8304 Provision Of Automatic Fire Detection Cum Warning System For Armoury Ammunition Store Lpg Store And Two Pol Stores At Minicoy Under Ge Navy Lakshadweep-1 Supply And Fix Fire Alarm Control Panel ( Facp ) Complying With Bs En 54 Single Loop Panel Of Capacity From 99 Detectors & 99 Modules Per Loop Including Two Number Of Batteries Of 12 V Connected In Series And Including Testing, Complete All As Specified And Directed By Engineer-In-Charge. 2 Supply And Fix Addressable Manual Call Point ( Mcp ) Break Glass Type, Complete All As Specified And Directed By Engineer-In-Charge. 3 Supply And Fix Addressable Electronic Sounder Cum Strobe, Complete All As Specified And Directed By Engineer-In-Charge. 4 Supply And Fix Addressable Multi Sensor Detectors Photoelectric Optical -Heat +Smoke Composite Detector, Include B501 Base , Sleek , Low Profile Design , Removable Cover And Insect Resistant Screen For Simple Field Cleaning But , Built-In Tamper Resistant Feature, Complete All As Specified And Directed By Engineer-In-Charge. 5 Supply And Fix Fire Alarm Sounders / Sirens Electronic Type Horizontal Two Stage Continuous Normal Operation For At Least 50 Minutes With Sound Level 65 Db To 120 Db Measured At 1.5 M With Sound Output Variation Of + 5 Db 1500M Range, Complete All As Specified And Directed By Engineer-In-Charge. 6 Supply And Fix Addressable Controle Module And Testing, Complete All As Specified And Directed By Engineer-In-Charge. 7 Supply And Fix Short Circuit Isolators Between The Zones And Testing, Complete All As Specified And Directed By Engineer-In-Charge. 8 Material And Labour For Sub-Main Wiring With Multi Stranded Copper Frls Armoured Cable Copper Conductor 2 Core X1.5 Sqmm Drawn In Stove Enamelled Steel Conduit, Complete All As Specified And Directed By Engineer-In-Charge. 9 Material And Labour For Point Wiring Point Controlled By One Way 5 Amp Switch Complete With 2 Runs Of 1.5 Sqmm Single Core, Pvc Insulated, Unsheathed Cable 1100 Volts Grade, Multi Stranded Copper Conductor Drawn Into And Including Suitable Size Of Stove Enameled Steel Conduit And Accessories On Surface Of Wall / Roof Etc. And Including Provision Of One Run Of Pvc Insulated 1.5 Sqmm Copper Conductor For Earth Continuity Conductor, Complete All As Specified And Directed By Engineer-In-Charge. 10 Switch Flame Proof Rotary Type With Termination Box In Lm6, 16A, Single Pole 250V, Complete All As Specified And Directed By Engineer-In-Charge. 11 Supply And Fix Flame Proof Exhaust Fan, 300Mm Sweep, Including Cutting The Existing Wall Of Suitable Size And Making Good The Disturbed Surfaces As Per Existing Complete All As Specified And Directed By Engineer-In-Charge. 12 Supply And Fixing Led Light Fitting 1X30 Watt Flame Proof, Cmri Certified, Recommended For Gas / Vapor Group Of Iia & Iiib, Zone 1 & 2 And Ip 65 Protection With Die Cast Aluminum Housing With Heat Resistant Toughened Glass, With Led Tube Light Fixtures Driver, Holders, Connector Etc. Complete With All Accessories Prewired And Including Connecting Up With Three Core Flexible Copper Conductor Cable With Suitable Size, Complete All As Specified And Directed By Engineer-In-Charge. 13 Material And Labour For Earthing Complete With Galvanised Steel Plate Electrode 600 X 600 X 6Mm Thick Buried Directly In Ground Vertically To A Depth Not Less Than 2.25Mtr Below Ground Level With Top Edge Of Earth Plate At A Depth 1.5Mtr Below Ground Level Connected To Galvanised Earth Lead Wire 4 Mm Dia By Means Of Nuts Bolts And Washers Of Galvanized Iron Protected By 15Mm Dia Light Grade Gi Tubing, Funnel, Wire Mesh, 20Mm Bore Gi Tubing Medium Grade Watering Pipe, Including Concrete Pit In Pcc 1:3:6 Type C-1, Precast Rcc ( 1:2:4 ) Type B-1 Cover Slab Of Size 350X350x50mm Reinforced With 8Mm Dia Tmt Bars @ 15Cm C / C In Both Ways And 10Mm Dia Ms Handle Of Suitable Size, Adequate Quantity Of Charcole And Salt In Alternate Layers, Including Necessary Excavation And Earth Work In Soft / Loose Soil All As Shown In Electric Plate No. 3 Of Ssr Part-I And Testing Complete All As Specified And As Directed By Engineer In Charge. Note: On Testing After Completion If The Desired Earth Resistance Is Not Obtained The Earthing Will Be Redone At No Extra Cost.
|