Construction Of Bsl Lab 3 In Microbiology Dept. At Rims Ranchi For The Year-1. Supply Ahu Capacity: 3500 Cfm Double Skin Ahu Complete With Mixing Box, Cooling Coil, Fan , Volume Control Dampers For Supply, Fresh Air, Fresh Air Filter. Static Pressure ( Mm Wg ) - 100 Construction – 28Mm Puf Moulded Double Skin Detachable Panels Structural - Extruded Spl Alloy Al Profiles Filled With Puf Panel - External Skin - 0.6 Mm Pre Plasticised Sheet Panel - Internal Skin - 0.6 Mm Plain Gi Sheet Insulation Material / Thickness - 25Mm Thick Puf With 45Kg / M3 Density Fan Make & Type - Nicotra / Kruger Make Didw Backward Curve Centrifugal Fan Fan Wheel Size & No. Of Fans - Rdh 315R #1 Fan Speed In Rpm – 2381, Critical Fan Speed In Rpm – 3100 Fan Outlet Velocity In Mps - 8.68 Motor Drive Arrangement - Taper Lock Pulleys For Fan & Motor Both Type Of Balancing / Test Procedure - Statically & Dynamically / Amca Tested Type Of Vibration Isolators - Rubberized Mounts Filters Provision - Pre Filters& Hepa Filters Coil Type - Cooling Coil Coil Surface Area - Sq. Ft - 6.11 No.Of. Coil Rows- 6 Face Velocity Across The Coil - 491 Coil Specification - 1 / 2 " Od 27Swg Copper & 36 Swg Ai Fin At Fpi Canvass - Srf Make Flexible Fire Retardant Canvass Hardware - Galvanized, Operationwt ( Kgs ) - Aprox – 240 2 Exhaust Ahu Capacity: 4500 Cfm Double Skin Ahu Complete With Mixing Box, Volume Control Dampers For Return, Fresh Air Static Pressure ( Mm Wg ) - 100 Construction - 28Mm Puf Moulded Double Skin Detachable Panels Structural - Extruded Spl Alloy Al Profiles Filled With Puf Panel - External Skin - 0.6 Mm Pre Plasticised Sheet Panel - Internal Skin - 0.6 Mm Plain Gi Sheet Insulation Material / Thickness - 25Mm Thick Puf With 45Kg / M3 Density Fan Make & Type - Nicotra / Kruger Make Didw Backward Curve Centrifugal Fan Fan Wheel Size & No. Of Fans - Rdh 315R #1 Fan Speed In Rpm - 2381 Critical Fan Speed In Rpm – 3100 Fan Outlet Velocity In Mps - 8.68 Motor Drive Arrangement - Taper Lock Pulleys For Fan & Motor Both Type Of Balancing / Test Procedure - Statically & Dynamically / Amca Tested Type Of Vibration Isolators - Rubberized Mounts Filters Provision - Pre Filters, Hepa Filters Hardware Etc 2.1 Ahu Control Panel 3 Ducting:Ventilation Ducting Will Be Made Out Of Minimum 22 Gauge Gi Sheet, Exhaust Duct From The Lab To The Ahu Will Be 22 Gauge Gi Duct. All The Ventilation Ducting Including Return Air Riser Will Be Leak Proof. Insulation Material With Nit Rile Foam / Cross Linked Polyethylene Material ( Aluminum Foil Insulation ) 4 Condensing Unit: Supply And Installation Of Condensing Unit With 8.5 Tr Capacity Including, Gas, Copper Tubing, Drier & Expansions Valves Etc 4.1 Treated Fresh Air Unit – 5 Tr 5 Dampers :Galvanised Steel Volume Controlled Damper, Opposed / Parallel Blade Dampers Are Used To Carry Out A Rough Air System Balance With Closer Control Being Carried Out At The Individual Grilles Or Diffusers. 6 Supply & Return Air Grills Moc: Crca Powder Coated, 1.2 Mm Thick With Perforation 7 Supply Hepa Filter Box Type : Box Type, Media : Ultra Clean Glass Fibre Paper-Imported, Casing : M.S. Powder Coated, Retention : 0.3 Micron, Efficiency : 99.97%, Pressure Drop: 25 Mm Of W.C. Size: 450 X 450 X 75 Mm 8 Bibo Filter Unit 9 Virus Burnout System 10 Ceiling Panel:Modular Ceiling: Modular Ceiling Will Be Made For Clean Room Application, Pre-Engineered 50 Mm Thick Puf Panels With Pcgi Sheets With Puf Insulation Of Minimum 38-40 Kg / M3. Both Surfaces Should Be Power Coated 0.47 Mm Thick Pcgi Sheet And Will Be Installed Along The Outer Walls, Partitions And False Ceiling To Create An Impervious Shell Which Is Fully Sealed. 