Maintenance And Servicing Of Fire Fighting Equipments And Systems In Bkpl , Group A Bkpl Barauni Pump Station , Checking , Inspection , Servicing And Maintenance Of Fire Fighting System , Equipments Hydrants , Extinguishers Of All Type ( Dcp/Co2/Clean Agent ) , Water Monitor Up To The Mark As Per Oisd/Isi Standards To Provide & Best Functioning Of The Equipments Always In Best Healthy Condition Inclusive Of Periodically Cleaning , Checking /Inspection/Oiling/ Greasing Of Assemblies Such As Coupling , Nozzles , Valves , Hydrants , Extinguishers , Hose Pipes , Water Monitor , Compounds Drums , Nozzles Foam Bunch , Hose Boxes , Sand Buckets Etc , Updating The Data & Identification Tags , Recording The Status Of Checking In History Register Etc . As Directed By The Engineers In Charge With All Labors , Carriages , Materials Etc . Complete Inclusive Of All Taxes . ( Inspection And Servicing Of The Equipment/Fire Fighting Facilities Is To Be Done Periodically As Mentioned Against Each ) :- , Fire Hydrants ( Double Headed ) On Monthly Basis , Fire Extinguishers Of All Types & Capacities On Monthly Basis , Hose Boxes - Monthly Basis , Valves Of Fire Line Of All Sizes Including Contractor Supplied Grease Of Suitable Quality On Monthly Basis . , Foam /Water Monitors On Monthly Basis/Mefg , Sand Buckets With Stands With All Bucket On Monthly Basis , Taking Delivery And Refilling The Extinguishers Of Various Sizes /Capabilities Including Supply Of Dry Chemical Powder , Co2 Gas Etc Updating The Data & Identification Tags , Recording The Status Of Checking In History Register Etc As Per Isi Standard And Replacing The Same As Directed By Engineer-In-Charge . ( The Co2 Cylinder May To Be Taken Out And Delivered Back Within 10 Days After Re-Filling /Repairing . However Fire Extinguishers Co2 Are To Be Supplied /Kept Temporary In Place Of Each Fire Extinguisher For Which Taking Out For Re-Filling /Repairing Is Required ) . , Dry Chemical Powder , 0 . 2 Kg Dcp Cartridge , 2 Kg Co2 Cylinder , 6 . 8 Kg Co2 Cylinder , 2Kg Clean Agent Cylinder , Supply And Replacing The Spares /Assembles Etc Of The Fire Fighting Equipments System For All Sizes / Capacities As Per Isi Standard And Approved Make With All Labours , Materials , Carriages , Inclusive Of All Taxes Etc . Complete , Supply And Installation Of Clear Pvc , Spiral Wound Hose ( Pick-Up Tube ) Of Length 3 M Length And Dia 40 Mm With Ss Jublee Clamp For Tightningsuitable For Existing Connectors Of 750 Gpm Monitor , Hydrants Sheet Washer/Rubber Including Fitting At Site . , Hydrants Coupling Washer , Rubber Washer For Extinguisher , Co2 Safety Valves 155Kgf/Cm2 , Co2 Safety Pins , Isi Marked Discharge Pipe With Horn For 2Kg , 3 . 2Kg , 4 . 5Kg Co2extinguishers , Isi Marked Discharge Pipe With Horn For 6 . 5 Kg And 6 . 8Kg Co2 Exitinguishers . , Rubber Gasket Of Dcp Main Cap , Hose Plunger Set & Nut . , Hose Spring & Nut , Dcp Main Cap ( Gun Metal ) Cp , Dcp Plunger Pin With Spring , Dcp Plunger Top , Squeezing Grip ( Plastic ) Nozzle , Replacement Of Fire Hose Box Glass ( Front ) , Dcp Cylinder Discharge Pipe Of Sufficient Length For 10 Kg Capacity Fire Extinguisher , Dcp Cylinder Discharge Pipe Of Sufficient Length For 75 Kg Capacity Fire Extinguisher , Supply And Fitting Of Plastic Blank Cap ( As Per Is 5290 , Red Colourwith Gi Chain ) Suitable For 63 Mm Hydrant Outlet As Per Direction Of Eic , Supply And Painting With Two Coats Synthetic Enamel Paint ( Asian/Burger ) Fire Paint Including Scrapping , Cleaning , Applying One Coat Of Red Oxide Primer Cost Of All Labours , Materials , Carriage , Taxes , Letter/Number Writing , Identification Marks Etc . Complete In All Respect . , Brush Painting Of Fire Hose Boxes ( Inside And Out Side ) Including Stand With Two Coat Of Paint Including Letter/Number Writing ( Colour To Be Specified By Eic ) , Spray/Brush Painting Of Fire Bucket Stand With Its Buckets ( 4-6 Bucket