Tender For Installation Of Hvac (Heating, Ventilation, And Air Conditioning) In Animal Facility, Gbu Design strategies shall include: Uses of 100 % fresh air with no recirculation in Animal holding area Managed directional flow Positive pressure monitoring and control Temperature 22+/- 2 Degree C Humidity below 65 ACPH more than 16 Supply air with three Stage filtration. Exhaust air through HEPA filters Installation of HVAC systems for the Animal House will also include the following: • Thermal insulation, GI Ducting for supply & return line • HEPA filters for Laboratory Exhaust - 2000 CFM • Supply and exhaust AHUs • Dx Type Condensing unit - 11 TR • Electrical wiring for AHU & DX units • 2 split ACs 1.5 TR • VFD Control Panel with VFD drive