit breaker, complete with operating mechanism for outgoing feeder.Three, 3-core, single phase current transformers (600-300-150/1-1-1A).1250A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector without earthing switch, complete with manual and motor driven operating mechanisms.1250A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one, 3 – ? or three 1 – ?, single pole, group operated earthing switch, complete with manual and motor driven operating mechanisms.1250A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one normal and one high speed fault make 3 – ? or three 1 – ?, single pole, group operated earthing switches, complete with manual and motor driven operating mechanisms.GIS Bus compartment with gas monitoring device, pressure switch etc. as required.Terminal boxes/ Local Control Cubicle.Interconnecting wiring/ piping.Grounding, support structures and platforms. 16 132kV XLPE copper Cable (4X1Cx1000mm2) for connecting 132kV side of 220/132kV transformer with GIS. 17 Termination kit for both ends for 132kV XLPE copper Cable (1C x1000mm2).(Termination Kit for (GIS/AIS) both ends along with all accessories constitute a set) 18 132kV XLPE Copper cables (4x1CX800mm2) to connect 132kV transmission line feeders with GIS. 19 Termination kit at both ends for 132kV XLPE Copper cables (1CX800mm2). (Termination Kit for (GIS/AIS) both ends along with all accessories constitute a set) 20 Ventilation system (AHU) to accommodate in designated room in GIS hall as per Annexure-V as it is already an integral part of the ventilation system. 21 33kV System (Single Bus for each T/F with bus sectionaliser)36kV, 2000A,single 3 – ? or three 1 –?, SF6 gas insulated, metal enclosed bus bars arrangement, consisting of 2000Asingle 3 – ? or three 1 –? SF6 gas insulated switchgears, each Bus Bar comprising of :-Bus bar enclosures running through the length of the switchgear to interconnect each of the circuit breaker bay modules in single bus system.Each GIS compartment with gas monitoring device, pressure switch etc. as required.Terminal boxes/ Local Control Cubicle consisting of all protection relays, mechanism control system, indication system etc.Interconnecting wiring/ piping.Grounding, support structures and platforms. 22 36kV, 2000A,single 3 – ? or three 1 –?, SF6 gas insulated, metal enclosed bus sectionaliser, consisting of 2000Asingle 3 – ? or three 1 –? SF6 gas insulated switchgears, each Bus Sectionaliser comprising of :2000A, One 3 – ? or three 1 – ?, SF6 gas insulated vaccum circuit breaker, complete with operating mechanism for sectionaliser bay.Three, single-core, single phase current transformers (2000-1000/5A)Two sets of 2000A, one 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one, 3 – ? or three 1 – ?, single pole, group operated earthing switch, complete with manual and motor driven operating mechanisms.Two sets of Three, 2-core, single phase or single 3 – ?, 2 corevoltage transformers/ PTs.Two sets of 2000A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one, 3 – ? or three 1 – ?, single pole, group operated earthing switch with manual and motor driven operating mechanisms.Each GIS compartment with gas monitoring device, pressure switch etc. as required.Terminal boxes/ Local Control Cubicle consisting of all protection relays, mechanism control system, indication system etc.Interconnecting wiring/ piping.Grounding, support structures and platforms(1 for each T/F) 23 36kV, 2000A, single 3 – ? or three 1 –?, Incomer transformer bay modules, consisting of 2000Asingle 3 – ? or three 1 –? SF6 gas insulated switchgears, for 100MVA, 220/33kV transformers, each comprising of: -2000A, One 3 – ? or three 1 – ?, SF6 gas insulated vaccum circuit breaker, complete with operating mechanism for incomer bay from 220/33kV transformer.Three, 4-core, single phase current transformers (2000-1000/0.577-5-5-1A)2000A, one 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one, 3 – ? or three 1 – ?, single pole, group operated earthing switch, complete with manual and motor driven operating mechanisms.2000A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one 3 – ? or three 1 – ?, single pole, group operated earthing switches complete with manual and motor driven operating mechanismsEach GIS compartment with gas monitoring device, pressure switch etc. as required.Terminal boxes/ Local Control Cubicle consisting of all protection relays, mechanism control system, indication system etc..Interconnecting wiring/ piping.Grounding, support structures and platforms.Set of Surge Arrestors & Voltage Detectors(2 for each T/F) 24 36kV, 630A, single 3 – ? or three 1 –?, Transmission line feeder circuit breaker bay modules, consisting of 630Asingle 3 – ? or three 1 –? SF6 gas insulated switchgears, each comprising of:-630A, One 3 – ? or three 1 –?, SF6 gas insulated vaccum circuit breaker, complete with operating mechanism for outgoing feeder.Three, 2-core, single phase current transformers (600-300/5-1A)630A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one, 3 – ? or three 1 – ?, single pole, group operated earthing switch, complete with manual and motor driven operating