Firefighting Equipment Installation Work – Gas Extinguishing Systems. The Stops On The U5 Subway Line Each Have A Computer Room - Here Called A System Technology Room - Which Is Protected With An Automatically Operating Gas Extinguishing System To Ensure The Greatest Possible Availability. There Is No Building Law Requirement For An Extinguishing System. The Inert Gas Argon Is Used As The Extinguishing Agent. The Size Of The Extinguishing Areas Is Approx. 500M3. The Extinguishing Areas Are Continuously Monitored By Smoke, Heat And/Or Flame Detectors. In The Event Of A Fire, These Send A Signal To The Fire Alarm Center. Fire Detection And Fire Alarm Panels Are Not Part Of The Scope Of Services Of The Gas Extinguishing System. The Deletion Process Is Triggered Via A Defined Standard Interface. The Central Technology And Extinguishing Agent Storage Is Located In A Room Directly Next To The Extinguishing Area. The Piping And Arrangement Of The Extinguishing Nozzles Within The System Technology Room Must Be Coordinated With The Arrangement Of The Installations. Approved Automatic Pressure Relief Flaps Are Provided In The Event Of Flooding. The System Must Be Manufactured In Accordance With The Vds Guidelines.