Tender For Water Supply Scheme For Augmentation Of Uwss Kushalgarh District Banswara Including 05 Years Om After 01 Year Of Defect Liability Period Under Amrut 2, Water Supply Scheme for Augmentation of UWSS Kushalgarh, District Banswara including 05 years O&M after 01 year of Defect Liability Period under AMRUT 2.0 Sl. No. Item Description 1 Providing, lowering, laying in trenches, aligning, fixing in position and jointing Ductile Iron (DI) ISI marked K-7 grade S&S pipes as per IS:8329-2000 (amended up to date), with internal cement mortar lining suitable for potable water with rubber ring (EPDM) joints as per IS: 5382-1985 including all taxes (Central and local), transportation and freight charges, inspection charges, loading/ unloading charges, including cost of labour and material, specials (Tee, bend etc.) satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge. (excluding earth work)Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item andshall not be paid separately. 2 100 mm 3 150 mm 4 200 mm 5 Providing, lowering, laying and jointing in trenches, standardlengths HDPE ISI marked Pipes as per IS-4984: 1995 (amended up to date) with necessary jointing material like mechanical connectors, i.e. thread/ insert joint/ quick release coupler joint/ compression fitting joint or flanged joint and specials jointing pipe by electro fusion welding method, including all taxes , transportation and freight charges, inspection charges, loading/ unloading charges, stacking of pipes, including cost of labour and material, specials (Tee, bend etc.), satisfactory hydraulic testing,disinfection, commissioning etc. complete as per technicalspecifications and direction of Engineer-in-charge of following classand diameter. (excluding earth work) .Note : Providing and fixing of all requisite specials as per drawing,design and layout are inclusive in RM measurement of the item andshall not be paid separately.Supply may be in coil or straight length in 6 M/12 M. 6 HDPE PE-100PN-6 7 90 mm 8 Fabrication, supply of flanged/ plain ended MS pipe made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete (excluding flanged jointing wherever required) including all material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer.Note : E/w to be measured and paid separately. 9 MS pipe specials upto 600mm dia (with minimum 5mm thickness sheet) 10 Providing Household Tap Connection as per technical specification andapproved drawing as per relevant IS code (amended up to date) fromHDPE/uPVC/DI/AC/MS/GI pipe line up to consumer meter/premisesby using PP mechanical Integrated saddle with inbuilt flow controlvalve made out of SS316 designed for 5 LPM discharge at 0.5 barpressure , not exceeding the flow of 7 LPM at 2 bar and acompression elbow, moulded in single piece/ fusion welded(Complete job) including digging out suitable size of pits and trench forlaying service line in all kinds of soil; depositing and refilling of pit &jhiri with watering & ramming /compacting in layers and disposal ofsurplus excavated soil as directed with in a lead of 100 meter ;providing & fixing of all fitting duly approved in accordance withspecification for potable water including GM Full-way Valve (IS:778Mark) or wheel valve and specials with 20 mm nominal dia MDPE pipePE 80 PN 16 as per ISO 4427 / 20 mm nominal dia PPR-C (Threelayered) pipe PN16 SDR 7.4 (IS:15801:2008) (ISI mark) and aboveground level using PPR-C pipe with standard PPR fittings/ GI pipes inthe premises for fixing a tap / meter box (excluding) ,including accessories with flushing, cleaning, disinfecting and testing of pipe linecomplete required for making of service connection complete in allrespect including labour charges . The service line should be laid atleast 45 cm below ground level.Note: Road cut and restoration is not part of this item and paidseparately. 11 For connection with 20 mm dia MDPE/PPR-C pipe length up to 05 mtr. 12 Road cutting for house hold service connection in minimum trench width wherever road crossing is required. Road cutting of cement concrete,WBM, Black top etc. of all thickness shall be done by using a concrete cutter machine keeping minimum trench width and restoration of the road with Cement concrete with PCC M-10 and CCM-30 grade as per specification and direction of Engineer in charge.. 