mechanisms.630A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one normal 3 – ? or three 1 – ?, single pole, group operated earthing switches, complete with manual and motor driven operating mechanismsEach GIS compartment with gas monitoring device, pressure switch etc. as required.Terminal boxes/ Local Control Cubicle consisting of all protection relays, mechanism control system, indication system etc.Interconnecting wiring/ piping.Grounding, support structures and platforms.Set of Surge Arrestors & Voltage Detectors(8 for each T/F) 25 36 kV, 630A, 31.5 kA for 3 sec, SF6 gas insulated Capacitor Bay Modules, consisting of 630A single 3 – ? or three 1 –?, SF6 gas insulated switchgears, each comprising of:-630A, One 3 – ? or three 1 –?, SF6 gas insulated vaccum circuit breaker, complete with operating mechanism for outgoing feeder.Three, 2-core, single phase current transformers (400-300/5-5A)630A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one, 3 – ? or three 1 – ?, single pole, group operated earthing switch, complete with manual and motor driven operating mechanisms.630A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one normal 3 – ? or three 1 – ?, single pole, group operated earthing switches, complete with manual and motor driven operating mechanisms.Each GIS compartment with gas monitoring device, pressure switch etc. as required.Terminal boxes/ Local Control Cubicle consisting of all protection relays, mechanism control system, indication system etc. Interconnecting wiring/ piping.Grounding, support structures and platforms.Set of Surge Arrestors & Voltage Detectors(1 for each T/F) 26 36 kV, 630A, 31.5 kA for 3 sec, SF6 gas insulated S/Stn Transformer Bay Modules, consisting of 630A single 3 – ? or three 1 –?, SF6 gas insulated switchgears, each comprising of:- 630A, One 3 – ? or three 1 –?, SF6 gas insulated vaccum circuit breaker, complete with operating mechanism for outgoing feeder.Three, single phase 2-core current transformers (60-30/5-1A)630A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one, 3 – ? or three 1 – ?, single pole, group operated earthing switch, complete with manual and motor driven operating mechanisms.630A, One 3 – ? or three 1 – ?, single pole, group operated isolator/disconnector with one 3 – ? or three 1 – ?, single pole, group operated earthing switches complete with manual and motor driven operating mechanismsEach GIS compartment with gas monitoring device, pressure switch etc. as required.Terminal boxes/ Local Control Cubicle consisting of all protection relays, mechanism control system, indication system etc. Interconnecting wiring/ piping.Grounding, support structures and platforms.Set of Surge Arrestors & Voltage Detectors(1 for each T/F) 27 33kV XLPE copper Cable (6X1Cx1000mm2) for connecting 33kV side of each I/C of 220/33kV transformer with GIS. (Two cables shall be used in each phase for each I/C, i.e. 2 Runs per phase x3 no. Phase x 4 no. I/C) 28 Single phase Termination kit for both end for 33kV XLPE copper Cable (1cx1000mm2).(Termination Kit for (GIS/AIS) both ends along with all accessories constitute a set) 29 33kV XLPE copper Cable (3cx300m2) for connecting 33kV capacitor bank bay 30 Three phase Termination kit for both end for 33kV XLPE copper Cable (3cx300mm2).(Termination Kit for (GIS/AIS) both ends along with all accessories constitute a set) 31 33kV XLPE copper Cable (3cx95mm2) for single ckt. for station transformer 32 Three Phase Termination kit for both end for 33kV XLPE copper Cable (3cx95mm2) (Termination Kit for (GIS/AIS) both ends along with all accessories constitute a set) 33 a)160 MVA 220/132 kV Power T/F along with10% extra T/F oilb) NIFPES for 220/132 kV Power T/F 34 a)100 MVA 220/33 kV Power T/F along with10% extra T/F oilb) NIFPES for 220/33 kV Power T/F 35 220 kV Surge Arrestor 36 220 kV NCT (450-300/1A) 37 220 kV CVT For Line 38 132 kV CVT For Line 39 132 kV Surge Arrestor 40 33 kV Surge Arrestor (Including Cap. Bank Surge Arrestor) 41 33kV L & E switch for Cap.Bank 42 33 kV NCT For 220/33kV T/F (2000-1000/5A) 43 220kV C&R Panels with SASi) Line Protection & Circuit Breaker control panel ( with auto reclose) 44 ii) Transformer protection& Ckt breaker control Panel (without auto reclose ) (forHVside of 220/132kV T/F) 45 iii) Transformer protection& Ckt breaker control Panel (without auto reclose ) (for both HV & LV side of 220/33kV T/F) 46 iii) Bus Coupler cum Bus Bar protection and circuit breaker control panel without auto reclose 47 132kV C&R PanelsLine Protection & Circuit Breaker control panel ( without auto reclose) 48 Bus Coupler Protection & Ckt breaker control Panel without auto reclose(Double Bus bar) 49 Transformer Incomer & Circuit breaker control panel 50 Time synchronizationequipment 51 21.744MVAR, 33 kV Capacitor Bank along with Str. & allied equipment (NCT, Series Reactor etc.,) as per specification. 