Tender For Mehroni Nagar Panchayat Reorganization Water Supply Scheme, Survey Soil Investigation Design Supply Of All Materials Labour Tandp Etc Required For Construction Erection Completion Testing And Commissioning Of Water Supply Works Such As Intake Well Wtp Rcc Oht Zps Cwr Cum Pumping Station Rising Main, MEHRONI NAGAR PANCHAYAT REORGANIZATION WATER SUPPLY SCHEME UNDER -AMRUT 2.0, DISTT. LALITPUR Sl. No. Item Description 1 INTAKE WELL 8.0 M DIA 2 Survey, Soil investigation, Design, Supply of all materials, labour, T&P etc. required for construction,of Intake- well - cum - pump house of 8.0 m. internal dia. The intake well upto floor level shallbe firmly based on suitable foundation made with open technologyand Annular raft foundation, including construction of 1.0 m. wide R.C.C. balcony at plinth level, construction of Pump House made of brick masonry, duly embraced within R.C.C. column, and fitting of doors and windows, making opening arrangement at floor level of pump house (8.00 m. dia and 4 m. height) including steel cage hinged with locking arrangement, duly supported on IS MB 300. plateform for transformer ,meter room and HT pannel room,LT pannelVentilator arrangement along with fixing of 250 mm. dia. DID/F pipesand Sluice Valves etc. as per site requirement or as per the design. The work also includes 20 mm. dia. G.I.Pipe (medium) railing in three rows on both sides of stair and balcony and fixing of 0.5m. wide S.S. ladder made of 50 x 50x 6mm. angle S.S. ladder from floor of pump house to floor of intake well, duly supported on R.C.C.landing at suitable interval. The ladder shall run spirally inside the intake well and each landing shall be supported on R.C.C. M.S. channelpost, spaced not more than 1.5 m. interval including Construction of R.C.C. foundation block as required. The floor of pump house & balcony shall be of Kota Stone & on foot bridge floor shall be plain chequered tiles etc. complete. Frames for doors shall be made of 50x50x6 mm. M.S. angle iron and ionized and shall be partly panelled and glazed, made of suitable steel sections, conforming to relevant BIS. The work also includes painting of all concrete surfaces with three coats of approved cement paint and painting of pipes, doors, windows with anticorrosive paints including design of intake well, foot bridge, pump house etc. considering seismic and other forces as per relevant BIS requirements.erection, completion, testing & commissioning of Intake well. complete as per the direction of Engineer In charge. 3 Survey, Soil investigation, Design, Supply of all materials, labour, T&P etc. required for construction, 4.0 mts. wide R.C.C Foot bridge from Intake well to bank of river for length of 90 mts. IncludingThe work also includes 20 mm. dia. G.I.Pipe (medium) railing in three rows on both sides of stair and balcony and fixing of 0.5m. wide S.S. ladder made of 50 x 50x 6mm. angle. 4 CONSTRUCTION OF 5.5 MLD CAPACITY WATER TREATMENT PLANT 5 Survey, Soil investigation,(including topographical survey, geotechnical investigation and other Surveys as required) for Design and Drawing, Supply of all materials, labour, T&P etc. required for construction,of specified capacity (5.5 MLD) of WTP based on 20 Hrs. operation (5.5 MLD + 25%) extra over loading capacity includinginlet chamber, aeration fountain / cascade, inlet channels including mechanical/manual fine/coarse screens, flash mixer, mixing channel with Parshall flume and flow measuring arrangement, clariflocculator with conventional, filter house and filter plant including back wash tank and back wash pumps with 100% standby, chemical house, coagulant feed tank with feed mechanism, poly aluminium chloride (PAC) or other coagulant tank of specified capacity and nos. with mixing and dosing arrangement complete, vacuum feed gas chlorinator with 100% standby, sludge handling unit and recycling of collected water from sludge etc. complete,All WTP scada Opratedexternal and internal electrification, laboratory building with all specified lab equipment, admin building, Quarter (One no.) Scada room and sub station building, sanitary block with necessary water supply and drainage arrangement, campus roads, landscaping and other campus development works, rain water harvesting, etc. all required works complete as per the direction of Engineer-in-Charge.The WTP shall be fully automatic based on PLC/SCADA with real time remote monitoring system and online contineuous effluent monitoring system. 6 All above units complete as per design and drawings approved by the engineering -in-charge. 7 Survey, Soil investigation,(including topographical survey, geotechnical investigation and other Surveys as required) for , Design,Drawing includingSupply of all materials, labour, T&P etc. required for construction, Construction of Panel Room (4m x 4m x 4 m) and Meter Room(3m x 3m x 4 m) usingwithbricks (RCC Frame Structure) as per type design 8 Provide all materials, labour T&P etc. and MCM Room Survey, Soil investigation,(including topographical survey, geotechnical investigation and other Surveys as required) for , Design,Drawing includingSupply of all materials, labour, T&P etc. required for construction,of (RCC Frame Structure) at WTP MCM-(SIZE 10.0MX5.0MX4.0M),and Panel Room (5m x 4m x 4 m) 9 RCC CWR;Detailed Survey, Design and Drawing, supply of all material, labour, T&P etc. required for construction of Ractangular, R.C.C Clear Water Reservoir cum pump house including various works like 1 m wide stair case with stainless steel hand railing to go inside