13 Add extra over item no 1.21, 1.22 & 1.23 for providing 20 mm PE 80 PN 16 as per ISO 4427 MDPE pipe including excavation, providing, laying & jointing of service line above 5.00 mtr. 14 Supply & Fixing of ISI marked three core PVC flat submersible cableas per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980 including making connection etc. 15 3 core 16.0 Sq.mm 16 Supply & Fixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade withaluminium conductor Armoured of IS:7098-I/1554-1 approved make in groundas per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thickunder layer of sand, second Class bricks covering, refilling earth, compactionof earth, making necessary connection, testing etc. as required of size. 17 Armoured Cable16.0 Sq. mm 4 core 18 Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I."B" class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size 300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance asrequired. 19 Providing & Lowering in tube well ISI marked GI Pipe medium duty (“B" class),Steel tube as per IS:1239 or amended up to date and zinc coating as per IS4736, threaded and double flanged (welded) on both ends and two number25x3mm MS flat welded on both ends between pipe & flange, rubber washer &nut bolts etc. complete in all respect. 20 65 mm dia 21 Construction and commissioning of RCC INTZE type Over Head Service Reservoir of following capacity and staging as per the Scope of work and Technical specifications, consisting of the following main activities: -a) Topographic survey, preparation of site contour plan, conducting SBC testand its approval from departmentbefore construction. Submission and approval of concrete mix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation, all RCC Work, Plinth protection all around the structure including all material, labour, shuttering, scaffolding etc.c) OHSR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the edge of outer most projection of OHSR.The plinth protection shall consist of 150mm thick PCC in M-15 grade concrete laid over 150mm thick layer of compacted soil.d) Providing and applying two coats of food grade epoxy paint on the inside surface on the top dome, edge beam and 600 mm height of the vertical wall.e)Conducting successfully hydro test and water tightness test as per I.S. code.f) Providing and applying three coats of anti-carbonation paint on the top surface of the Top Dome.g) Providing and applying three coats of cement-based paint on the external surface of the container, balcony, cone wall, columns & beams etc..h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS-304 ladder from top dome/Slab to bottom dome/Slab inside container. i) Providing and fixing of MS section ladder from the last landing to balcony having railing all around it and MS ladder with safety cage from balcony to top dome/slab.j) Providing and fixing water level indicator (float type).k) Providing and fixing of hand railing all around the balcony, top dome and staircase consisting of 25mm diameter Class-B GI pipe in two rows and 1000 mm high, 50X50X6mm angle iron vertical post at a maximum spacing of 1500mm centres.l) All MS parts to be painted with two coats of the enamel paint over the primer coat of red oxide.m) Providing and fixing of 150mm wide PVC water bar for the construction joints in the container (vertical wall & cone wall).n) Providing one Aluminium portable ladder of appropriate length to access first landing (3.5 to 4.5m above GL) from ground.o) Lighting arrestor consisting of providing and fixing of 2 Nos.of chemical earthing and connecting it to the conical cover of SS ventilator with two separate GI strips of 50mmX3mm.p) CI/DI puddle collar shall be fixed in the bottom dome/ slab for connecting inlet, outlet, overflow and washout pipe of the reservoir.q) Painting the name of the scheme and other details on the reservoir, and any other work related to structure as per the directions of Engineer-in- Charge, Technical Specification and Scope of Work.r) Inlet, outlet, overflow, washout pipes and valves are not included in this work, provision for the same shall be taken separately. 22 Rates for RCC OHSR,SBC 10 T/sqm, SEISMIC ZONE-II & STAGING 18 M 23 400 KL 24 Construction of RCC (Flat slab type) Clear Water Reservoir of following capacity as per the Scope of work and Technical specification, consisting of the following main activities: -a) Topographic survey, preparation of site contour plan, conducting SBC test and its approval from department before construction. Submission and approval of concrete mix design and water quality test report for water to be used in construction. b) Excavation in all types of soil, PCC below foundation & all RCC Work including all labour and material charges including providing and fixing of accessories such as SS ladder, SS manhole frame and covers, water level indicator (float type), SS ventilator with SS screen, float valve, puddle collars, G.I. pipe railing around walk way, Top