Tender For Special Repair To Lt Cables, Lt Panels And Connected Items From Power House To Cadet Mess Kitchens At Nda Khadakwasla.; 1 Supply and Laying in replacement including testing and commissioning LT UG Power cable, XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with multi-stranded aluminium conductor including termination with LT Panel/Feeder Pillar with galvanised or Cadmium plated high tensile nuts, bolts and washers etc including Sheddling /clamping on any type of wall with suitable size of GI Clamps, nuts, bolts & washers etc complete of size 300 Sqmm 3.5 Core all as specified and directed. 2 S & F ofWire mesh Cable Tray Hot Dipped Galvanized size 54 X 300mm, Trays should comply Standard EN ISO 14 61: at least 550 h of SST. The deflection of cable tray must be no more than 1/200th of the distance between two supports and tested in accordance with the standard IEC 61537, Wire cable trays must be designed with an optimum span of 1.5 m, taking into account the maximum carrying capacity authorised by the manufacturer including all standard wall mounting accessories e.g. SS Mounting Bracket, bends, Fastners, kitastar, nut, bolts and washers etc complete all as specified and directed.It shall be manufactured with a longitudinal "T- welded" safety edge complete all as specified and as directed. 3 S&F GI tubing"light grade"150 mm dia ISI marked with all fittings laid in trenches and fixed on pole by flat iron clamps, nut, bolt, washer of suitable size complete all as specified and directed 4 S & F in replacement including testing and commissioning LT Feeder Panel weather proof outdoor type double door, fabricated out of 3.15 mm thick CRCA sheet with epoxy powder coating of RAL-7035 (Siemens Gray) shade with matt finish with seven tank pre treatment process.The panel shall be fabricated by CPRI approved manufacturer only.The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, front side double door type with locking arrangementfor front side and nut bolt fitting for back side, comprising ofgaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel.The panel shall be provided with aluminium bus bars, electrolytic grade of 1000 Amp current rating connected with item No. 05 bus bar in closed compartment.The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding.The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured.All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc.The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign Cts and RYBLED indicating lamps at incoming.The panel shall be provided with manufacturer"s name plate, skull & bones danger notice board etc.The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement .All MCCBs shall be provided with spreader links with phase separators on both sidesand suitable extended rotary handes for all incoming and outgoing MCCBs .The overall size of the panel shall not less than 1700mmX500mmX1400mm (LxDxH).The panel shall be provided for Cable entry from bottom side for each Cable including2 Nos of Earthing Terminals one on each side of the Panel with GI earth strip and including following accessories complete all as specified and as directed :-Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by Engr-in-charge.(a) MCCB 4 Pole, 415 Volts, 630 Amp, 50 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links and phase seperators on both side. (Incoming) - 01 No. (b) MCCB 4 Pole, 415 Volts, 250 Amp, 36 KA Breaking capacity with thermal adjustable with Ics = 100% of Icu including suitable size of spreader links and phase seperators on both side. (Outgoing) - 05 No.(c) MCCB 4 Pole, 415 Volts, 160 Amp, 36 KA Breaking capacity with thermal adjustable with Ics = 100% of Icu including suitable size of spreader links and phase seperators on both side. (Outgoing) - 01 No. 5 S & Finstallation,testing and commissioningLT Feeder Panel weather proof outdoor type double door, fabricated out of 3.15 mm thick CRCA sheet with epoxy powder coating of RAL-7035 (Siemens Gray) shade with matt finish with seven tank pre treatment process.The panel shall be fabricated by CPRI approved manufacturer only.The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, front side double door type with locking arrangementfor front side and nut bolt fitting for back side, comprising ofgaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel.The panel shall be provided with aluminium bus bars, electrolytic grade of 1000 Amp current rating connected with item No. 04 bus bar in closed compartment.The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding.The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured.All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc.The panel shall be provided with manufacturer"s name plate, skull & bones danger notice board etc.The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement .All MCCBs shall be provided with spreader links with phase separators on both sidesand suitable extended rotary handes for all incoming and outgoing MCCBs .The overall size of the panel shall not less than 1200mmX500mmX1400mm (LxDxH).The panel shall be provided for Cable entry from bottom side for each Cable including2 Nos of Earthing Terminals one on each side of the Panel with GI earth strip and including following accessories complete all as specified and as directed :-Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by Engr-in-charge.