The Subject Of The Order Is The Delivery Of A Brand New, Complete Emergency Power Generator Mounted On A Trailer. Minimum Technical Requirements Of The Unit: A. Maximum Power – Min. 104 Kva/83 Kwb.Rated Power – Min. 100 Kva/80 Kwc.Voltage – 400/230 Vd.Frequency - 50Hz (Full Frequency Stabilization +/- 2%E. Engine: Diesel, 4-Cylinder, In-Line, Liquid-Cooled, 1500 Rpm, Stage V - In Accordance With Regulation (Eu) 2016/1628F. Fuel Type: Diesel Oil. Fuel Tank - Min. 350 L, Built Into The Frame Of The Unit, Operating Time On One Full Zbiorniku Min. 20Hh.Ciśnienie Akustyczne W Odległości: 7 M Max 68 Db; W Odległości: 1 M Max 79 Dbi.Elektroniczna Regulacja Obrotów Silnikaj.Elektroniczny Sterownik Agregatu Z Możliwością Automatycznego Startuk.Liczba Faz – 3L.Sterownik Z Funkcją Automatycznego Startu Agregatu (Amf),M.Zabezpieczenie Prądnicy W Ręcznym I Automatycznym Trybie Pracyn.Instalacja Elektryczna 24V Lub 12V. Air Filter, Fuel Filter, Oil Filter. Automatic Start-Up. Silenced Silencer, Silenced Housing. Digital Unit Management Panel. Circuits, - Residual Current Protection Where Required, - Earthing Clamp/Terminal, - Appropriate Marking Of All Circuits, - Degree Of Protection Suitable For Outdoor Operation. The Switchboard Should Include: - 63 A, 400 V, 5P, 3P + N + Pe, Industrial Socket, - 32 A, 400 V, 5P, 3P + N + Pe, Industrial Socket, - 3 × 230 Socket V, 16 A, 2P+Pe, - Independent Protection Of Individual Sockets. 1B. The Generator Should Have An External Multi-Contact Control Connector, Enabling Connection With The Control Cable To The Ats/Ats System Of The Facility In Which It Will Be Disposed In The Future. The Connector Is Required To Provide At Least The Following Functions: - Remote Start Of The Generator, - Remote Stop Of The Generator, - Generator Ready For Operation Signal, - Signal Generator Is Running, - Signal The Generator Has Reached The Correct Voltage/Frequency, - The Generator Failure Signal, - The Low Fuel Level Signal, - The Operation On Load Signal - If The Generator Controller Allows Its Output. The Connector Should Have A Minimum Of 8-12 Contacts. The Contractor Is Obliged To Provide, Together With The Generator, A Diagram Of The Control Connector Terminals, A Description Of All Signals And Requirements For The Control Cable. The Generator Must Enable Operation In The Auto Mode. In The Auto, The Generator Should Be Waiting For A Signal From The Szr/Ats System. After Receiving The Start Signal, The Generator Should Automatically Start The Engine, Achieve The Required Electrical Parameters And Send A Signal Of Readiness To Take Over The Load To The Szr/Ats System. After The Signal Demand For The Generators Operation Disappears, It Should Automatically Return To The Standby Mode And Then Stop The Engine After The Run-Down/Cooling Time Specified By The Manufacturer. The Entire System Should Enable Automatic Taking Over And Releasing The Load Without The Need To Manually Operate The Generator, While Maintaining The Required Interl
|