Supply, Erection, Testing, And Commissioning Of Equipment And Materials On Epc Basis Excluding Civil Works At 66/11Kv Kotarpur Ais Under Rdss Scheme-A Supply and Erection of 66kV Equipments considering 25mm/kV creepage (as per respective technical specifications and relevant special conditions) suitable for Single Main Bus scheme with Single Zebra conductor 1-a Surge Arrester 60kV, 10kA, Designation-SM with structure and clamp connectors (suitable to Single Zebra conductor) as per technical specifications 1-b Surge Arrester 60kV, 10kA, Designation-SM with structure & cable support arrangement and clamp connectors (suitable to Single Zebra conductor) as per technical specifications 2 PT 66kV/v3-/110V/v3-2C with structure and clamp connectors (suitable for Single Zebra Cond.) as per technical specifications 3 BPI 4kN with structure and clamp connectors (suitable for Single Zebra Cond.) as per technical specifications 4 HDB Isolator with one ES 1250A 25kA 3s with structure and clamp connectors(suitable for Single Zebra Cond.) as per technical specifications 5 HDB Isolator without ES 1250A 25kA 3s with structure and clamp connectors (suitable for Single Zebra Cond.) as per technical specifications 6 HDB Isolator without ES 2000A 25kA 3s with structure and clamp connectors (suitable for Single Zebra Cond.) as per technical specifications 7 CT 600-300/1 3C, 31.5KA 3S with structure and clamp connectors (suitable for Single Zebra Cond.) as per technical specifications 8 SF6 CB 1600A 25kA 3S with structure and clamp connectors(suitable for Single Zebra Conductor) as per technical specification. B Supply and Erection of 66kV Materials considering 25mm/kV creepage distance (as per respective technical specifications and relevant special conditions) suitable for Single Main Bus scheme with Single Zebra conductor 1-a Gantry structures GI as per BOM , Steel & A/B part 1-b Gantry structures GI as per BOM , Bolt nut part 2-a LM structures GI as per BOM , Steel & A/B part 2-b LM structures GI as per BOM , Bolt nut part 3 Stringing of Main bus with Following Conductor for all the three phases with required Silicon Rubber Insulators, hardwares & accessories etc. complete as per relevant standards and approved drawings with Jumpers for continuous Bus Arrangement. 3.1-A Single Zebra Cond.- Main Bus with 18.0Mtr. Span (1 No. of Span) 3.1-B Break Up of Supply Items for Erection of above work Single Zebra Conductor Silicon Rubber Insulator string-120KN Double Tension H/W & Acc with Sag Plate.suitable for Single Zebra cond. & 120kN SRI Double Tension H/W & Acc without Sag Plate.suitable for Single Zebra cond. & 120kN SRI 3.2-A Single Zebra Cond.- Main Bus with 25.8Mtr. Span (1 No. of Span) 3.2-B Break Up of Supply Items for Erection of above work Single Zebra Conductor Silicon Rubber Insulator string-120KN Double Tension H/W & Acc with Sag Plate.suitable for Single Zebra cond. & 120kN SRI Double Tension H/W & Acc without Sag Plate.suitable for Single Zebra cond. & 120kN SRI 4 Droppers (including required suspension string with hardware & accessories if any) & Jumpers (including Equipment to Equipment) with Following conductor as per standards and approved drawings . (It includes cost of Conductor, Silicon Rubber Insulators,hardwares & accessories, Fire Wedge Connectors etc. all items for satisfactory functioning. Any variation in quantities shall be absorbed by erection contractor). 4.1-A Single Zebra Conductor 4.2-B Break Up of Supply Items for Erection of above work Single Zebra Conductor Fire Wedge Connectors suitable for Single Zebra Conductor to Single Zebra conductor C Supply and Erection of General purpose equipments and materials considering 25mm/kV creepage distance as per respective technical specifications and relevant special conditions. 