Dome/Slab, Staircase. c) CWR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the vertical wall of CWR. The plinth protection shall consist of 150mm thick PCC in M-15 concrete over 150mm thick compacted soll fill.d) Providing and applying two coats of food grade epoxy paint on the inside surface of the roof slab, and 600 mm height of the vertical wall.e) Successful hydro test and water tightness test as per 1.S. code.f) Providing and applying three coats of anti-carbonation paint on the roof Slab. g) Providing and applying three coats of cement-based paint on the remaining external surface area of the structure.h) Providing and fixing SS-304 ventilator, 55 304 manhole frame and cover and 55 304 ladder from roof slab to bottom Slab, inside container. Providing and fixing water level indicator (Float type).i) Providing and fixing MS ladder from ground to top slab.j) All MS parts to be painted with two coats of the enamelled paint over the primer coat of red oxide. k) Providing and fixing of 150mm wide water bar for the construction joints in the container.l) Providing and fixing CI/DI puddle collars the vertical wall for connecting inlet, outlet, overflow and washout pipes of the reservoir.m) Inlet, outlet, overflow, washout pipes and valves are not included in this work, provision for the same shall be taken separately. 25 Rates for RCC Partially Underground type clear water reservoir SBC 7 T/sqm, SEISMIC ZONE-2,3 & 4 26 150 KL 27 Providing and fixing double flanged ISI marked DI Class K-9 pipes as per IS:8329-2000 (amended up to date), as vertical pipes for RCC Reservoirs including specials required suchas duck foot bend, bend, tee etc. providing and fixing clamps at every 3 mtr, jointing materials such as nuts, bolt, rubber packing, hydraulic testing etc. complete in all respect up to and from valve chamber as per direction of EIC, Technical Specification and Scope ofwork. 28 For OHSR 29 100 mm 30 200 mm 31 Providing and fixing double flanged ISI marked DI Class K-9 pipes as per IS:8329-2000 (amended up to date), as vertical pipes for RCC Reservoirs including specials required suchas duck foot bend, bend, tee etc. providing and fixing clamps at every 3 mtr, jointing materials such as nuts, bolt, rubber packing, hydraulic testing etc. complete in all respect up to and from valve chamber as per direction of EIC, Technical Specification and Scope ofwork. 32 For OHSR 33 200 mm 34 Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipeline including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth includingconsolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc.:All kinds of soil 35 In All Typeof Soil 36 Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming ofbottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth includingconsolidating each deposited layer by ramming, watering etc. and stacking serviceable material for measurements and disposal of unserviceable material as directed, with in a lead of 50 Mtr. including all safety provisions required . 37 Ordinary rock 38 Hard rock(blasting prohibited) 39 Dismantling of cement concrete pavement for pipe line and chambers by mechanical means using pneumatic tools, cutting the peripheral edge by CCcutter, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000meters. Measurement for dismantled trench to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, re-handling of material/earth to complete the tasks as per technical specification and scope of work. 40 Dismantling of flexible pavements and disposal of dismantled materials up to a lead of 50 metres as directed by Engineer. 41 Bituminous courses 42 Granular courses 43 Providing and laying in position cement concrete M10 grade nominal mix 1:3:6 (1 Cement : 3coarse sand : 6 graded stone aggregate 40 mm nominal size) in base course complete including all material, labour, machinery, lighting,guarding for road restoration work in trenches of pipe line and chamber work. Measurement for CC work to be made as per standard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified, complete work as per technical specification and scope of work. 44 Providingand laying in position cementconcrete in specified gradeover prepared base course complete including finishing, curing, all material, labour, machinery, lighting, guarding for road restoration work in trenches of pipe line andchamberwork.MeasurementforCCworktobemade asperstandard trench width specified in tender document and no extra payment shall be made be made for trench width more than specified,complete work as per technical specification and scope of work. 45 M20 grade Nominal Mix1: 1.5: 3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20mm nominal size). 