52 220V 200 AH Lead Acid Tubular type San Container Battery 53 220 V SMPS Battery charger 54 220 V D.C.D.B. suitable for 200AH Battery 55 415 V LT AC MCCB Board 500 A 56 33/0.4 kV Station Transformer 200 KVA 57 100 KVA DG Set along with associated accessories 58 EOT-Crane as per clause 3.10.7 Section-1 and Clause 29.0 of GIS Specification and as per EOT crane specification.For 220kV GIS hall (10 Tonnes) 59 For 132kV GIS hall(5 Tonnes) 60 1.1 kV Copper Control Cable Armoured(FRLS type)for 220 kV bays of size2CX6mm2, 7CX4mm2, 4CX4mm2, 2CX4mm2, 16CX2.5mm2, 10CX2.5mm2, 7CX2.5mm2, 3CX2.5mm2 including Junction box (as per HVPNL Tech. spec ification) 61 1.1 kV Copper Control Cable Armoured(FRLS type) for 132 kVbays of size 2CX6mm2, 7CX4mm2, 4CX4mm2, 2CX4mm2, 16CX2.5mm2, 10CX2.5mm2, 7CX2.5mm2, 3CX2.5mm2 including Junction box (as per HVPNL Tech specification). 62 1.1 kV Copper Control Cable Armoured(FRLS type) for 33 kV bays of size 2CX6mm2, 7CX4mm2, 4CX4mm2, 2CX4mm2, 16CX2.5mm2, 10CX2.5mm2, 7CX2.5mm2, 3CX2.5mm2 including Junction box (as per HVPNL Tech. specification)). 63 650/1100 Volts 3.5 core 240 mm2 aluminium power cable from Aux. Transformer to ACDB 64 650/1100 Volt 3.5 core 70 mm2 aluminium cable for oil filtration set. 65 650/1100 Volt 4 core 16 mm2 armoured copper power cable for MLDB and other cable required as per contract for 220kV bays. 66 650/1100 Volt 4 core 16 mm2 unarmoured copper power cable for MLDB and other cable required as per contract for 132kV bays. 67 650/1100 Volt 4 core 16 mm2 unarmoured copper power cable for MLDB and other cable required as per contract for 33kV bays. 68 Earthing Mat MaterialThe earth mat will be designed / quoted for soil resistivity of 50?m. In case soil resistivity is more than 50?m then the earth mat will be designed for actual soil resistivity. The payment of extra material to be used for earth mat shall be made on pro rata basis. The approximate area of earth mat to be laid is given in the corresponding columns of the substations. However, item will remain a Lot item. Note:-Earthing of sub-station and equipment should be in line with HVPNL Tech. spec.and IEEE-80 considering fault and shock duration of 1 sec.(23000 sq meter (approx) ) 69 Fire Fighting equipments as per specification22.5 Kg Capacity FE CO2 type, Trolley Mounted 70 25 Kg Capacity FE DCP type, Trolley Mounted 71 DCP 9 Kg Capacity, Wall mounted 72 FE CO2 6.5 Kg Capacity, Wall mounted 73 DCP 6 Kg Capacity, Wall mounted 74 Foam Type 9 Litre Capacity, Wall mounted 75 Water CO2 9 Litre, Wall mounted 76 Fire Buckets(12 No.s with stand in one set) 77 Supply and installation of 2 fittings of 240W LED lamps with all accessories for Complete lighting of outdoor Switch yard area including all accessories, cables etc. as per clause 16.0 of section 7 of the specifications. 78 Complete lighting of road and street by providing 90W LED lamps on tubular steel poles at a distance of 15 meter along the roads and streets including all accessories, cables etc. as per clause 16.0 of section 7 of the specification 79 Supply and installation of 35W LED tube fitting on tubular steel poles along Fencing/ boundary wall at a distance of 30 meter including all accessories, cables etc. as per clause 16.0 of section 7 of the specification. 80 Supply and installation of post top lantern 40W LED Lamps with all complete accessories at the entrance gate of sub-station. 81 Supply and installation of 40W LED Lamps with all complete accessories on corners of control room building. 82 High wall type split AC unit of 2 Ton capacity for computer room (2No.) and 220kV & 132 kV C&R Panel rooms (4 No. each) (as per technical specification) 83 Complete substation automation system for 220/132/33 kV substations including hardware (along with transducers)& software for present Bays and software for future bay along with associated equipment for the bays as defined in the technical specification, section sub-station automation system) as per technical specification. The scope for present and future is as under:- 220kV System: Present Bays:Future Bays Line bays=4 Line bays=2 T/F bays =4 T/F bays =2 Bus coupler =1Bus coupler =0132kV System: Present Bays:Future Bays Line bays=8 Line bays=4 T/F I/C bays =2 T/F I/C bays =1 Bus coupler Bay =1Bus coupler =033kV System: Present Bays: Future Bays Line bays=16Line bays=8 T/F I/C bays =4T/FI/Cbays =2 Bus Sectionliser bay =2Bus Sectionliser bay =1 Capacitor bay =2 & Capacitor bay =1 & Station T/F bay=0 Station T/F bay=2 84 Testing of IEM System at NABL accredited lab 85 BOM FOR SAMAST COMPLIANT IEM ( ON SEPARATE CUBICLE) FOR 33 KV I/Ci. 3P4W Interface Energy Meters (ABT type) 0.2s Class 1A with TTB & BCS No. 8 (02 no. for each 33 KV Incomer) Note- 4Cx4Sq mm armored and 3Cx2.5 Sq mm un-armored copper control cables shall be used for integration of IEMs. 86 ii. Wired Indoor Meters Panel suitable for 8 meters 87 iii.16 P Industrial Grade un-managed Network switch 88 iv. Data concentrator unit (DCU)/ communication Gateway (IG) with dual SIM Modem along with enclosure and accessories 89 v. Cat-6 cable-unshielded 90 vi. PVC conduit Pipe - 3/4 with accessories for Cat-6 cable lot Lot (In line with cat-6 cable) 91 vii.Armored Fibre Optic Cable (2 pair) 92 viii. HDPE conduit - 40/33 with accessorieslot Lot (In line with armored cable for CT/PT)Note- 4Cx4Sq mm armored and 3Cx2.5 Sq mm un-armored copper control cables shall be used for integration of IEMs. 93 Computer system (SFF) with Intel Core i5, 9th generation processor, 8GB RAM, 1 TB HDD, 19.5 Display with UPS. 94 Mono chrome Multi-functional Printer,A-4,25 PPM,Wi-Fi 95 Anti Fire Wall 96 Bolted type 220kV Single suspension string assembly with Silicone Rubber Polymer Composite Insulators (E&M strength 90 kN) with all hardware accessories including ball & socket connections and suspension clamp sets suitable for single Tarantula conductor. 