1 66/11.55kV, 20 MVA Power Transformer with mineral oil, Conventional OIP Porcelain bushings, NIFPS and accessories as per Technical specification. Terminal connector shall be suitable for Single Zebra Cond. 2 Distribution Transformer 11kV/415V,63 kVA with suitable Dist. Box and its fixing -mounting. Required LT Distribution boxes with LT cable supply is in the scope of bidder. 3 Supply, Installation and Commissioning of Solar roof top System on Control Room Building with generation capacity of 10kW as per Technical specifications 4 Motor operated rack in - rack out Trolley system for 11kV VCB panel as per General Technical Requirements 5 Supply of Furniture, RO Water Filter System, Water Cooler Etc. as per Ann. D Supply of Steel Chair ’S’ type, overhanging arm with cushion with cane seat/ 1x16 gauge round pipe frame Supply of Steel Rack of size 36x30x12 (3’ x 2.5’x1) with three partitions, prepared with 20 gauges Supply of Steel Table of size 54x30x30 (4.5 x 2.5’ x 2.5) one side three drawers, one side shelf 1x18 gauge square pipe with Nova PAN Prelaminated top complete with locking arrangement to Supply of Computer Table from prelaminated board with Key board facility and drawer with locking facility with continuous printer out facility & mouse tray and also with special tray fo CPU & UPS Supply of Steel revolving Chair,‘revolving & tilting, low back high type seat with foam rubber 3 in seat 2.in back with good quality raxine cover ,five legs. Chromium plated frame. Supply of Steel Cupboard , of size 78x36x18 four partition, door & Shelves 20 gauge. Providing & Fixing of Aquaguard Toatal Reviva Water R.O. Plant including Commissioning & Testing and also with required peripherals for installation of plant as per site condition Display Boards and others Single line diagram drawn with radium paint on a board of approx size of 1200x900 mm with fixing arrangement on control room wall. Key board with hook for different keys of each equipments/panels/cubicles with SLD drawn with color approx size 2x2 6 Providing and Fixing of fire stand from 75mm GI pipe A class ISI mark heavy duty having 5ft width and 4ft height as per instruction of Engineer In Charge. work includes cutting, drilling, welding of pipe as required. Fabrication and supply of 16mm dia meter hook required size for 4 nos of buckets are to be provided fire stand should be grouted with excavation of pit size 300 mm x 300 mm - 02 nos. 600mm depth with 1:3:6 Mix Muffing 300 mm in height including levelling of stand. The fire stand is to be painted with post box with red colour of approval quality as per EIC. All required approved material including cement, sand, metal etc are to be provided by contractor The work is to be executed as per drawing No. CDR/E/06S/FIRE STAND/6695 - R1 Dated: 19.04.2017 7 Providing and fixing of various type of sign Board, sticker, Big Sign Board, earthing pit board, earthing pit Board & Single line diagram etc as per instruction of IEC. Sticker of red, white, black Letters are to be utilised for various sign board. - Earthing Pit Board Size:- 6“ x 6 -30 Nos. - Safety Slogan Board, Hard Sheet board size 2 x 2’and 4mm thick (Gujarati Language)- 2 Nos. - Safety Slogan Board, Hard Sheet board size 3’ x 2’and 4mm thick (Gujarati Language) with red and Yellow colour.-03 Nos. - Single line diagram size 5’ x 3 Digital with Aluminium frame with fitting and as per approved diagram given by IEC.-01 No. - Big sign board size 5 x 4’ and 2mm thickness indicating sub station name digital with S.S. rod with hole & as per approved symbol with fitting charge.- 01 No. - Switch yard sign Board 12 X 6 with 2 mm Thickness black & white Gujarati language.-25 Nos. - Safety Slogan Board size 2 x 6 in side control room.