46 Providing, installation, testing and commissioning of Centrifugal Monoblockpump set conforming to IS 9079 , 2 pole motor operating at synchronisedspeed of 3000 RPM with requisite MOC impeller, priming funnel, cock,suitable flanges at suction and delivery side. Pump shall have common shaftfor pump and motor. Motor shall be suitable for working on 415 V ± 10%, 3Ph, 50 Hz A.C. Supply. Motor shall be TEFC type and Pump set shall besuitable for working at various discharge and head requirements as perscope of work. Pump shall be erected on C.C. foundation / cross channels /RSJ frame block with suitable foundation bolts grouted in C.C. foundationblock etc. complete in all respect as per specification, scope of work anddirection of Engineer in Charge of following power rating, suitable forprescribed duty conditions mentioned in TD. 47 Centrifugal Monoblock Pump set (Single Stage) 48 11.0 KW (15 HP) 49 Providing, installation, testing and commissioning of submersible Monoblock pump set conforming to IS 8034 and 2 pole motor operating atsynchronised speed of speed 3000 RPM, with water proof winding. Pumpshall be suitable for various delivery head and discharge with stainless steelshaft. Motor suitable for working on 415 V ± 10%, 3 Ph, 50 Hz AC and withwater lubricated bearing to accept entire hydraulic thrust. Supply, with cableguard, thrust carbon/fibre bearing to withstand entire hydraulic thrust. Thepump set shall be suitable for direct coupling, with suitable suction strainer.Pump should have suitable discharge out let as per manufacturer"s design.Antithrust stream lined non return valve shall be provided with the pumpand minimum 6 m submersible copper conductor cable in single / doublerun and 2 pairs of suitable size erection clamp 10 mm thick shall be providedwith each pump etc. complete in all respect as per specification, scope ofwork and direction of Engineer in Charge of following posion : Less than 1.6mm Variation in thickness: Less than 3.2 mm) 50 submersibleMonoblock Pump set (Single Stage) 51 15.0 KW (20.0 HP) 52 Providing,lowering, aligning,fixingin positionin pipeline,CID/FSluicevalvesstraight and pocket less body passage of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200Stem - AISI- 410 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS, Face to face dimensions as per IS 14846/2000 (amended up to date) ,Epoxy ( Non-Toxic- suitable for drinking water) applied inside and outside,Flanges Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steelInsertion rubber of black EPDM 6mm thick . Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. 53 Manually Operated CI Sluice valve of Class PN-1.0 54 100 mm HW 55 200 mm HW 56 Providing, lowering, aligning, fixing in position and Jointing in pipe line, CI Double Acting Kinetic Air Valve with isolating Sluice Valve of approved makes for following pressure rating & dia complete, confirming to IS: 14845-2000 (amendedup to date) and of following specifications: Body , Cover and Cowl - Grey Cast Iron as per IS:210- FG 200 ,Float - Stainless Steel AISI 304 / IS: 3444 , Float GuideHBT1.HP Orifice- HTB2/ SS,Body seat ring - Leaded tin bronze/ SS .Seal ring and face ring - EPDM/NBR ,Ends flanged according to IS 6418,Fastners - CS, Epoxy paint inside outside of food grade safe for drinking water ,Valves including all material,labour, testing and commissioning as per Technical Specifications and as per direction of Engineer in charge.Note: Rates are exclusive of connecting tee, pipe piece and earth work. 57 Class PN 1.0 58 40 mm 59 50 mm 60 Providing, lowering, aligning, fixing in position in pipe line at work site, DI D/F Resilient seated (soft seated) Sluice Valves (Gate Valves) , Vacuum tight(bubble tight), straight and pocket less body passage of approved make of following class & dia complete confirming to BS-EN-1171/ AWWA C-509 and of following specifications: Body & bonnet of Ductile cast iron of grade GGG40/GGG50 as per DIN 1693 or GR SG-400/12 as per IS 1865 or equivalent grade as per IS :3896-part2-1985 and subsequent revisions, Wedge of same material as body & shall vulcanisedrubber lined with EPDM (food grade quality) and seals of NBR Face to face dimensions as per BS 5163-89/ IS 14846/2000 (amended up to date) /Din 3202 F4, Stem/ spindle of SS AISI 316/410 Electrostatic epoxy powder(EP-P)/ Fusion bond epoxy ( Non-Toxic- suitable for drinking water) coated with minimum thickness of 250 microns inside and outside, Drilled as per IS 1538. Nut-Bolt confirming to IS:1363 and IS: 1367(Galvanised steel) Insertion rubber of black EPDM 6mm thick. Suitablesupport structure as per directions of EIC, Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. 