97 Bolted type 220kV Single suspension string assembly with Silicone Rubber Polymer Composite Insulators (E&M strength 90 kN) with all hardware accessories including ball & socket connections and suspension clamp sets suitable for Twin Tarantula conductor. 98 Bolted type 132 kV single tension string assembly with Silicone Rubber Polymer Composite Insulators (E&M strength 90 kN) with all hardware accessories including ball & socket connection and tension clamp set suitable for twin Tarantula (string). 99 Bolted type 132 kV single suspension string assembly with Silicone Rubber Polymer Composite Insulators (E&M strength 90 kN) with all hardware accessories including ball & socket connection and suspension clamp set suitable for twin Tarantula (string). 100 Bolted type 132 Single suspension string assembly with Silicone Rubber Polymer Composite Insulators (E&M strength 90 kN) with all hardware accessories including ball & socket connections and suspension clamp sets suitable for single Tarantula conductor. 101 Bolted type 33 kV single tension string assembly with Silicone Rubber Polymer Composite Insulators (E&M strength 90 kN) with all hardware accessories including ball & socket connection and tension clamp set suitable for twin Tarantula (string). 102 Bolted type 33 kV Single suspension string assembly with Silicone Rubber Polymer Composite Insulators (E&M strength 90 kN) with all hardware accessories including ball & socket connections and suspension clamp sets suitable for Twin Tarantula conductor. 103 Boltless C- Type Wedge connectors matching with conductor size. 104 Copper lugs glands, PVC ferrules for control cabling. 105 Fiber cleats, Aluminium clamps, bolts, nuts, washers etc for fixing control cables in trenches 106 Galvanised iron perforated tray with side coupler plate bolts, nuts, washers and clamps etc. of size 150x25x2 mm, 100x25x2 mm and 75x25x2 mm and G.I conduits of 50/100mm diameter from equipment to main trench as per Section-7 for Switchyard erection. 107 2.5” dia HDD/PVC pipe for 4Cx4mm2 control cable from CT, VT to metering system as per Section-5, Chapter-5. 108 AAC Tarantula Conductor 109 7/3.15 GS Earth wire 110 Spacers for Twin Tarantula conductor 111 U-bolt 20mm dia 112 ‘Lattice type steel structure for 220 kV/132kV/33kV GIS Substation, IMT, Phase III,HSIIDC Rohtak. Supply of material, preparation of fabrication drawing, galvanizing and delivery of lattice type steel structure for tower and beams for 220/132/33 kV switchyard fabricated from steel conforming to IS: 2062 including nuts-bolts gusset plates foundation bolts and other accessories as per drawings supplied by the owner.Main Substation tower and beamTower type AT-1 113 Tower type AT-3 114 Beam type AB-1 115 Tower type BT-1 116 Tower type BT-3 117 Beam Type BB-1 118 Beam type CT-4 119 Beam type CT-5 120 Beam type DD-1 121 Equipment Structure220 kV NCT drawing No. HTD/ST-150 122 220 kV CVT drawing No. HTD/ST-147 123 132kV CVT drawing No. HHW/ST-67 124 220 kV surge arrestor drawing No.HTD/ST – 93R 125 132kV Surge Arrestor drawing No. HTD/ST-63R 126 33 kV NCT drawing No. HTD/ST-88 R 127 33 kV Surge Arrestor drawing No. HW/ST- 89 128 33kV structure for L&E HTD/ST-110 129 Cable support structure (To be designed by the bidder for XLPE cables) for: 220KV including spare cables 130 132KV 131 33kV 132 LILO of 220kV S/C Kabulpur - Rohtak line at IMT,RohtakPLC terminals (No.) 133 PLC terminal with Prot.coupler (No.) 134 Wave trap 1250A 135 LTU (P/P) (Set.) 136 48V Battery & Battery Charger 300AH 137 HFcable (kms) 138 220kV D/C Kalanaur-IMT Phase-III HSIIDC Rohtak linePLC terminals (No.) 139 PLC terminal with Prot.coupler (No.) 140 Wave trap 141 LTU (P/P) (Set.) 142 HFcable (kms) 143 Equipments for maintenancePortable circuit breaker operation analyzer. 144 Digital Micro-Ohm meter for contact resistance measurement Ranges (0-100 ohm)(0-1 milliohm)(0-10 milliohm). 145 Dew Point meter 146 Portable partial discharge monitoring system for GIS. 147 Digital Earth resistance meter. 148 5 kV Automated insulation resistance tester. 