reservoir, sump below the pump house area, stainless steel railing over the R.C.C slab of reservoir, Granular texture finish on exterior surface of pump house, gantry beam, food grade epoxy coating of FOSROC / Ciba-Geigy or reputated brand on inside surface area of water container after testing for water tightness, kota ston floring,bypass arangment ,and soil testing for Bearing capacity of capacity mentioned as under:Note : The bid prices of Clear Water Reservoir / Pumping Stations are to be submitted considering the depth of excavation may extend up to 6 m BGL. Design and Drawing approved by competent authority and Design vetted by Reputed Govt. Engineering College including Soil testing 10 450 KL MCWR (Departmental Rate) Size - L- 10M, B-10M, H-5M 11 Supply of all the materials, labour T&P and construction of a R.C.C. Over head tank above ground level with main components, based on IS-3370 or liquid storage concrete in over head tank and foundation concrete as per specification in I.S. 2911. 12 Construction of Over Head Tank: Detailed Survey, Design and Drawing,Soil Testing and Construction of RCC Overhead Tank ( RCC mix grade as per latest IS Specification.) on Raft and pile cum raft foundation (Keeping the minimum foundation depth to be 2.5 m below natural ground level) at the site of work as per site condition of different of capacitymentionedand staging capacity including Excavation of foundation in all type of soil or rockas required with continuous bailing out of water, including cutting of rock with special T&P, making temporary approach road ,Ventilator at top dome,and Water level indicator, Lightening conductor, D.I. D/F Verticle pipes (Inlet Pipe, Outlet Pipe, Overflow Pipe & Washout Pipe), duck foot bend, puddle collers and bell mouths,Reputed makeSluice valve scada compitable on inlet, outlet & washout pipe and Valve Chamber, Bye-pass arrangement of OHT, Flooring, Apran & Drain (100 mm thick PCC of 1:2:4 & 100 mm thick RCC of 1:1.5:3), Floor shall be 30 cm above the finished ground level of Campus, Two coat apex painting over one coat primer of approved colour after finishing of RCC surface with grinder, repair of pin holes, unevenness., Railings-Mild Steelrailing 100 cm hight minimum weight65 Kg per Meter consist of minimum 6 mm thick flat and 12mm square bar top of C channel around stair case (both sides), balcony & top dome periphery, S.S ladder from opening of top dome to bottom dome inside tank, Stair case (Seperate two column basedRCC staircase and 1 m wide balcony with arrangement of M.S Gate with cage), Food grade epoxy coating of FOSROC / Cika-Geigy or reputated brand on inside surface area of water container after testing for water tightness and site development ( PLANTATION AND Placing The GRASS up to 100 SQM) all complete as per direction of Engineer in charge. Design and Drawing approved by competent authority and Design vetted by Reputed Govt. Engineering College. 13 950 Klwith 22 m staging (ZONE -2 ) 14 900 Klwith 24 m staging (ZONE -3) 15 Testing of bearing capacity of soil from a reorganized Govt. Engineering College or as directed by department. 16 Rehabilitation of Existing OHT 400KL/16M Zone-1, 17 Rehabilitation of Existing OHT 125KL/24M Kasiram Awas Yojna, 18 Excavation for pipe line trenches in soil mix / all type of rocks with moorum/shingles/kanker requiring use of special T&P ie. pick axe, sabbals etc. lift upto 1.50 m lead upto 50 m. stacking and spreading as directed, normal dewatering,preparing the bed,Filling watering ramming of excavated earth into pipe line trenches and disposal of surplus earth upto a distance of 10 KM from the centre of the pipe line trenches. 19 Soil Mixed with moorum/ Shingle Kankar 0 to 1.5 m depth 20 Excavation for pipe line in all type of rock by chaieselling0 to 1.5 m depth 21 Supply of ISI mark DI K-9 S&S pipes (push on joints) of following class and diameters inclusive of jointing material (Rubber gasket of EPDM Quality IS 12820 / 1989) conforming to IS 8329/2000 for its latest ammendment F.O.R. desination rates per meter (exclusive of GST) in Rs. every where in UP upto stores of consignees inclusive of third party inspection chacking and forwarding charges, transit insurance charges, road transportation charges, unloading & stacking the same etc. complete suitable for pipe with rubber gasket, coupling, coupler as per I.S. F.O.R. destination including all local cartage etc complete. and supply of all DI DF/DI DS specialslike Tees, all type bend and Distance pieces End Caprequired( For Distribution, Feedermain And Rising main Purpose ) 22 80 mm dia K-9 (Kasiram Awas Yojna) 23 150 mm dia K-9 (ZONE-1) 24 200 mm dia K-9 (ZONE-2 & 3) 25 400 mm DI K-9(Bhonrat dam to WTP) 26 DI K-7 Pipes 27 200mm (DI-k7) 28 250 mm (DI-k7) 29 300 mm (DI-k7) 30 350 mm (DI-k7) 31 Supply of High Density Polyethelene Pipes (HDPE (PN-6)/PE-100), conforming to IS 4984 / 14151 / 12786 / 13488 in coils/ standard lengths F.O.R. desination rates per meter (exclusive of GST) in Rs. every where in UP upto stores of consignees inclusive of third party inspection charges, packing and forwarding charges, transit insurance charges, road transportation chaloading & stacking the same etc. complete. including cost of 1 HDPE coupler per pipe length and all bend , reducer, tee and all type of spacial which are required in Electro fusion joint fitting inclusive of all taxes and duties, 3rd party inspection charges, packing and forwarding charges, transit insurance charges, road transportation charges etc. F.O.R. destination etc. complete .HDPE PN-6/PE-100 32 90 mm dia HDPE Pipe PN-6 33 110 mm dia HDPE Pipe PN-6 34 125 mm dia HDPE Pipe PN-6 35 140 mm dia HDPE Pipe PN-6 36 160 mm dia HDPE Pipe PN-6 37 Lowering, laying and jointing with SBR ruber gasketsD.I. K-7/ D.I. K-9 of various classes with DI / MS specials of following diameter in proper position, grade and alignment including conveyance of material to site of work. It also includes cost of jointing materials and rubber rings labour,hydraulic testing etc. complete. Cartage of following size of D.I. K-7 /K-9 pipes specials from local store to site for work . lowering them in already prepared trenches and laying in truealignment & jointing including sectional testing of laid pipeline , including supply of all material and T&P etcall complete upto the satisfaction of Engineer in Charge. 