Bids Are invited for Oil Filled Auxiliary Service Transformers For 2X660 Mw Ennore Tps 3500Kva, 11Kv 3.6Kv, 3 Phase, 2 Winding, Outdoor, Onan, Z 5.0 Percent, Dyn1 , Extra Oil , 10 Percent, In Sealed Non Returnable Standard Drums For 3500Kva Transformer , Tank Pressure Test , Tank Vacuum Test , Measurement Of Acoustic Noise Level As Per Nema Tr 1 , Temperature Rise Test At A Tap Corresponding To Maximum Losses , Lightning Impulse, Full And Chopped Wave Test On Windings , As Per Iec 60076 3 , Measurement Of The Harmonics Of The No Load Current , Zero Sequence Impedance Measurement , Short Circuit Test, Special Test As Per Iec 60076 5 , Hv Bushing With Metal Parts And Gaskets , Lv Bushing With Metal Parts And Gaskets , Lv Neutral Bushing With Metal Parts And Gaskets , Wti With Contacts , Tap Changer Contacts , Magnetic Oil Gauge, Oil Level Indicator With Contacts , Oti With Contacts , Buchholz Relay Complete , Float With Contact For Buchholz Relay , Set Of Gaskets Other Than That With Bushing , Set Of Valves , Pressure Relief Device Total Quantity : 23
|