Set ) Including Letter/Number Writing . , Spray Painiting Of Fire Extinguishers Of All Sizes Including Letter/Number Writing . , Spray/ Brush Painting Of Foam/Water Monitors/Double Hydrant Valves Along With Its Stand Post Including Letter/Number Writing . , Fire Siren Including Letter / Number Writing . , Others , Ppe Maintenance / Up-Keeping / Cleaning On Monthly Basis Of Various Items Like Helmets , Breathing Apparatus , Water Jel Blanket , Asbestos Blanket , Hand Gloves ( Rubber / Asbestos ) , First-Aid Box , Stretcher , Resuscicator , Safety Belt , Ear-Muffs , Fire Proximity Suits , Safety Torch , Safety Goggles Including The Cost Of Labour , Material Etc . Complete As Per Instruction Of Engineer-In-Charge . , Cleaning & Stacking Properly The Foam Containers , Updating Stock , Date Of Expiry , Date Of Manufacturing On Board And In Register , Placing Foam Containers At The Foam Monitors And Water Hydrants . , Taking Hose Pipe For Hydrotesting And Keeping It Back In Positionafter Drying /Rolling Inclusive Of All Taxes . , Air Filling In Cylinders Of Breathing Apparatus Inclusive Of All Cost With Transportation . , Hydraulic Testing Of Co2 Cylinders Inclusive Of All Taxes ( 2 To 4 . 5 Kg/Cm2 ) , Hydraulic Testing Of Co2 Cylinders Inclusive Of All Taxes ( 6 . 8 Kg/Cm2 ) , Hydraulic Testing Of Dcp Cylinders Of All Sizes Inclusive Of All Taxes , Hydraulic Testing Of Breathing Appratus Set , Supply & Pasting Of Slips On The Extinguishers Showing How To Use The Extinguishers & Date Wise Maintenance Records Of Fire Extingusher . The Good Quality Of Adehsive To Be Used On Slips For Sticking On The Extinguishers Inclusive Of All Taxes As Per Direction Of Engineer-In-Charge . , Supply And Fixing Of Wind Socks On The Position Including All Labour , Tolls And Tackels As Per Direction Of Engineer-In-Charge Inclusive Of All . , Patch Work Welding On The Firefighting/Foam Line In Case Of Leakage Including All Manpower & Materials With Tools And Tackels With Materials Required As Per Satisfaction Of The Engieer-In-Charge Upto 12X12 Size Inclusive Of All . , First Aid Box With Snake Serum , Fire Bucket , Safety Helmet , Lettering With Black Japan Paint Of Approved Brand And Manufacture . ( Note: Unit Ea Shall Mean Per Letter Per Cm Height ) . , Supply & Fitting Of Transparent Acrylic Sheet Thickness 3 Mm Of Hose Box Inclusive Of Rubber Beeding By Fixing It With Proper Adhesive Wherever Required Complete In All Respect Inclusive Of Material , Labours , Consumables Etc . ( Inclusive Of Rates For Both Glasses And Rubber Beading . , Complete Overhauling Of Hand Operated Siren Including Oiling , Greasing , Painting And Testing As Per Direction Of Eic Inclusive Of All Tools & Tackles , Transportation , Man-Power Etc , Testing Of Afff As Per Bis:4989 From Reputed Institutes Like Girda Or Any Other Approved Laboratory In All Respect By Providing Cas , Transportation , Man Power Etc . , Maintenance And Calibration Of Multigas Detector Sensor ( Lel , O2 , Co , H2s ) The Charges Includes Cost Ofcalibrating Canisters Inspection , Maintenence Of The Detectors And Issuance Of The Calibration Certificates The Cost Of Sending Lel Meterto The Party Workshop ( In India ) Will Be In The Scope Of Iocl But After Calibraiton And Completion Of Work Thecost Of Transportation Of Lel Meter To Iocl Installation Shall Be In Thescope Of Vendor . Rate Are For Calibration Of All Sensor , Make: M/S Respo Products Model: Qrae Ii , , Make: Bw ( Honeywell ) Model: Gasalertmax X , Fire Water Line , Dismantling Of Gate Valves Of Sizes Up To 8 Of Fire Hydrant Line E Etc From Bonnet Cleaning And Lapping The Gate And Refixing It With New Gasket ( Iocl Supplied ) Alongwith All Tools , Tackles , Material , Manpower Etc , Removal And Installation Of Of Faulty Gate Valves/Nrv/Glove Valve/Strainer Upto 8 Inch Size Including Transportation Either From Owners Storage Point To Workshop Or Work Sit
|