38 80 mm dia K-9 (Kasiram Awas Yojna) 39 150 mm dia K-9 (ZONE-1) 40 200 mm dia K-9 (ZONE-2 & 3) 41 200mm (DI-k7) 42 250 mm (DI-k7) 43 300 mm (DI-k7) 44 350 mm (DI-k7) 45 400 mm DI K-9(Bhonrat dam to WTP) 46 Lowering, laying and jointing of HDPE pipe in proper position using electrofusion specials including supply of all Electrofusion specials & hydraulic testing as per relevent IS Code complete with all accessories like Electrofusion machine, power arrangements, hydraulic testing arrangements, labours, material etc. complete Including Carting of following pipes, specials and fittings from site store to site of work, lowering them into trenches, laying true to alignment and gradient, laying and jointing with electro fusion fitting of pipe line including cutting of pipe for making up lengths as required for proper completion of work. HDPE PN-6/PE-100 47 90 mm dia HDPE Pipe PN-6 48 110 mm dia HDPE Pipe PN-6 49 125 mm dia HDPE Pipe PN-6 50 140 mm dia HDPE Pipe PN-6 51 160 mm dia HDPE Pipe PN-6 52 Double flanged Ductile Iron Sluice valves as per IS 14840 : 2000 Supply of following type of valves as per specifications F.O.R. desination rates per meter (exclusive of GST) in Rs. every where in UP upto stores of consignees inclusive of third party inspection charges, packing and forwarding charges, transit insurance charges, road transportation charges, including DI tail pieces with EPDM fully covered wedge and epoxy coating, internal and externalunloading & stacking the same etc. complete. Double flanged Ductile Iron Sluice valves as per IS 14840 : 2000 53 400 mm DI K-9(Bhonrat dam to WTP) 54 80 mm dia K-9 (Kasiram Awas Yojna) 55 150 mm dia K-9 (ZONE-1) 56 200 mm dia K-9 (ZONE-2&3) 57 100 mm 58 125 mm 59 150 mm 60 200 mm 61 300 mm 62 80 mm dia for Scour valve 63 Air valves as per IS 14845 : 2000 64 100 mm 65 50 mm dia K-9 (Kasiram Awas Yojna) 66 50mm Size air valve using in Raising Main for Zone -1 67 50 mm Size air valve usingin Raising Main for ZONE-2&3 68 50 mm for distribution 69 80 mm 70 Fire Hydrant as per IS Code 908 : 1975 71 80 mm 72 Carting, lowering, laying, aligning, fixing in position and installation of following valves in pipe line including all material, labour, testing and commissioning as per direction of Engineer-in- charge.Double flanged Ductile Iron Sluice valves as per IS 14840 : 2000 73 400 mm 74 80 mm dia K-9 (Kasiram Awas Yojna) 75 150 mm dia K-9 (ZONE-1) 76 200 mm dia K-9 (ZONE-2&3) 77 100 mm 78 125 mm 79 150 mm 80 200 mm 81 300 mm 82 100mm dia for Scour valve 83 Kinetic Double Air Valves 84 100 mm 85 85 mm dia Air Valve 86 50 mm 87 80 mm 88 Fire Hydrant as per IS Code 908 : 1975 89 80 mm 90 Dismantling (cutting by sharp eage machine tools) of following type of road surfaces for laying of pipe line and house connection work including sorting out of serviceable materials and disposal of unserviceable materials. 91 Bituminious Road 92 Cement Concrete Road 93 Interlocking Tiles Road 94 Brick on edge Road (BOE) 95 Re-instatement of following type of road surfaces after laying of pipe line and house connection work including supply of all materials, T&P etc. requuired for proper completion of the work as per direction of engineer-in-charge. The quantity of re-instatement has been increased by thirty percent in the view of additional damaged of dismantled road due to traffic / vehicle movement. 96 Bitumen roadTYPE AConstruction of bitumen road as per UPPWD specification including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-GSB G-1 (One coat) (90-40 mm) = 12.5 cmG -2 (one coat) (45-63 mm) = 7.5 cmG - 3 (one coat) (22.5 - 53 mm) = 7.5 cmBM (One coat)= 7.5 cmSDBC (One coat)= 2.5 cm 97 TYPE BConstruction of bitumen road as per UPPWD specification including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-Bitumen Road (SDBC + Tack coat)SDBC (One coat)= 2.5 cmTack coat with bituminous emulsion (MS)= 0.25 kg/sqm(30% consider for over dismantling of existing road) 98 Cement Concrete Road(100mm PCC 1:4:8 and 100mm CC 1:2:4) 99 C.C. Interlocking Tiles Road Type AConstruction of 80 mm tihck C.C. Interlocking Tile road including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-PCC = 100 mm,1:4:8 (cement, coarse sand & stone ballast of 20-40 mm)Sand= 50 mm thick local sand lair for preparation of surfaceTiles = 30% new + 70% old 100 Brick on edge Road (BOE) 101 Construction of thurst block in RCC 1:2:4 at bends & Tee in all feeder main including supply of all labour, material, T&P etc. complete as per the details given below :-Total no. of bends & Tee - 35 102 Providing nominal reinforcement @ 0.15% of Above items including cutting bending, hooking the bars, binding with wires or tack welding and supporting as required etc. complete (including cost of binding wire and MS Bar) 103 Supply of all materials, labour, T&P etc. required for construction of following masonry type chambers as per type design.Sluice valve Chamber 104 400mm 105 upto 100 mm 106 125 mm to 250 mm 107 300 mm to 400 mm 108 Air valve Chambers 109 50 mm dia VC 110 80mm dia 111 100 mm dia 112 Scour Valve Chamber 113 Fire Hydrant Chamber 114 Disposal of surplus earth /unserviceable material, by mechanical transport including loading, transporting, unloading to approved municipal dumping ground for lead upto 10 km for all lifts, complete as per directions of Engineer-in-charge. 