11 Modular Wall: Modular Wall Will Be Made For Clean Room Application, Pre-Engineered 50 Mm Thick Puf Panels With Pcgi Sheets With Puf Insulation Of Minimum 38-40 Kg / M3. Both Surfaces Should Be Power Coated 0.47 Mm Thick Pcgi Sheet And Will Be Installed Along The Outer Walls, Partitions And False Ceiling To Create An Impervious Shell Which Is Fully Sealed. 11.1 Modular Wall:80 Mm Wall Panel With Return Air Riser 12 Covings: Extruded Aluminum Anodized R75 Clip-On Type ( Male & Female Connectors ) Covings For Entire Wall To Wall & Wall To Ceiling Joints 13 Modular Clean Room Door Flush Door Finishes Shall Be 50 Mm Thick 1.2Mm Thick Pcgi Sheet Suitable To Fix On 50 Mm Thick Wall Panel With Provisions For Double Glazing Glass For All Door And Hardware Like Push Plate.Puf Panels Will Be With Pcgi Sheets, Powder Coated On Both Sides And Puf Insulation Of Minimum 38-40 Kg / M3. Concealed Hardware For Fixing Of Door Frames, Door Closure, Ss Hinges, Ss Door Handle, Ss Ball Bearing Butt Hinges, Automatic Drop Seal, Concealed Tower Bolt For The Double Door, Both Sides Lock And Key Arrangement Etc 13.1 Size: ( Single Door ) 1000 X 2100 Mm 13.2 Size: ( Double Door ) 1200 X 2100 Mm 14 Differential Pressure Gauge Supply, Installation Of Dwyer Make Magnahelic Pressure Gauges 0 – 10 Mm For Monitoring Differential Room Pressures 15 Epoxy Flooring:Flooring Shall Be Of 6 Mm Of Industrial Epoxy Including Screed Compound For Adhesion With Bubble Free Perfect Smooth Finishing Completed Into Two Steps: Hardening And Smoothening .Epoxy Used For This Application Will Be Self-Leveling And Clean Room Compatible. 16 Epoxy Coving 17 Door Interlocking System 18 Dynamic Pass Box:Moc : Ss 304 Size: 2’ X 2’ X 2’ , Door, Interlocking System, Hepa Filter, Pre Filter, Motor Blower, Uv Light, Fluorescent Lamp Etc 19 Electricals:For The Purpose Of Energizing The Bsl Laboratory Facility All The Electrical Fittings And Fixtures In The Laboratories Areas Shall Be Suitable For Clean Room Application And Shall Be Sealed. 20 Shed Work For Ahu & Ac 21 Civil Work 22 Uv Lamp 23 Led Lights 24 Split Ac 1.5 Tr, With Stabilizer, Copper Tubing Etc 25 Split Ac 5 Tr, Timer Control With Stabilizer, Copper Tubing Etc 26 Garment Storage Cabinet: A Garment Storage Cabinet That Can Be Locked Shall Be Provided In The Change Rooms For Each Lab Worker. The Garment Storage Cabinets Shall Be In Ss304 , Dimension: 4’ X 1.5’ X 5’ ( Moc: Crca Powder Coated ) 27 Elbow Operated Tap With Ss Sink Unit 26 Emergency Shower: Emergency Shower With Eye Wash 28 Fire Detection & Alarm System: Fire Detection And Alarm System Will Be Provided For The Entire Bsl-3 Laboratory Facility To Detect Any Eventual Case Of Fire In The Building. 29 Fire Extinguishers - 2 Kg 30 Epabx System ( Intercom Facility ) : Telephone Instrument Facility To Be Provided Between Microbiologist / Staff Room 31 Cctv Surveillance System With 8 Dvr And Storage Capacity With Monitor And 8 Cctv Cameras In The Bsl Iii, Ante And Change Rooms 32 Lan Wiring And Connectivity With Sockets To Be Provided At Strategic Locations In The Bsl Facility 33 Uninterrupted Power Supply System : For Interlocking System, Fire Panel, Cctv Etc ( 5 Kva ) 34 Uninterrupted Power Supply System Forbio Safety Cabinet ( 3 Kva ) 35 Drain: All Liquid Drain Coming Out From The Laboratory Will Be Connected To A Single Drain With Back Flow Prevention 36 Water Supply: Water Supply To The Bsl-3 Laboratory Shall Be Provided Through The Existing Water Distribution Network In Campus. All The Necessary And Required Arrangements For Tapping And Extension Of Existing Water Line From The Adjacent Building 37 Bio Safety Cabinet: Class Ii Type B2 Size: 4’ X 2’ X 2’ ( W X D X H ) Moc: Crca Powder Coated ( Make: Microflow / Biobase ) 38 Work Table – 4 Feet Steel
|