149 Earth stick with lead suitable for use in 220/33kV Switchyard 150 SF-6 Gas filling and evacuating plant 151 SF-6 Gas leak detector (Portable) 152 Tools for gas handling 153 LT DC Leakage detector from control cabinets and LT cables 154 Mandatory Spares for 220KV GISGeneralComplete GIS modules, along with enclosure, all active parts such as conductor, conductor joints, shields, end covers etc. for each type of? Bus Bar Sections (including Bus Bar Interconnection Modules)? Bus Ducts Sections (including Compensators/expansion joints/bellows)? Bends? SF6/Air Bushing.? Oil/SF6 Bushing? Cable Termination kit 155 SF6 gas Pressure Relief Device assembly of each type 156 SF6 Pressure gauge cum switch /Density monitors and pressure switch as applicable, of each type 157 Coupling device for pressure gauge cum switch for connecting Gas handling plant of each type 158 Rubber Gaskets, “O” Rings and Seals for SF6 gas for GIS enclosures of each type 159 Molecular filter for SF6 gas with filter bags (10 % of total weight) 160 Control Valves for SF6 gas of each type 161 SF6 gas (20 % of total gas quantity) 162 Pipe length (Copper or Steel as applicable) for SF6 Circuit of each type (if applicable) 163 Locking device to keep the Dis-connectors (Isolators) and Earthing/Fast Earthing switches in close or open position in case of removal of the driving Mechanism 164 UHF PD Sensors of each type along with BNC Connector 165 Support Insulators (gas through) of each type (complete with metal ring etc.) 166 Gas Barriers of each type (complete with metal ring etc.) 167 SF6 to air bushing of each type complete in all respect 168 SF6 CIRCUIT BREAKERComplete Circuit Breaker (Three Phase) with interrupter, main circuit, enclosure and Marshalling Box with operating mechanism to enable one to one replacement of applicable type of CB by spare. (if applicable) 169 Fixed, moving and arcing contacts including insulating nozzles of each type (for Main Chamber & PIR Chamber as applicable) 170 Trip coil assembly with resistor as applicable 171 Closing coil assembly with resistor as applicable 172 Relays, Power contactors, push buttons, timers & MCBs etc. of each type 173 Auxiliary switch assembly of each type 174 Operation Counter 175 Wind scope / Observing window of each type 176 For Hydraulic Operated Mechanism, if applicableHydraulic operating mechanism with drive motor of each type 177 Ferrules, joints and couplings of each type 178 Hydraulic filter of each type 179 Hose pipe of each type 180 N2 Accumulator of each type 181 Valves of each type 182 Pipe length (copper & steel) of each size & type 183 Pressure switches of each type 184 Pressure gauge with coupling device of each type 185 Hydraulic oil (20% of total Oil quantity) 186 Pressure Relief Device of each type 187 For Spring Operated Mechanism, if applicableComplete Spring Operating Mechanism including charging mechanism etc. of each type 188 Spring Charging Motor 189 For Hydraulic-Spring Operated Mechanism, if applicableComplete Hydraulic-Spring Operating Mechanism including charging mechanism etc. of each type 190 Spring Charging Motor 191 Pressure switches of each type 192 Pressure gauge with coupling device of each type 193 Disconnector Switches/Earthing SwitchesComplete set of 3-phase dis-connector of each type including main circuit, enclosure, driving mechanism and support Insulator etc. to enable complete one to one replacement of all applicable type of Isolator by spare 194 Complete set of 3-phase Maintenance Earthing switch of each type, including main circuit, enclosure, driving mechanism and support Insulator etc. to enable complete one to one replacement of all applicable type of Earth Switch by spare 195 Complete set of 3-phase Fast Earthing switch of each type, including main circuit, enclosure, driving mechanism and support Insulator etc. to enable complete one to one replacement of all applicable type of Earth Switch by spare (if applicable) 196 Copper contact fingers & corona shield for dis-connector male & female contact–for one complete (3-phase) dis-connector of each type 197 Copper contact fingers & corona shield for Maintenance Earthing switch male & female contacts, for one complete (3- phase) earthing switch of each type 198 Copper contact fingers & corona shield for Fast Earthing switch male & female contacts, for one complete (3-phase) earthing switch of each type (if applicable) 199 Open/Close contactor assembly, timers, key interlock, interlocking coils, relays, push buttons, indicating lamps, Power contactors, resistors, fuses, MCBs & drive controlcards etc. one of each type for one complete MOM boxFor Disconnector 200 For Maintenance Earth switch 201 For Fast Earthing Switch (if applicable) 202 Limit switches and Aux. Switches for one complete MOM BoxFor Disconnector 203 For Maintenance earth switch 204 For Fast Earthing Switch (if applicable) 205 Drive Mechanism of each typei. For Disconnector 206 ii. For Maintenance earth switch 207 iii. For Fast Earthing Switch (if applicable) 208 Motor for Drive Mechanism of each typei. For Disconnector 209 ii. For Maintenance earth switch 210 iii. For Fast Earthing Switch (if applicable) 211 CURRENT TRANSFORMERComplete CT of each type and rating as supplied with enclosure and primary conductors to enable one to one replacement of all applicable type/rating of CT by spare 212 Voltage TransformerComplete PT of each type with enclosure to enable one to one replacement of all applicable type/rating of VT by spare (if applicable) 213 SURGE ARRESTORComplete Gas insulated Surge arrester of each type and ratings with enclosure and insulator (if applicable) 214 Surge counter/ monitor of each type (if applicable) 215 Local Control Cubicle (LCC)Aux. relays, Contactors, Push Buttons, Switches, Lamps, Annunciation Windows, MCB, Fuses, Timers, Terminal Blocks etc. of each type & rating 216 Mandatory Spares for 132KV GISGeneralComplete GIS modules, along with