115 Provision for crossing of Nalas for laying of pipe line using HDPE casing pipe of suitable dia. Width (0.5mto 2.0 m width) more than the outer width of nala, labour, T&P, necessary arrangement for diversion & pumping of water if required, barricading etc required for proper completion of work as per directions of engineer-in-charge. 116 0.5 - 1.0 m (Clear span) 117 1.0 - 1.5 m (Clear span) 118 1.5 - 2.0 m (Clear span) 119 Repairing / Shifting of existing water supply house connection due to falling in alignment of pipe line including supply of all materials, labour, T&P etc. required for proper completion of the work. 120 Inter connection with exesting risigingmain 121 CWR to Kashiram Awas Yojna - OHT 122 CWR to Zone I - OHT 123 Repairing of drain/ public ramp/other miscellaneous structures which are coming in alignment of pipe line and damaged during the laying of pipe line including supply of all materials, labour, T&P etc. required for proper completion of the work. 124 Brick masonry in cement mortar 1:4 125 12mm thick plaster in cement mortar 1:4 126 RCC M-20 (including MS work) 127 Providing new water supply house connection to the consumersfrom new distribution pipe line of following diametersincluding making ferrule connection, cost of ferrule, 15 mm dia HDPE and GI pipe, saddle piece, ball valve, specials, excavation, refilling of pit etc. complete. It also includes supply of all materials, labour, T&P etc. required for proper completion of the work. As per attached drawing. 128 For 80mm to 110 mm dia 129 For 125mm to 150 mm dia 130 For 150 mm to 250 mm dia 131 BOUNDARY WALL Construction of Boundry wall around campus as per unit estimate with RCC Columns @ 3.0m c/c distance with plinth beam and brick work including supply of all Materials, Labour, Tools and Plants etc. complete., as per departmental type drawing.Construction of2.0 meter high compound wall from formation level of campus,comprising of 230mmx230mm RCC Columns @ 3.0 m c/c distance with 230 mm thick beam at plinth and top, brick work of 230 mm thick in 1:4 and 12 MM THICK 1:4 cement plaster over all surface of wall , two coat of Exterior emulsion paint of approved reputed make over one coat of primer and even surface preparation by applying 2-3 layer of approved reputed make Puttyas perdesign approved by engineer in Charge, including supply of all material, labour, T& P etc complete. 132 At WTP site 133 M.S. GATE Supply and fixing M S iron gate 4.5M wide with a wicket gate including primer and painting etc all complete OHT / CWR Campus and wtp campus 134 3.60 m wide gate & 1.2m. Wicket Gate 135 Provide all materials, labour T&P etc. required for proper completion of work and construct Interlocking approach road in water works campous. 136 At WTP site 137 Provide all materials, labour T&P etc. required for proper completion of work including levelling, dressing excavation and filling of earth where necessary for develop of water works site including carriage of earth. 138 At WTP site 139 Construction of single roomed Staff Quarter with box (a set of two) 1 set = 2 nos. of staff quarters (2 G.F. + 2 F.F.) including common stair case and other miscellaneous works. The plinth area of each staff quarter is 57.706 sqm.Detailed Survey, Design& Drawing, Construction of Residential Building based Office Building on R.C.C frame structure at different location finished with all respect, flooring made up with vitrified Tile/ Kota stone , Flush door shutter , glazed window cum ventilation including mosquito proof shutter, waterproofing at roof , anti-skid tile at toilet / bathroom / kitchen , water supply and sanitary work & electrification with all fixture, painting with 3 coat apex at exterior surface and emulsion at interiorsurface including2 coat Birla white puttyofbuilding, apron around building, appropriate size of septic tank and soak pit, including supply of all material, labour, T&P complete as per the direction of the engineer in charge 140 At WTP site 141 ELECTRICAL AND MECHANICAL ITEMS: 142 INTAKE WELL AT BHONRAT DAM FOR 5.5 MLD WTP 143 PUMPING PLANTS: 144 Supply of Vertical Turbine Oil lubricated Raw water pump to lift 2500 LPM discharge at 43 m head complete with 19 m column assembly , 40 HP VSS squirrel cage induction motor B class insulation with reversible ratchet, chuck nutsuitable to operate on 415 volt (±10%), 3 Phase 50 HZ AC supply. (Synchronous Speed 1450 RPM) 145 2500 LPM, 40 HP, 43 m Head, 1450 RPM 146 A) MAIN PIPING- Supply of CIDF 200 mm Main piping required for delivery side, 250 mm common Header upto 1 m outside with 3 Nos 250x250x200 mm size Tee and 1 Nos 250x250x200 mm size Tee forbye pass arrangement ofthe pump housealong withall necessarydismantaling joints in delivery and common header , enlarger , reducer nuts, bolts, rubber packing etc. complete in all respect as per site conditions . 