-05 Nos. - Various type of control room equipment sticker size-24 cms x 5cms.--18 Nos. - Safety picture board size:3 x 3’ (Laminated for O/D use)-03 - Name plate board of transformer size : 2’ x 1- 04 Nos. - Cable marker size:- 6 x 6, Radium, fixed on 750mm long M.S.Rod for fixing arrangement.- 30 Nos. Supply of ISI mark Rubber Matting sheet suitable for 11KV Class As per following specification. Reference IS:15652-2006 with latest amendment. Suitable for Voltage Class :B Max Use Voltage 11KVAC proof voltage 22KVDielectric strength 45KVLeakage current : < 10 micro ampereColur RED/BLUE Make : Vardhman or equivalent ( Rubber house India)Length -2 Mtr. Width :1 mtr.Thickness :2.5 mm.Surface :Chequered on one side and other side plain. NOTE: Contractor has to supply Rubber Matting sheet as per IS:15652-2006 with latest amendment specification and shall submit test certificate for routine test as per relevant IS Supply and installation of ISI marked fire extinguishers of various types required for 66 KV sub station. 1) Dry chemical powder type of 9 Kg. capacity. 2) Carbon dioxide ( CO2) gas type of capacity 6.5 Kg. capacity 3) Carbon dioxide (CO2) gas type of capacity 22.5 Kg. capacity 4) Mechanical Foam type of capacity 9 LT. 5) Mechanical Foam type of capacity 60 LT. Supply and installation of materials for Illumination system in all respect as per respective specifications and special conditions ( Successful bidder has to submit the complete design and BOQ for approval) Indoor Illumination Industrial Type Indoor Illumination of Control room building and Security cabin with respect to required lux level, relevant tender drgs and as per technical spec. Scope includes providing and fixing of Lighting Fixtures,15/5 A plug, Portable Emergency Light, Bell, Fan, Ex- Fan, DC Point,Switchborads, Occupancy & Light Level Sensor with requisite MCBs and DC 100W lamp , DC Plug etc. Safety device ELCB shall be provided as per technical requirement. Following drawings and Ann.4 shall be used for reference purpose: 1) TYPICAL FITTING LAYOUT OF STANDARD CONTROL ROOM ILLUMINATION FOR 66KV SUB-STATION - GETCO/ E/ Sh. 2 OF 2 6S-STD / S-015,Dtd. 01.02.2017 2) TYPICAL SCHEMATIC DIAGRAM FOR STANDARD CONTROL ROOM ILLUMINATION FOR 66KV SUB-STATION- GETCO/ E/ Sh.1 OF 2 6S-STD / S-015,Dtd. 01.02.2017 Note: The rates shall be inclusive of GI conduit,PVC insulated 660 V grade make copper wire of various size,clamps,cables and all the materials required for satisfactory functioning of below items as per Technical requirement and EIC instructions. Providing and Fixing separate point wiring in GI. Conduct pipe having IS Code & CM//L No & size of 20 mm dia and 1.6 mm wall thickness with single PVC insulated (3C x 2.5 Sqmm. copper wire of Avocab/Polycab/RR Kabel/Havells/L&T or equivalent standard make using (2+ 3 pin in socket Anchor brand or equivalent standard make 15 Amp. plug socket & switch as separate plug point with shock proof accessories incl. indication lamp.It shall be erected on powder coated M.S/Metal box separate decorative mat finish hylum sheet board on wall with providing adequate green earthing wire as per specification and instruction of Engineer In charge. Providing and Fixing separate point wiring in GI. Conduct pipe having IS Code & CM//L No & size of 20 mm dia and 1.6 mm wall thickness with single PVC insulated (3C x 1.5 Sqmm. copper wire of Avocab/Polycab/RR Kabel/Havells/L&T or equivalent standard make using (2+ 3 pin in socket Anchor brand or equivalent standard make 5 Amp. plug socket & switch as separate plug point with shock proof accessories incl. indication lamp. It shall be erected on powder coated M.S/Metal box separate decorative mat finish hylum sheet board on wall with providing adequate green earthing wire as per