61 Manually Operated Resilient Seated Sluice Valves of Class PN 1.6 62 100 mm 63 150 mm 64 200 mm 65 Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (Suitable for Sluice valves etc.) as per IS specificationscompleteofthefollowingsizesincludingall jointing material,costofalllabour,testingandcommissioning Technical Specifications and as per direction of Engineer. Class PN 1.0 66 100 mm dia. 67 150 mm dia. 68 200 mm dia. 69 SITCSTAR DELTA Starter type LT Panel of followingrating:all switchgears are of PHED approved makes, CRCA sheet of Panel enclosure is of TATA/ Essar 1.6mm/ 2.0mm thick duly Electrostatic Powder Coated withangleframeincludingotherancillaries(Insulators, AcrylicSheet , Backlight Sheet, Hardware, Wire, Name Plates, Lugs, Pvc Channel , Mcb Chanel , Lock, Hing , Bidding , Connectors, Neutral Links , Spiral , Saddle & Packing Material ) etc. and 100A/ 125A ,TPN, Aluminium Bus Bar with Colour coated heat shrinkage sleeves complete as per Technical Specifications and as per direction of Engineer-In-Charge. 70 STAR DELTA STARTER 11.0 KW (15.0 HP)- :For 2 motors (1 W+ 1S)I/C -MCB 63A ,FP, 10 KA, C Curve (1) , Analog Voltmeter 96*96mm ( 0- 500V ) (1), Volt Selector Switch (1) , Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 60/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue - 1 ) (1), Control MCB 6A SP 10 KA C Curve (3) andO/G-MCB 40A ,TP, 10 KA, C Curve (2), Power Cont 25A TP AC3 Duty(2),2NO+2NCAux.Block(2),ThermalOverloadRelay(9-13A)(2),Control MCB6ASP10KACCurve(2),SinglePhasePreventer(2),Indicating Lights (Red- 1, Green - 1, Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 7.5Kvar (2), S/D Timer(2) 71 STARDELTASTARTER 15.0KW (20.0HP) : For2motors(1W+ 1S)I/C- MCCB 100A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (1),Spreaders (2),Extended Rotary Handle (1) , Analog Voltmeter96*96mm(0-500V)(1),VoltSelectorSwitch(1),Analog Ammeter 96*96mm ( 0-60A ) (1), Amp. Selector Switch (1), C. T. 100/5A CL 1.0 5VA (3) , Indicating Lights ( Red-1, Yellow -1) (2), Indicating Lights ( Blue-1)(1),ControlMCB6ASP10KACCurve(3) andO/G-MCCB 63A TPN 25 KA With T/M Based Over Current & Short Circuit Protection (2), Power Cont 32A TP AC3 Duty(2), 2 NO+2 NC Aux. Block(2), Thermal Overload Relay (12-18A )(2), Control MCB 6A SP 10 KA C Curve (2),SinglePhasePreventer(2),IndicatingLights(Red-1,Green-1,Amber-1)(6), Push Button 22.5 ( Red - 1, Green - 1 )(4), Selector Switch 1 Pole, 2 Way (2), Capacitor 440VAC Heavy Duty MPP Type 7.5Kvar (2), S/DTimer(2) 72 Construction of boundary wall of Brick/ stone masonry as per enclosed GAdrawing, scope of work and technical specifications complete work in allrespect. Brief details of boundary wall parameter is as below:1. Depth of foundation- 900 mm.2. PCC in M-10, width -900 mm and thickness 100 mm,3. Stone masonry in CM: 1:6 section of foundation above PCC, 600mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D)4. Superstructure work: Stone masonry in CM: 1:6, W-300, height-1650mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm.5. Cement mortar pointing on Stone masonry and cement mortar plaster20 mm thick on brick masonry in CM 1:6.6. Expansion joint shall be on every 30 mtr.7. On top of wall there shall be CC Coping 75 mm thick (1:2:4) shall beprovided.8. Pillar for main gate 350x350 mm in size is part of boundary wall.9. Cement paint of approved colour in 3 coat shall be done. 73 Providing and fixing steel, gate, grating and grills made of angles, tees,square bars, flats or black pipe with hold fast and fitting complete as perdesign and drawing including cutting welding and fabrication with primingcoat of red oxide and two coat of enamel paints. 74 Construction of Pump house of RCC framed structure with pump pit in RCCwalls as per scope of work and technical specification complete work in allrespect including electrical works for indoor and outdoor lighting and fans,rain water drainage, sanitary, plumbing, monorail/ EOT crane etc. completeas per direction of Engineer-in-charge. The GA, structure, electrical,sanitary, P&ID, SLD to be prepared by the contractor and submitted todepartment for approval for earth quake zone II. 75 Pump House with Monorail arrangement 76 ConstructionofRCCSluicevalvechamberfordifferenttypeofvalves includingearthworkexcavation,100mmPCCM15 aslevellingcourse, RCC M25 grade for base slab, side wall & cover slab , including cost of steelreinforcement,formwork,Pre-castslabs,plasticencapsulated CI/MS Foot Rest, MS flats for the support of pre-cast, proper curing of concrete work complete in all respect as perspecifications and standard drawings and as per direction of Engineer-in-Charge. 