147 B) VALVES- 148 a) Supply of following size motor operated actuaters with DI sluice valves 149 i) 200 mm size 150 ii) 250 mm size 151 b) Supply of following size DI Non Return Valves 152 i) 200 mm size 153 ii) 250 mm size 154 CE/UL Certified Electromagnetic flow meter 155 (i) Electromagnetic flow meter of size 250 mm 156 ELECTRICAL ITEMS: 157 Supply of 3.5 core 120 Sq.mm. Armoured Aluminum Conductor Cable From LTControl Panelto MCC panel with lugs etc. 158 Supply of Auto Phase reversal unit / Automatic switch with inbuilt the delay & enclosure (Confirms to IEC: 60947-1 & IEC: 60947-6-1) of followint rating: 159 (i) 160 Amp. 160 Supply of dust and vermin proof MotorControl panel consisting of one no. incoming of 320 Amp MCCB and 4 Nos. (3+1)100 Ampand 2 Nos 63 amp outgoing MCCB Mirco processor based completesuitable to operate on 415±6 %volt , 3 phase , 50 Hz, AC supply with CT"S, PT, AVF meter, PF meter, Relays and protective devicecomplete in all respect. individual motors 161 Supply of 3 core 35 Sq.mm. Armoured Copper Conductor Cable from MCC panel to respective motors with lugs etc. 162 Supply of 40 HP (30 KW) digital Soft Starter with RS485 port - 400 V class. 163 Supply of CE/UL Certified Pressure Transmitter for each pump and common header 164 Supply of CE/UL Certified Radar type Level Transmiter for Intake well. 165 Supply of CE/UL Certified Surge protector for control panel 166 Double Plate Earthing of complete Pumping Station (as per IER/IS) including civil works and all material, separate double earthing for each equipment shall be carried out. 167 Supply of HOT of 3 Ton capacity, 10 mtr span , 12 mtr lift with traveling trolly 168 Supply of Spare of pumping plant as impeller, bowel bearing, wear rings etc. 169 Supply of Tools as per tender document 170 Supply of 10 mm Thickness Electrical rubber resistance sheet 171 Supply of Cable trench Chequerred plate 6 mm thickness, angle and C Chanel etc. 172 Supply of Fire fighting equipments such as four nos. fire extinguishers CO2/ ABC type. 173 Internal & External electrification and lighting of pumping station including necessary wall mounting fittings and lighting poles. 174 Painting Works including all material and T&P Complete. 175 Installation, Testing and Commissioning of all equipments and pumping plants etc including all material , T&P , labour complete in all respect. 176 CWR 177 ZONE -I 178 PUMPING PLANTS: 179 Supply of Vertical Turbine water lubricated Clear Water Pump with 4.5 mt column assembly along with VHS / VSS squirrel cageinduction motor complete with ratchet arragment chucknut and top shaft locking arragmentsuitable to operate on 415 volt (±10%), 3 Phase 50 HZ AC supply. (Synchronous Speed 1450 RPM) with following specifications. 180 500 LPM, 15 HP, 44 m Head, 1450 RPM 181 A) MAIN PIPING- Supply of 80 mm CIDF Main piping required for delivery side, 100 mm common Header upto 1 m outside with 3 Nos 100x100x80 mm size Tee and 1 Nos 100x100x80 mm size Tee forbye pass arrangement ofthe pump house along withall necessary enlarger , dismantaling joints in delivery and common header,reducer nuts, bolts, rubber packing etc. complete in all respect as per site conditions . 182 B) VALVES- 183 a) Supply of following size motor operated actuaters with DI sluice valves 184 i) 80 mm size 185 ii) 100 mm size 186 iii) 250 mm size at OHT (400 kl )Outlet 187 iv) 80 mm size at OHT(125 KL Kansiram Yojna) Inlet 188 v) 100 mm size at OHT(125 KL Kansiram Yojna) Outlet 189 b) Supply of following size DI Non Return Valves 190 i) 80 mm size 191 ii) 100 mm size 192 Supply of CE/UL Certified Electromagnetic flow meter 193 (i) Electromagnetic flow meter of size 100 mm for CWR outlet 194 (ii) Electromagnetic flow meter of size 250 mm for OHT (400 KL)outlet 195 (iii) Electromagnetic flow meter of size 100 mm for OHT (125 KL Kansiram Yojana)outlet 196 Supply of Chlorine Analyser with MODBUS RTU having Following specification - (a) FRC senser range 0-5 ppm (b) Analyser with RS 485 O/P suitable to OHT distribution line and compatible with SCADA system too. 197 ELECTRICAL ITEMS: 198 Supply of 3.5 core 120 Sq.mm. Armoured Aluminum Conductor Cable from LT Panelto MCC Panel with lugs etc. 199 Supply of Auto Phase reversal unit / Automatic switch with inbuilt the delay & enclosure (Confirms to IEC: 60947-1 & IEC: 60947-6-1) of followint rating: 200 (i) 250 Amp. 201 Supply of dust and vermin proofMCC Panel consisting of 1Noincoming Mirco processor based MCCB of 500 Amp , 4 Nos. (3+1) outgoing MCCB of 100 Amp , 10 No 63 Amp MCCB Mirco processor based for Lighting /Sparecomplete with power wiring, Ampire meter, Voltmeter etc. 202 Supply of 3 core 25 Sq.mm. Armoured Copper Conductor Cable from MCC panel to respective motors with lugs etc. 203 Supply of 15 HP (11 KW) digital Soft Starter with RS485 port - 400 V class. 204 Supply of CE/UL Certified Pressure Transmitter for each pump and common header 205 Supply of CE/UL Certified Radar type Level Transmiter for CWR for all zone. 206 Supply of CE/UL Certified level transmitter for OHT 207 Supply of CE/UL Certified Surge protector for control panel 208 Double Plate Earthing of complete Pumping Station (as per IER/IS) including civil works and all material, separate double earthing for each equipment shall be carried out. 209 Supply of 3Ton capacity hand operated overhead travelling (HOT) crane suitable for span up to 6 mtrs and travelling length upto 10 mtrs with clear lift up to 6 mtrs including gear type chain pulley block and geared travelling trolley complete with all accessories including girder. 