(a) MCCB 4 Pole, 415 Volts, 160 Amp, 36 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links and phase seperators on both side. (Outgoing) - 04 No (b) MCCB 4 Pole, 415 Volts,125 Amp, 16KA Breaking capacity with thermal adjustable with Ics = 100% of Icu including suitable size of spreader links and phase seperators on both side. (Outgoing) - 02 No. 6 M & L in replacement for earthing complete with galvanized steel earth plate electrode 600 X 600 X 6.3 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.50 m deep below normal ground level in any type of soil strata, connected to galvanized iron strip 25 x 4mm by means of bolts, nuts and washers of galvanised iron or steel all as shown in earth plate No 3 of MES schedule 1991 Part – I connected to LT Panel/Feeder Pillar/Sub Feeder Pillar/Change over Panel etc as required including necessary excavation and earth work, concrete pit & chamber in PCC 1:2:4 type B1 & pit cover with lifting handle and Earth lead and 20mm Dia GI watering pipe medium grade, Funnel, wiremesh, etc. complete all as specified and directed by Engr-in-Charge including testing on completion. Note:GI strip 25x4mm beyond 7.5m lenght shall be measured and paid seperately. 7 Supply & install in replacement of ACB,1000 Amps, 4 Pole, 415 Volts, 50 KA, Manual Draw Out (MDO) type, as per IS/IEC-60947-2 with microprocessor based adjustable LSIG & temperature rise protection consisting of digital LCD display with battery backup, inbuilt LED indication and alarm for temp rise, current metering, RS 485 Port and UV Release etc including test certificate of ACB.Rates also include for fixing to LT Panel including cutting, welding to CRCA sheet and necessary busbar arrangement etc including taking down existing one complete all as specified and directed. 8 Excavation in trenches, n.exc 1.5m wide and n. exc 1.5 m depth and getting out for foundation of pole, stay, laying of cable and pipe as in soft/loose soil complete all as specified and directed 9 Ditto all as per item No 08 above but hard / Dense soil 10 Returning and filling, including spreading levelling and well ramming in layers n exc 25 cm all as specified and directed. 11 Removing excavated material a distance n. exc 50 m & depositing where directed at a level n. exc 1.5 m above the starting point complete all as specified and directed 12 Supply and laying 160 x 135 mm outer & inner dia, double walled corrugated (DWC) HDPE duct pipe confirming to IS-16205 Pt-24 with antirodent and non flame propogating properties of approved colour complete with fittings i.e.coupler,Tee, elbow clamp for cable protection of size 300 to 400 Sqmm 3.5 core complete all as specified and directed 13 M&L for road cutting through existing bituminous road as required for laying pipe/cable etc and make good with and including earthwork and necessary excavation, complete material required to match with the existing one or with PCC (1:2:4) type B1 and bitumin complete all as specified and as directed 14 S & F in replacement of GI strip 25 x4 mm earth as earth continuity conductor or main earthing lead fixed to wall batten or recess or chases or buried in groung or fixed to poles or any other indicated situation complete all as specified and as directed. 15 S & F in replacement including testing and commissioning LT Feeder Panel weather proof outdoor type double door, fabricated out of 3.15 mm thick CRCA sheet with epoxy powder coating of RAL-7035 (Siemens Gray) shade with matt finish with seven tank pre treatment process.The panel shall be fabricated by CPRI approved manufacturer only.The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, front side double door type with locking arrangementfor front side and nut bolt fitting for back side, comprising ofgaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel.The panel shall be provided with aluminium bus bars, electrolytic grade of 400 Amp current rating.The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding.The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured.All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc.The panel shall be provided with digital multifunction meter 4410 Series, Accuracy Class 1 with RS 485 Parameters with cast Resign CTs and RYB, LED indicating lamps at incoming.The panel shall be provided with manufacturer"s name plate, skull & bones danger notice board etc.The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement .All MCCBs shall be provided with spreader links with phase separators on both side complete all as specified and as directed. The overall size of the panel shall not less than 1600mmX400mmX1000mm (LxBxH).The panel shall be provided for Cable entry from bottom side for each Cable including2 Nos of Earthing Terminals one on each side of the Panel with GI earth strip and including following accessories:-Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved by Engr-in-charge.(a) MCCB 4 Pole, 415 Volts, 250 Amp, 36 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links on both side. (Incoming) - 01 No. (b) MCCB 4 Pole, 415 Volts, 80 Amp, 16 KA Breaking capacity with adjustable Thermal and adjustable Magnetic overload protection with Ics = 100% of Icu including suitable size of spreader links on both side. (Outgoing) - 04 No. (c) MCB 4 Pole, 415 Volts, 63 Amp, 10 KA Breaking capacity conforms to IEC 60947-2. (Outgoing) - 02 Nos. 16 M&L preperation of old/new steel surfaces over 10 cm in width or girth not otherwise described and applying 2 coats of synthetic enamel paint over a coat of red oxide primer.
|