Checking The Volume Of 2 Split-Type Air Conditioners, Cleaning The Filters, Checking And Adjusting The Electronic-Automatic Part, Checking The Engine-Compressor, General Washing Of The System (Take Into Account The Number Of Times), Services To Be Provided In Connection With The Main Electrical Distributor (External Inspection Of The Sections Of The Main Distribution Board, Switching Off Of The Sections, Removal Of The Back Panel, Detection Of Malfunctions And Heating Of Contacts, Removal Of Internal Dust And Cleaning, External Inspection Of The Automatic System, Shutdown, Detection Of Malfunctions And Heating Of Contacts Making, Removing And Cleaning The Internal Dust, Performing Thermal Diagnostics (Switches, Contactors, Chokes, Capacitors) (Number Of Times Be Considered As), Services To Be Provided Related To The Ups In The Main Electrical Distributor (Testing Of Automation Related To Ups, Inspection Of Internal Elements Of The Cabinet, General Inspection And Testing Of Ups. (To Be Considered As Number Of Times), Services To Be Provided For 2 Stabilizers (External Inspection Of Stabilizers, One-By-One Shutdown, Troubleshooting And Heating Of Contacts, Internal Dust Removal And Cleaning, Recommendations For Troubleshooting Using Additional Equipment If Necessary) (As Per Number Of Times Be Considered), 3 Stabilizer Services For Elevator (External Inspection Of Stabilizers, Recommendations For Troubleshooting Using Additional Equipment If Necessary) (Considered As Number Of Times Get It), Cleaning The Combustion Chamber And Checking The Combustion System (Nozzle) Of The Alarko Brand Ask-2 1500 Boiler In The Boiler House, Checking Its General Functionality, Washing And Cleaning The Boiler (Pipes, Drains), Adjusting And Checking The Manometers, Checking The Water Circulation In The Boiler System, The Automatic Control Panel Of The Boiler Checking And Tuning, Fire System (Engine, Blowing System, Gas Line, Etc.) Etc.) Checking, Debugging. (Count As Number Of Times), Cleaning The Combustion Chamber And Checking The Combustion System (Nozzle) Of The Yetsan (1500000 Kcal/H) Boiler In The Boiler House, Checking The General Functionality, Managing The Boiler Checking And Tuning Of The Automatic Control Panel, Gas Line And Etc.) Checking, Boiler Chimney Cleaning (To Be Taken Into Account As Number Of Times), Servicing Of The Moving Part Of Villo Brand Typ Ipl 32/95-0, 55/2 Model Motors And Pumps (To Be Considered As Number Of Times), Servicing Of The Moving Part Of Villo Brand Typ Ipl 32/105-0, 75/2 Model Motor And Pumps (To Be Considered As Number Of Times), Servicing Of The Moving Part Of Villo Brand Typ Ipl 65/130-4/2 Model Motor And Pumps (Regardless Of The Number Of Times), Servicing Of The Moving Part Of Villo Brand Typ Ipl 40/130-22/2 Model Motor And Pumps (Regardless Of The Number Of Times), Servicing Of The Moving Part Of Villo Brand Typ Ipl 32/135-1, 1/2 Model Motor And Pumps (Regardless Of The Number Of Times), Servicing Of Villo Brand Typ Ipl 80/140, 1/2 Model Motor And Moving Part Of Pumps (Regardless Of The Number Of Times), Adjusting The Circulation In The Hot And Cold Water System In The Administrative Building And Servicing The Air Pressure Expansion Tank That Supplies Water To The Upper Floors With Normal Pressure, Checking The Manhole And Checking The Moving Parts Of The Water Pressure Hydrophores And Adjusting The General Water System (Regardless Of The Number Of Times)
|