77 For Class-A loading 78 Sluice valve chamber of size1.13m x0.85m x1.27mfor pipe size-upto100mm 79 Sluice valve chamber of size1.17m x0.95m x1.415mfor pipe size-from 125-to-150mm 80 Sluice valve chamber of size1.26m x1.185m x1.82mfor pipe size-from 200-to-300mm 81 Construction of RCC Air valve chamber for different type of valvesincluding earthwork excavation, 100mm PCC M15 as levelling course,RCC M25 grade for base slab, side wall & cover slab , including cost ofsteel reinforcement , form work, Pre-cast slabs, Plastic encapsulatedCI/MS Foot Rest, MS flats for the support of pre-cast, proper curing ofconcrete work complete in all respect as per specifications andstandard drawings and as per direction of Engineer-in-Charge. 82 Air valve chamber of size0.9m x1m x1.695mfor air valve size-from 50 mm-to-80mm 83 SITC of Bulk Flow Meter with removable mechanism class "B" confirming to ISO:4064:2005/ IS: 2373of approved make of following dia sized pipelines andspecificationscomplete: Media:Water(Clear),Temp.50deg.,Pr. rating:PN16,Protectiontype:IP-68, BodyMaterial:IS-210Gr.FG-200, AccuracyClass:ClassB(±2%@Nominalflowrate),MagneticDrive, Dry Dial, Epoxy powder coated, Pulse out put option, Anti-magnetic protection including all materials and making connection with existing pipeline required for Bulk Flow Meter including cutting the existing pipeline etc. complete in all respect as per technical specification and as per direction of Engineer In- Charge.Note: Rates are exclusive of tail piece / dismantling joints and earth work. 84 BFM 200 mm 85 Design, construction, commissioning & testing of Non Mechanical RapidGravity Filter Plant of capacity as under. This work includes constructionof RCC receiving chamber, baffle channel, flocculate, clarifier, collectingchannel, filter beds , operation gallery, clear water chamber, channel,chlorination chamber, Back wash tank, pipe system for carrying rawwater from Pump House to inlet of RGF, clear water from Plant to CWR,De-sludging system including providing pipe system from clarifier ,flocculate & back wash water chamber to existing storage tank, overhead back wash tank, back wash pumps (1W+1S) set with piping system,air blowers (1W+1S) as per design, interconnection of raw water, clearwater, sludge pipes etc. including allied works such for construction,commissioning of system as defined in scope of work, technicalspecifications and provisions of CPHEEO manual at various water supplyschemes 86 Up to 40 KLH capacity 87 Providing, laying, spreading and compacting of granular sub-base by providing close graded Material, mixing in a mechanical mix plant atOMC, carriage of mixed Material to work site, spreading in uniformlayers with motor grader on prepared surface and compacting withvibratory power roller to achieve the desired density, complete asper MoRT&H specification clause - 401 including all material, labour,machinery, lighting, guarding and maintenance of diversion.Grading - I Material 88 Providing, laying, spreading (with paver finisher only) andcompacting wet mix macadam (WMM) base course comprising ofgraded stone aggregate and granular material conforming toMORT&H specifications (Table 400-II) in layers of equal compactedthickness each consolidated, including pre-mixing the material withwater at OMC in mechanical mixer (Pug Mill), carriage of mixedmaterial by tippers to site, laying in uniform layers in base course ona well prepared sub-base/ base course and compacting with powervibratory-roller to achieve the desired density complete as perMoRT&H specification clause - 406 including all material, labour,machinery, lighting, guarding and maintenance of diversion. 89 Providing and applying primer coat over prepared surface of granular base with bitumen emulsion as per IS : 8887 and approved quality @ 0.6 kg/sqm with the help of spray set fitted on bitumen Container (boiler) after cleaning the surface including removing of binding material and other foreign matter with wire brushes and small picks, sweeping with brooms or soft brushes and finally dusting with old gunny bags and compressed air to receive bituminous treatment complete as per clause 502 of MoRT&H specification including all material, labour, machinery, lighting, guarding and maintenance of diversion. 