enclosure, all active parts such as conductor, conductor joints, shields, end covers etc. for each type of? Bus Bar Sections (including Bus Bar Interconnection Modules)? Bus Ducts Sections (including Compensators/expansion joints/bellows)? Bends? SF6/Air Bushing.? Oil/SF6 Bushing? Cable Termination kit 217 SF6 gas Pressure Relief Device assembly of each type 218 SF6 Pressure gauge cum switch /Density monitors and pressure switch as applicable, of each type 219 Coupling device for pressure gauge cum switch for connecting Gas handling plant of each type 220 Rubber Gaskets, “O” Rings and Seals for SF6 gas for GIS enclosures of each type 221 Molecular filter for SF6 gas with filter bags (10 % of total weight) 222 Control Valves for SF6 gas of each type 223 SF6 gas (20 % of total gas quantity) 224 Pipe length (Copper or Steel as applicable) for SF6 Circuit of each type (if applicable) 225 Locking device to keep the Dis-connectors (Isolators) and Earthing/Fast Earthing switches in close or open position in case of removal of the driving Mechanism 226 UHF PD Sensors of each type along with BNC Connector 227 Support Insulators (gas through) of each type (complete with metal ring etc.) 228 Gas Barriers of each type (complete with metal ring etc.) 229 SF6 to air bushing of each type complete in all respect 230 SF6 CIRCUIT BREAKERComplete Circuit Breaker (Three Phase) with interrupter, main circuit, enclosure and Marshalling Box with operating mechanism to enable one to one replacement of applicable type of CB by spare. (if applicable) 231 Fixed, moving and arcing contacts including insulating nozzles of each type (for Main Chamber & PIR Chamber as applicable) 232 Trip coil assembly with resistor as applicable 233 Closing coil assembly with resistor as applicable 234 Relays, Power contactors, push buttons, timers & MCBs etc. of each type 235 Auxiliary switch assembly of each type 236 Operation Counter 237 Wind scope / Observing window of each type 238 For Hydraulic Operated Mechanism, if applicableHydraulic operating mechanism with drive motor of each type 239 Ferrules, joints and couplings of each type 240 Hydraulic filter of each type 241 Hose pipe of each type 242 N2 Accumulator of each type 243 Valves of each type 244 Pipe length (copper & steel) of each size & type 245 Pressure switches of each type 246 Pressure gauge with coupling device of each type 247 Hydraulic oil (20% of total Oil quantity) 248 Pressure Relief Device of each type 249 For Spring Operated Mechanism, if applicableComplete Spring Operating Mechanism including charging mechanism etc. of each type 250 Spring Charging Motor 251 For Hydraulic-Spring Operated Mechanism, if applicableComplete Hydraulic-Spring Operating Mechanism including charging mechanism etc. of each type 252 Spring Charging Motor 253 Pressure switches of each type 254 Pressure gauge with coupling device of each type 255 Disconnector Switches/Earthing SwitchesComplete set of 3-phase dis-connector of each type including main circuit, enclosure, driving mechanism and support Insulator etc. to enable complete one to one replacement of all applicable type of Isolator by spare 256 Complete set of 3-phase Maintenance Earthing switch of each type, including main circuit, enclosure, driving mechanism and support Insulator etc. to enable complete one to one replacement of all applicable type of Earth Switch by spare 257 Complete set of 3-phase Fast Earthing switch of each type, including main circuit, enclosure, driving mechanism and support Insulator etc. to enable complete one to one replacement of all applicable type of Earth Switch by spare (if applicable) 258 Copper contact fingers & corona shield for dis-connector male & female contact–for one complete (3-phase) dis-connector of each type 259 Copper contact fingers & corona shield for Maintenance Earthing switch male & female contacts, for one complete (3- phase) earthing switch of each type 260 Copper contact fingers & corona shield for Fast Earthing switch male & female contacts, for one complete (3-phase) earthing switch of each type (if applicable) 261 Open/Close contactor assembly, timers, key interlock, interlocking coils, relays, push buttons, indicating lamps, Power contactors, resistors, fuses, MCBs & drive controlcards etc. one of each type for one complete MOM boxFor Disconnector 262 For Maintenance Earth switch 263 For Fast Earthing Switch (if applicable) 264 Limit switches and Aux. Switches for one complete MOM BoxFor Disconnector 265 For Maintenance earth switch 266 For Fast Earthing Switch (if applicable) 267 Drive Mechanism of each typei. For Disconnector 268 ii. For Maintenance earth switch 269 iii. For Fast Earthing Switch (if applicable) 270 Motor for Drive Mechanism of each typei. For Disconnector 271 ii. For Maintenance earth switch 272 iii. For Fast Earthing Switch (if applicable) 273 CURRENT TRANSFORMERComplete CT of each type and rating as supplied with enclosure and primary conductors to enable one to one replacement of all applicable type/rating of CT by spare 274 Voltage TransformerComplete PT of each type with enclosure to enable one to one replacement of all applicable type/rating of VT by spare (if