210 Supply of Tools as per tender documet 211 Supply of 10 mm Thickness Electrical rubber resistance sheet 212 Supply of Cable trench Chequerred plate 6 mm thickness, angle and C Chanel , angle etc. 213 Supply of Fire fighting equipments such as four nos. fire extinguishers CO2/ ABC type. 214 Internal & External electrification and lighting of pumping station including necessary wall mounting fittings and lighting poles. 215 Painting Works including all material and T&P Complete. 216 Installation, Testing and Commissioning of all equipments and pumping plants etc including all material , T&P , labour complete in all respect. 217 ZONE -II 218 PUMPING PLANTS: 219 Supply of Vertical Turbine water lubricated Clear Water Pump with 4.5 mt column assembly along with VHS / VSS squirrel cage induction motor complete with ratchet arragment chucknut and top shaft locking arragment suitable to operate on 415 volt (±10%), 3 Phase 50 HZ AC supply. (Synchronous Speed 1450 RPM) with following specifications. 220 1150 LPM, 20 HP, 44 m Head, 1450 RPM 221 A) MAIN PIPING-Supply of 150 mm CIDF Main piping required for delivery side, 200 mm common Header upto 1 m outside with 3 Nos 200x200x150 mm size Tee and 1 Nos 200x200x150 mm size Tee forbye pass arrangement ofthe pump house along withall necessary enlarger , dismantaling joints in delivery and common header ,reducer nuts, bolts, rubber packing etc. complete in all respect as per site conditions . 222 B) VALVES- 223 a) Supply of following size motor operated actuaters with DI sluice valves 224 i) 150 mm size 225 ii) 200 mm size 226 iii) 400 mm size at OHT Outlet 227 b) Supply of following size DI Non Return Valves 228 i) 150 mm size 229 ii) 200 mm size 230 Supply of CE/UL Certified Electromagnetic flow meter 231 (i) Electromagnetic flow meter of size 200 mm for CWR outlet 232 (ii) Electromagnetic flow meter of size 400 mm for OHT outlet 233 Supply ofChlorine Analyser with MODBUS RTU having Following specification - (a) FRC senser range 0-5 ppm (b) Analyser with RS 485 O/P suitable to OHT distribution line and compatible with SCADA system too. 234 ELECTRICAL ITEMS: 235 Supply of 3.5 core 70 Sq.mm. Armoured Aluminum Conductor Cable from LT Panelto MCC Panel with lugs etc. 236 Supply of Auto Phase reversal unit / Automatic switch with inbuilt the delay & enclosure (Confirms to IEC: 60947-1 & IEC: 60947-6-1) of followint rating: 237 (i) 160 Amp. 238 Supply of dust and vermin proofMCC Panel consisting of 1Noincoming Mirco processor based MCCB of 250 Amp and 4 Nos. (3+1) outgoing MCCB of 125 Amp , 2 No 63 Amp MCCB Mirco processor based for Lighting /Sparecomplete with power wiring, Ampire meter, Voltmeter etc. 239 Supply of 3 core 35 Sq.mm. Armoured Copper Conductor Cable from MCC panel to respective motors with lugs etc. 240 Supply of 25 HP (18.5 KW) digital Soft Starter with RS485 port - 400 V class. 241 Supply of CE/UL Certified Pressure Transmitter for each pump and common header 242 Supply of CE/UL Certified level transmitter for OHT 243 Supply of CE/UL Certified Surge protector for control panel 244 Double Plate Earthing of complete Pumping Station (as per IER/IS) including civil works and all material, separate double earthing for each equipment shall be carried out. 245 3Ton capacity hand operated overhead travelling (HOT) crane suitable for span up to 6 mtrs and travelling length upto 10 mtrs with clear lift up to 6 mtrs including gear type chain pulley block and geared travelling trolley complete with all accessories including girder. 246 10 mm Thickness Electrical rubber resistance sheet 247 Tools 248 Cable trench Chequerred plate 6 mm thickness, angle and C Chanel , angle etc. 249 Fire fighting equipments such as four nos. fire extinguishers CO2/ABC type. 250 Internal & External electrification and lighting of pumping station. 251 Painting Works 252 Installation, Testing and Commissioning of all equipments and pumping plants etc including all material , T&P , labour complete in all respect. 253 ZONE -III 254 PUMPING PLANTS: 255 Supply of Vertical Turbine water lubricated Clear Water Pump with 4.5 mt column assembly along with VHS / VSS squirrel cage induction motor complete with ratchet arragment chucknut and top shaft locking arragment suitable to operate on 415 volt (±10%), 3 Phase 50 HZ AC supply. (Synchronous Speed 1450 RPM)with following specifications. 256 1150 LPM, 25 HP, 46 m Head, 1450 RPM 257 A) MAIN PIPING-Supply of 150 mm CIDF Main piping required for delivery side, 200 mm common Header upto 1 m outside with 3 Nos 200x200x150 mm size Tee and 1 Nos 200x200x150 mm size Tee forbye pass arrangement ofthe pump house along withall necessary enlarger , dismantaling joints ,reducer nuts, bolts, rubber packing etc. complete in all respect as per site conditions . 258 B) VALVES- 259 a) Supply of following size motor operated actuaters with DI sluice valves 260 i) 150 mm size 261 ii) 200 mm size 262 iii) 400 mm size at OHT Outlet 263 b) Supply of following size DI Non Return Valves 264 i) 150 mm size 265 ii) 200 mm size 266 CE/UL Certified Electromagnetic flow meter 267 (i) Electromagnetic flow meter of size 200 mm for CWR outlet 268 (ii) Electromagnetic flow meter of size 400 mm for OHT outlet 269 Chlorine Analyser with MODBUS RTU having Following specification - (a) FRC senser range 0-5 ppm (b) Analyser with RS 485 O/P suitable to OHT distribution line and compatible with SCADA system too. 270 ELECTRICAL ITEMS: 271 Supply of 3.5 core 70 Sq.mm. Armoured Aluminum Conductor Cable from LT Panelto MCC Panel with lugs etc. 272 Auto Phase reversal unit / Automatic switch with inbuilt the delay & enclosure (Confirms to IEC: 60947-1 & IEC: 60947-6-1) of followint rating: 273 (i) 160 Amp. 274 Supply of dust and vermin proofMCC Panel consisting of 1Noincoming Mirco processor based MCCB of 250 Amp and 4 Nos. (3+1) outgoing MCCB of 125 Amp , 2 No 63 Amp MCCB Mirco processor based for Lighting /Sparecomplete with power wiring, Ampire meter, Voltmeter etc. 275 Supply of 3 core 35 Sq.mm. Armoured Copper Conductor Cable from MCC panel to respective motors with lugs etc. 276 Supply of 25 HP (18.5 KW) digital Soft Starter with RS485 port - 400 V class. 