90 Extra for additional bitumen emulsion used in above item for every 1 kg per 10 sqm 91 Providing and laying open graded premix carpet 20mm thick (compacted), on prepared surface in a single course as wearing course, composed of specified graded crushed stone aggregate as per Table 500-23, premixed with bituminous binder @ 14.60 kg/ 10sqm (including Cost of anti-stripping compound Minimum 1% in Lime/Cement as per design wherever required), including loading of material with F.E. loader, hot mixing of stone aggregate and bitumen in computerised hot mix plant, transporting the mixed material by tippers to paver and laying with paver finisher fitted with electronic sensor control to the required level and grade, compacting smooth wheeled roller 8-10 tonne capacity and finishing to required level to achieve the desired density as per clause 511 of MoRT&H specification including all material, labour, machinery, lighting, guarding and maintenance of diversion but excluding cost of tack coat/ seal coat. 92 With Bitumen VG-grade 30 93 Providing laying and consolidation Semi Dense Bituminous Concrete, as per Design Mix (approved by Engineer), on prepared surface with specified graded crushed aggregates as per table 500-15 for wearing coarse including loading of material with F.E. loader, hot mixing of stone aggregate, filler and bitumen (including Cost of anti-stripping compound Minimum 1% in Lime/Cement as per design wherever required) heating and mixing in in computerised hot mix plant, transporting the mixed material by tippers to paver and laying with paver finisher fitted with electronic sensor control to the required level and grade, compacting by power rollers and vibratory rollers or 150 to 250 KN pneumatic tyred roller with TP = 0.7 Mpa, to achieve the desired density (approximately 2.3 tonne/cum) complete as per clause 508 of MoRT&H specification including all material, labour, machinery, lighting, guarding and maintenance of diversion but excluding primer/tack coat. 94 25-30 mm compacted thickness (Grade-2) using Bitumen VG-grade 30 @ 5% (percent by weight of total mix) 95 Bored cast-in-situ R.C.C. pile with cutting / Drilling for anchoring of pile into rocks wherever firm rocky strata is available, shall be done upto desired depth (minimum 1.50 m) as per drawings, specifications and as directed by Engineer. Bore hole shall be cleaned properly before concreting. No, distinction shall be made for penetration through hard rock or rock socketing with design mix concrete (M-35) using batching plant, transit mixer and concrete pump excluding reinforcement complete as per drawing and technical specifications and removal of excavated earth with all lifts and lead upto 1000 m. as per clause 1100, 1600 & 1700 of MoRT&H Specification including all material, labour and machinery. 96 450mm dia pile 97 Providing, installation, testing and commissioning of Diaphragm Type Pressure Gauges Dial size 150 mm glycerin filled shatterproof glass, Over range protection: 125% of maximum pressure, Material of sensor and other wetted parts: SS type 316, Housing material: Die cast aluminum 98 Filling available excavated earth (excluding rock) in trenches, plinth side of foundation etc. in layers not exceeding 20 cm. in depth, consolidating each deposited layer by ramming and watering including lead up to 50 meter and with all lift. 99 Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level. 100 M10 grade Nominal Mix 1: 3: 6 (1 cement : 3 coarse sand : 6 graded stoneaggregate 20mm nominal size). 101 Supporting block of size 2m, 1.2m 102 For height 10m 103 Providing and laying in position specified grade ofcement concrete forall RCC structural elements upto plinth level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement. M20 grade Nominal Mix / Design Mix 104 Providing M-30 grade concrete by usingcement as per codal provision instead ofM-20 grade design mix. 105 Centering and Shuttering with plywood or steel sheets including strutting, propping bracing both ways and removal of formwork for foundation , footings,strap beam, raft , bases of columns etc. 106 Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates,anchorblocks,sills,chhajjas,lintel,beam, plinth beam etc. 107 Columns, pillars, posts and struts etc. 108 Structural steel work riveted,bolted or welded in built up sections, trusses and framed work, including cutting, hoisting (height upto 10 m) , fixing in position and applying a priming coat of approved steel primer all complete: 109 Cost for Basic Service Charges, Administration and Management, Running of Operation, Maintenance and Repairs including Preventive Maintenance, Cost of material required for maintenance & repairs, Cost of Lubricants, Consumables, Spare Parts (if the spare parts supplied to PHED are used in emergency)as per Scope of Work & terms & conditions of contract for 05 year after defect laibility period of one year DLP (except power feeder, IEC & miscllenous provision) for Water Supply Project 110 1st year 111 2nd year 112 3rd year 113 4th year 114 5th year
|