applicable) 275 SURGE ARRESTORComplete Gas insulated Surge arrester of each type and ratings with enclosure and insulator (if applicable) 276 Surge counter/ monitor of each type (if applicable) 277 Local Control Cubicle (LCC)Aux. relays, Contactors, Push Buttons, Switches, Lamps, Annunciation Windows, MCB, Fuses, Timers, Terminal Blocks etc. of each type & rating 278 MANDATORY SPARES (33kV GIS)Line voltage transformer (3 nos.) 279 Bus voltage transformer (3 nos.) 280 Current transformers suitable for incomer panel (3 nos.) 281 Current transformers suitable for transformer panel (3 nos.) 282 Current transformers suitable for bus coupler panel (3 nos.) 283 Trip Coil 284 Closing Coil 285 CB Spring charging motor 286 Auxiliary switch (2 no each type) 287 Disconnector motor for isolator 288 Disconnector motor for earth switch 289 Gas density switch 290 Bursting disc / pressure relief plate complete 291 Capacitive voltage indicator (6 nos) 292 Civil PortionEARTH WORK IN FILLINGEarth filling with good earth (as per satisfaction ofEngineer incharge), laying in layers (as per specification), dressing, including carriage, irrespective of lead, loading, unloading, watering and compaction in layers with roller including compensation of earth complete in all respect. 293 FOUNDATIONSDesign engineering, supply of labour, T&P, material and construction of RCC footings & pedestals etc. for steel gantry and equipment structures complete in all respects as per technical specificationsincluding cost of excavation, concreting, cement, reinforcement steel, form work, grouting, holding down bolts, backfilling etc.and other items not mentioned herein but required for the completion of work.GANTRY TOWERS AT-1 294 AT-3 295 BT-1 296 BT-3 297 CT-4 298 CT-5 299 EQUIPMENT220kV LA 300 220kV CVT 301 220kV NCT 302 132kV LA 303 132kV CVT 304 33kV LA 305 33kV NCT 306 CABLE SUPPORT STRUCTURE FOUNDATIONDesign, Engineering, Supply of labour, material and Construction of cable support structure foundations including all associated works, RCC, PCC, reinforcement steel, misc. structural steel and other items not mentioned herein but required for the completion of work as per technical specifications. 220kV cable support structure 307 132kV cable support structure 308 33kV cable support structure 309 ROADSSupply of labour, material and construction of cement concrete roads and walkways/shoulders from NH/SH/etc. to Switch yard/Switch house building as per GELO/CLO as per sectional detail drawing no. HCD/SK-181 R1 and technical specification.6.0m wide road (Near main gate of substation) 310 5.0m wide road within substation land 311 3.66m wide road within substation land 312 CAPACITOR BANK FOUNDATIONSDesign, Engg. & supply of labour, material & construction of foundations for capacitor bank with capacitor unit (with allied equipments) & series Reactor etc. including chain link fencing 1.8M height around cap. bank complete in all respect including any other items not specifically mentioned herein but required for completion of job as per technical specification.21.744 MVAR 33 kV capacitor bank 313 ROAD CULVERTDesign, Engineering and const. of Pipe culvert(s) at suitable locations under the approach road (from main PWD/ HUDA/Municipal/Village road to the sub-station entry point) including, cost of labour, material complete in all respects as per I.R.C. Standards. 314 TRANSFORMER FOUNDATIONDesign, Engg., supply of labour, material and construction of T/F foundation including radiator foundations etc. complete transformer foundations including all associated works, RCC, PCC, Reinforcement steel, misc. structural steel and other items not mentioned herein but required for the completion of work as per technical specifications. In case additional foundation is/are required as per approved equipment drawing, the same shall be constructed by the successful bidder without any extra cost to HVPNL. Such drawing(s) shall, however, be got approved from HVPNL.160MVA,220/132kV T/F foundation including associated foundations, fire fighting system etc. NIFPES system complete in all respect. 315 100MVA,220/33kV T/F foundation including associated foundations, fire fighting system etc. NIFPES system complete in all respect. 316 Design, Engg., supply of labour, T&P and material including RCC, PCC, Reinforcement steel, misc. structural steel & other item(s) not mentioned herein but required for the completion of work as per tech. specs. for construction of below mentioned foundations. 200KVA 33/0.4kv Station T/F 317 100kVA DG Set 318 OUTDOOR CABLE TRENCHESSupply of labour, material such as cement, reinforcement steel, GI angles, flats, PCC & brick pillars below cable trenches for construction of Out-Door Cable Trenches (ODCT) of required depth/ type with pre-cast RCC covers including associated works like Cable Trench Culverts crossings for roads and sumpit-cum-pump chamber with 2HP motor of reputed make, starter, volt meter, amp-meter etc. as per approved Trench layout plan, HVPNL drgs. & tech. specs. complete in all respect. 319 SITE SURFACINGProviding, supplying & laying 100mm thick in two layers of 50mm each of 20mm nominal size uncrushed/crushed/ broken stone pebbles gravel fill including dressing, rolling & compacting complete in all respects as per specs. & instructions of engineer incharge. 