277 CE/UL Certified Pressure Transmitter for each pump and common header 278 CE/UL Certified level transmitter for OHT 279 CE/UL Certified Surge protector for control panel 280 Double Plate Earthing of complete Pumping Station (as per IER/IS) including civil works and all material, separate double earthing for each equipment shall be carried out. 281 3Ton capacity hand operated overhead travelling (HOT) crane suitable for span up to 6 mtrs and travelling length upto 10 mtrs with clear lift up to 6 mtrs including gear type chain pulley block and geared travelling trolley complete with all accessories including girder. 282 10 mm Thickness Electrical rubber resistance sheet 283 Tools as per tender document 284 Cable trench Chequerred plate 6 mm thickness, angle and C Chanel , angle etc. 285 Fire fighting equipments such as four nos. fire extinguishers CO2/ABC type. 286 Internal & External electrification and lighting of pumping station. 287 Painting Works 288 Installation, Testing and Commissioning of all equipments and pumping plants etc including all material , T&P , labour complete in all respect. 289 INTAKE WELL SUB STATION (160 KVA) 290 Supply of 2mm thick MS Sheet fabricated factory wired dust and vermin proof cubical and floor mounting type control panel comprising of 1 No. incoming V.C.B.(630 Amp) and 2 Nos. outgoing V.C.B. panel with all accessories and protective devices suitable for 160 KVA 2 Nos.11/0.4 KVtransformers. 291 Supplyof70 Sq.mm size XLPE cable from 11 K.V.UPPCL metering panel to 11 KV incoming H.T. switch gear panel and panel to transformer including laying with cable tray of suitable size, all required material, labour T&P complete in all respect. 292 Supplyof 160 KVA 11/0.433 KV 50 Hz Copper woundoil cooled Transformer withoff load tap changer from +7.5% to -15% LV side @ 2.5 % step vectore group Dy11 as per IS 1180, 2014 Part 1 Level 1 effecient with neccessory saefty devices . 293 Supplyof 14 SWG CRCA MS sheet fabricated factory wired, floor mounting type L.T. panel comprising of following.L.T. panel comprising of 2 Nos. incomer 320 Amp Microprocessor based MCCB draw out type and 1Nos. outgoing Microprocessor based MCCB of 320 Amp and1 no. outgoing 63Amp MCCB or suitable capacity for auxiliary lighting / spare suitable to operate on 415±6 %volt , 3 phase , 50 Hz, AC supply with CT"S, PT, AVF meter, PF meter, Relays and protective devicecomplete in all respect. 294 Supply of 75 kvar APFC panel suitable for above LT panel with all necessary metering and protective devices complete in all respect. 295 Supply and laying of 1100 volt grade 70 sq mm 3½ core PVC Armored Aluminum cable from transformer to L.Tpanel (2x3½x70 sq mm)with required size of cable tray and all nessesary material, T&P , laboure complete in all respect. 296 Making earth pit for Earthing system shall executed as per IS: 3043 and I.E. rules. 297 Installationtesting and commissioning of 11 KV/0.4 KV substations including Transformers, HT Panels and L.T. main control panel including all labor T&P complete in all respect. 298 Supply and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugsof 70 sq mm size 3 core XLPE aluminium conductor cable of 11 kv grade. 299 Supply and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugsof 70 sq mm size 3 core XLPE aluminium conductor cable of 11 kv grade. 300 Provision for routine testing of equipments such as transformer, HT Panels and Main LT Panel at manufacturer’s works. 301 19 mm Thickness Electrical rubber resistance sheet 302 Cable trench Chequerred plate 6 mm thickness, angle and C Chanel etc. 303 Fire fighting equipments such as four nos. fire extinguishers CO2 type and fire bucket with stand 304 Internal & External electrification of sub station 305 NOC from Electrical safety department for all field installations such as pumping plants, substation etc. 306 SUB STATION OF WTP +CWR (315 KVA) 307 Supply of 2mm thick MS Sheet fabricated factory wired dust and vermin proof cubical and floor mounting type control panel comprising of 1 No. incoming V.C.B.(630 Amp) and 2 Nos. outgoing V.C.B. panel with all accessories and protective devices suitable for 315 KVA 2 Nos.11/0.4 KVtransformers. 308 Supply of120 Sq.mm size XLPE cable from 11 K.V.UPPCL metering panel to 11 KV incoming H.T. switch gear panel and panel to transformer including laying with cable tray of suitable size, all required material, labour T&P complete in all respect. 309 Supply of315 KVA 11/0.433 KV 50 Hz Copper woundoil cooled Transformer withoff load tap changer from +7.5% to -15% LV side @ 2.5 % step vectore group Dy11 as per IS 1180, 2014 Part 1 Level 1 effecient with neccessory saefty devices . 310 Supply of 14 SWG CRCA MS sheet fabricated factory wired, floor mounting type L.T. panel comprising of following.L.T. panel comprising of 2 Nos. incomer 800 Amp Microprocessor based ACB draw out type and 1Nos. outgoing Microprocessor based MCCB of 400 Amp for WTP and1 no. outgoingMicroprocessor based MCCB of 500 Amp for CWR and 1 Nos63Amp MCCBfor auxiliary lighting / spare suitable to operate on 415±6 %volt , 3 phase , 50 Hz, AC supply with CT"S, PT, AVF meter, PF meter, Relays and protective devicecomplete in all respect. 