|
Bids Are Invited For 1 Multi-sensor mounting-ceiling detector wall. operating voltge-15 to 32 vdc; loop powered, operating current- 200 μΑ, alarm current-4.5 ma, temp. range-0°c- 38°c, addressing-laddress Rotatory switch addressing 2 Plug-In Photoelectric Smoke Detector Base, diameter: 4.0 inches (10.2cm), Base Height: 74 inches (18.8 mm), Operating Voltage: 15 to 32 VDC, Standby Current: 150µA compatible with Multi sensor detector FSP-951T with Surface plate and accessories 3 Response indicator compatible for 2 wire detectors, alarm status is indicated By Red color LED, operates on 12 VDC, Dual LEDs for 360 visibilities, Flush / Ceiling wall mount, Operating Current: 10mA, Indication: 12 Vdc alarm 4 Hooter, Strobe Flash Rate 60Hz; 1 Flash per second ,horn Sound Output 73-104 dBA; 24VDC Nominal, 9.0 Operating Voltage 16 VDC to 33 VDC (24 VDC nominal), Maximum Current 98 mA RMS, Dimensions 131 mm L Å~ 127 mm W Å~ 38 mm D along with the accessories round trim ring to adapt the wall device for ceiling mount applications5 Break glass indoor type Addressable manual call point. compatible with all Notifier intelligent panels. Max. Operating Current:7.8mA, Avg Operating Current 385 µA, operating voltage 24V DC, IP24 with accessories Control module for notifier with accessories, protocol-flash scan. external supply 6 voltage-24 vdc, max AC current rating-3A, Operating voltage-15 to32vdc, operating current-485mA, Alarm current-6.5 ma 7 Relay module for notifier panel with accessories, mounting-wall, operating voltage 15 to 32 Vdc, operating current 255mA, Alarm current 6.5 ma, addressing address, rotatory decimal switch. 8 fault isolator with accessories for isolating wire-to-wire short circuits on an notifier SLC loop mounting wall, operating voltage-15 to 32 vdc.operating current-450 μ.Α, Alarm current-17mA, temp. range-0°c-49°C, dimension-101 mm (w) x 114 mm (h) x 6 mm (d) 9 Emergency exit LED light LED with accessories, Rated voltage -24V DC housing Aluminium & Glass, Power Consumption 1 Watt Colour standard green, Serial two wire technology. Class-A, Style 6 10 Red colour 4-inch square wall mounted PVC junction boxes with cover plate and accessories, minimum depth of 2.5 inches suitable for mounting of notifier Input/output modules 1 Control cable 2C x 1.5 sq mm up to 1.1 KV, annealed tinned copper solid conductor, PVC insulation, galvanised steel wire/strip armoured, PVC inner sheath, and FRLS PVC outer sheath, outer sheath colour fire red OFC Single Mode, 6 Fibre, 9/125-micron primary coated buffers, OS2 (IEC 60793-2-50, B1.3 and ITU T G652.d). Uni-tube construction. 12 Cable type: Optical fibers in water blocked loose tube, taped, corrugated steel tape armored (STA) polyethylene (HDPE) outer sheathed embedded with two steel wires on the periphery. The cables are with UV Stabilized PE Jacket and protected from Rodent attacks. Complying to ISO/IEC 11801, EN50173, ANSI/TIA 568-C3, Telcordia GR-20; suitable for use in indoor/outdoor ducts, direct burial and backbone cabling. 13 Heat detectors, rate-anticipated with accessories.operate within a controlled range of two to three degrees of their set points. Temperature setting 194°F (90°C) ratings. Heat detector suitable for surface mounting (ex'd', iic, 13) for battery room application) Manual call points-outdoor with accessories, wall mounting with chain and hammer.protocol-flash scan, operating voltage. rating voltage-24 vdc, non-addressing; addressing through interface module, dimension- 105 mm (w) x 215 mm (h) x 115 mun Explosion proof, integral terminal chamber, Push button actuator with mushroom head, constant contact with a glass cover which activates when broken, Anti corrosive epoxy powder coated, Area classification Zone 1&2, GAS group- I, IIA, IIB, Apparatus standard -IS-2148/81, CMRI Certificate no: CMRS/TC/H167. 15 Beam detector, mounting wall, Operating voltage-20 to32 vde, Adjustment angle +/- 10 Degrees horizontal & vertical, protection range up to 100m. compatible with notifier panel. 16 Zone controller module for LHS cable and accessories, Voltage: 13-30 Vdc (2 wire Mode), Rating: IP 66, Relay Contacts 1 A @ 24 Vdc/120 Vac, One number NO+ NC for fire alarm and one NO+NC for fault condition 17 Monitor module for input signal with accessories compatible with notifier panel, mounting wall.operatingvoltage-15-32V dc. Operating current-375µa, alarm current-5ma, addressing-laddress, rotatory decimal switch, housing color white, temp.range-0°c-49°c, dimension 101mm(w)x14mm(h)x32mm(d 18 Mini monitor module with: accessories for input signal, compatible to notifier panel, mounting wall, operatingvoltage-15-32v operating current-dc. 350µa, alarm current-600µa, addressing-1 address, rotatory decimal switch, housing colorwhite, temp. range-0°c-49°C, dimension-70mm(w)x33mm(h)x16mm(d) 19 Smoke Duct detector suitable for HVAC duct application compatible with notifier panel nominal senstivity-1.79 +/- 0.84%/ft, temp range- 0 to 55 deg C, Duct air velocity air velocity 100 to 4000 FPM for fire alarm system Technical Specification for 06 Core SM Fiber Armored Cable Total Quantity : 6990
|