320 Providing, supplying & laying 100mm thick PCC (1:4:8) using 20mm nominal coarse aggregates and supplying & spreading 100mm thick layer of 40mm nominal size uncrushed/ crushed/broken stone pebbles over the PCC including construction of toe wall (exposed wall plastered with cement mortar 1:5) to hold 40mm single size uncrushed/ crushed /broken stone pebbles wherever required in the bays covered under the present scope as detailed in the GELO & instructions of engineer incharge. 321 BOUNDARY WALLSupply of labour, T&P, material & construction of front, side & U/C boundary walls (brickwork below DPC level) as per GELO/CLO, tech. spec. & HVPNL drgs including excavation, PCC, back filling etc. complete in all respects. 322 Supply of labour, material and construction of front, C & U/C boundary walls above DPC including main gate foundationsas per GELO/CLO, technical specifications. & HVPNL drg. HCD/TS-1176 R3 including DPC complete in all respect.i) 6 ft. high U/C B/wall with barbed wire on angles at top including construction of entrance gate(w/o wicket gate) for yard. 323 ii) 4½ ft. high front wall including providing grill at top of wall & construction of main entrance gate (with wicket gate). 324 iii) 4½ ft. side wall with GI barbed wire 325 CONTROL ROOMSupply of labour, material, T&P and construction of control room building complete in all respect as per tech. specs. & approved drgs. attached with the bid/tendered drawings including exterior weather proof paint, interior emulsion, all internal services like water supply including supply & providing of 5000ltr. capacity double layer Sintex/Diplast PVC tank, Sewerage system, electrification including wiring, modular switches, maximum 20W 4ft. long LED tubes with fittings minimum 1960 lumens, ceiling/exhaust fans, Finishing, Plinth protection, closed drain around the building (i.e RCC Pipe), Indoor trenches, Soakage pit near the switch house building, connection of sewerage system to Soakage pit/Sewerage system of local authorities (as applicable), connection to main water supply system of local authority, bore (Tubewell) (as applicable) etc. & any other item not mentioned herein but required for completion of works. 326 GIS HALL/BUILDINGDesign, Engineering including architectural & structural, supply of labour, material and construction of GIS building with ventilation system including crane hoisting system (EOT), equipment foundations as detailed in the bill of quantities under Annexure-1 ofSection-I of bid/contract documents, electrification including wiring, receptacle, modular switches,maximum 20W 4ft. long LED tubes with fittings minimum 1960 lumens , bulkhead LED lights including fixtures, ceiling/exhaust fans, stair case etc. interior & exterior acrylic emulsion, paint, RCC paving/plinth protection starting from the building up to 1.5 m clear distance for the full length width of the building, closed drain around the building (i.e RCC Pipe) etc. complete in all respect for GIS hall/building and any other item not mentioned herein but required for completion of job as per specifications. 220 kV GIS Building 327 132 KV GIS Building 328 33 kV GIS Building 329 U/C FENCING & GATES Providing & fixing chain link fencing including foundations, GI angle iron posts and gate(s) complete as per electrical layout & tech. spec. & as per drawing attached. 330 PCC PAVEMENTConstruction of PCC pavement in front, rear or side (as per site requirement of the switch house building) as per drawing no. HCD/SK-172 & technical specifications. 331 DRAINAGE-CUM-RAIN HARVESTING SYSTEMThe successful bidder shall evolve design & drawing for drains, manholes with RCC covers andsettlement tankincluding preparation of drainage layout drawing for disposal of rain water from building’s roof top & switch yard (s/stn.) area into respective bore well(s) in such a way that there shall be no ponding of water on the roof and switch yard (s/stn.). The layout so developed shall be got approved from the employer. The location of sump-pit-cum-pump chamber shall preferably be locatedon corner(s) of the s/stn. and shall be got decided from the concerned Engineer in-charge on the basis of surroundings of the substation(s). The successful bidder will also supply labour and material for construction of sump-pit-cum-pump chamber as per HVPNL drgs. & provide one no. non clog pump(s) of 5HP of reputed make capacity with main switch, starter, volt meter, Amp. Mtr. etc. (for each sump pit) for disposal of excess water to outfall point. Any other item(s) not mentioned herein but is/are required for completion of works shall be done by the successful bidder without any extra cost to the employer.Drain Section-1 332 Drain Section-2 333 Drain Section-3 334 Road Crossing 335 Trench Crossing 336 Sump Pit Cum Pump Chamber 337 RCC ANTIFIRE WALLConstruction of RCC anti fire wall of suitable height between T/F as per HVPNL drawing and all associated works including supply of labour, material, cement, reinforcement steel, steel form work etc. as per technical specification.
|