311 Supply of 175 kvar APFC panel suitable for above LT panel with all necessary metering and protective devices complete in all respect. 312 Supplyof 1100 volt grade 300 sq mm 3½ core PVC Armored Aluminum cable from transformer to L.Tpanel (2x3½x300 sq mm) including laying with cable tray of suitable size, all required material, labour T&P complete in all respect. 313 Making earth pit for Earthing system shall executed as per IS: 3043 and I.E. rules. 314 Installationtesting and commissioning of 11 KV/0.4 KV substations including Transformers, HT Panels and L.T. main control panel including all labor T&P complete in all respect. 315 Supply and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugsof 70 sq mm size 3 core XLPE aluminium conductor cable of 11 kv grade. 316 Supply and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugsof 120 sq mm size 3 core XLPE aluminium conductor cable of 11 kv grade. 317 Provision for routine testing of equipments such as transformer, HT Panels and Main LT Panel at manufacturer’s works. 318 19 mm Thickness Electrical rubber resistance sheet 319 Cable trench Chequerred plate 6 mm thickness, angle and C Chanel etc. 320 Fire fighting equipments such as four nos. fire extinguishers CO2 type and fire bucket with stand 321 Internal & External electrification of sub station 322 NOC from Electrical safety department for all field installations such as pumping plants, substation etc. 323 Automation of Intake Well 324 ForIntake Well 325 SITC of CE & UL Certified PLC/RTUwith redundantCPU & Powersupply in IP 54 enclose suitable to Communicate with GSM based modem unit withredundant CPU & Powersupply with annlog & digital parameter & featuers as specified, for each Intakewell to store and transmit dataon GSM backbone, RTU/PLC desgined with logic to transfer data at multiple stations with control panel as specified intender technical specifications. 326 SITC of G.S.M./G.P.R.S. based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories include with signal enhancer antenna made for pumping plant internetcharges as specified in tender technical specification . 327 SITC of Intelligent energy meters 328 SITC of Control Panel with IP 54 Protection, Industrial Grade for all equipment. (Separate for control (24 V) and power equipments.) upto 3 pumps. 329 CE/ UL Certified 7" HMI touch screen suitable to communication with PLC/RTU for local display & control of process parameters. 330 Cabling 331 Complete Cabling for Intake well including all power & control cable of all equipments at ZPS and OHT. 332 SITC of Security Survelliance IP Camera with recorder 333 Automation of Main CWR 334 ForMain CWR 335 SITC of CE & UL Certified PLC/RTUwith redundantCPU & Powersupplyin IP 54 enclose suitable to Communicate with GSM based moden unit withredudant CPU & Powersupply with annlog & digital parameter & featuers as specified, for each ZPS/OHT to store and transmit dataon GSM backbone, RTU/PLC desgined with logic to transfer data at multiple stations with control panel as specified intender technical specifications. 336 SITC of G.S.M./G.P.R.S. based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories include with signal enhancer antenna made for pumping plant internetcharges as specified in tender technical specification . 337 SITC of Intelligent energy meters 338 SITC of Control Panel with IP 54 Protection, Industrial Grade for all equipment. (Separate for control (24 V) and power equipments.) upto 3 pumps. 339 SITC of CE/ UL Certified 7" HMI touch screen suitable to communication with PLC/RTU for local display & control of process parameters. 340 Cabling 341 SITC of Complete Cabling for Intake well including all power & control cable of all equipments at ZPS and OHT. 342 SITC of Security Survelliance IP Camera with recorder 343 Master Control Station (MCS) 344 SCADA DISPLAY 345 SITC of CE/UL & BIS Certified industrial grade LED MONITOR with latest configrutation as per specification 346 (i)65" Size in No 347 SITC of Desktop/PC with i5/i7 processor for as per specification mentioned in technicalbid documents. 348 SITC of CE/UL Certified 5KVA UPS with batteries as per specification mentioned in technical bid document. 349 SITC of CE/UL Certified master control room PLC with redundant CPU & power supply at MCS in IP54 - enclouser as spec mentioned in technical bid documents. 350 SITC of CE/UL Certified Field gateway agent for transfering data from MCS to Central control room. 351 SITC of GSM based wireless /Broadband/Equipment communication system for PLC capable to transfer & received data & gather dat from remote sites to control station,All accessories included signal enhancer antenna along with running expenses till DLP. 352 CE/UL Certified Firewall for network protection. 353 SITC of SURGE PROTECTOR FOR ETHERNET Communication protection. 354 CE/UL certified industrial grade Ethernet Switch. 355 SITC of Mobile App Facility system architecture(Industries internet based & viewed through mobile apps for increased local & Remote Visibility). 356 Canon/HP or equivalent Laser Printer 1018 or equivement. 357 SITC of Security Surveillance IP camera with recorder (optional) 358 Installation, Commissioning & testing including required furniture A/c etc. 359 Trial run for 3 month period 360 TRAIL & RUN 361 Operation Charges for 03 Months Trial & Run for above TW"S & CWR"S
|