specification and instruction of Engineer In charge. Providing and Fixing of Ceiling Fan of 1400mm sweep Bajaj/Crompton / Orient/ usha or equivalent standard make (ISI approved). Providing and fixing of heavy duty exhaust fan- industrial type - 373 watt size 18of GEC/KHAITAN/ CROMPTON/ BAJAJ or equivalent standard make incl. M.S. lourex shutter of Fan & necessary wall finishing works and applying bird proof net on outside wall with required arrangement for rain water sealing and necessary connection from ceiling rose as per Direction and instruction of EIC. Providing and fixing of Exhaust fan- commercial type - 200 watt of GEC/KHAITAN/ CROMPTON/ BAJAJ or equivalent standard make incl. M.S. lourex shutter of Fan & necessary wall finishing works and applying bird proof net on outside wall with required arrangement for rain water sealing and necessary connection from ceiling rose as per Direction and instruction of EIC. DC Socket with MCB Portable Emergency Lighting Electric bell- 30 watt ix 3 ph.wtih neutral 15A test plug x Switchboards as per Technical requirement xi Providing and fixing of 50 Watt LED Lighting Fixture size 600mm x 600mm modular grid ceiling (CGL Cat No. LCTLRN-50-FO-CDL 50 W or equivalent. Make shall be of CGL/BAJAJ/PHILIPS/GE/OSHRAM or equivalent including supply & fixing of 3C x 1.5 sq.mm flexible cu cord of Polycab/Avocab/RR Kabel/L &T or equivalent standard make from point to the fixtures as per instruction of EIC. xii Providing and fixing of 41.5W LED Lighting Fixture (in battery room & store area)( CGL Cat No.LPFC-36-CDL 41.5W, or equivalent. Make shall be of CGL/BAJAJ/PHILIPS/GE/OSHRAM or equivalent including supply & fixing of 3C x 1.5 sq.mm flexible cu cord of Polycab/Avocab/RR Kabel/L &T or equivalent standard make from point to the fixtures as per instruction of EIC. xiii Providing and fixing of approved make 40 W LED Lighting fixtures as per drawing (in porch office area) ( CGL cat no. LCTAR3N-40-CDL(1x4) 40 W or equivalent. Make shall be of CGL/BAJAJ/PHILIPS/GE/OSHRAM or equivalent including supply & fixing of 3C x 1.5 sq.mm flexible cu cord of Polycab/Avocab/RR Kabel/L &T or equivalent standard make from point to the fixtures as per instruction of EIC. xiv INDUSTRIAL BULKHEAD LUMINAIRES FOR GLS CGL CAT NO.-IBH1110ES/BC (100 WATT) OR EQUIVALENT. xv RECESS MOUNTED DOWNLIGHT LUMINAIRES CGL CAT NO.DDLV10BC) (100 WATT-GLS) OR EQUIVALENT xvi RECESS MOUNTED DOWNLIGHT LUMINAIRES CGL CAT NO.DDLV10BC) (100 WATT-GLS) OR EQUIVALENT Outdoor Illumination 2 Outdoor Illumination with Philips/CGL/Bajaj/GE/Oshram make HPSV 150/250W lamp with energy efficient type choke (HF), control gear box & ancillaries and suitable for mounting on structure at appropriate height, Street Light and Post top lantern as per specifications TS illuminations cl. no 2.10.4.8 with necessary GI fabrication & GI bolt nuts to fix control gear box at the structure with complete internal and external wiring to J. box ,Dist panel/section feeder pillar etc. Following drawings and Ann.4 shall be used for reference purpose: 1) STANDARD OUTDOOR ILLUMINATION LAYOUT PLAN OF 66KV SUB-STATION - GETCO/ E 06S-STD / S-013,Sh. 2 of 3 Dtd. 01.02.2017 2) INSTALLATION & LOADING DETAILS FOR STANDARD OUTDOOR ILLUMINATION OF 66KV SUB-STATION - GETCO/ E 06S-STD / S-013,Sh. 3 of 3 Dtd. 01.02.2017 Note: The rates shall be inclusive of GI conduit,PVC insulated 660 V grade make copper wire of various size,clamps,cables and all the materials required for satisfactory functioning of below items as per Technical requirement and EIC instructions. i Providing and fixing of Single Piece Cast Aluminium with full frame with Acrylic Cover integrated luminaries Energy Efficient flood light luminaries on LM,Gantry structure or Control room building by providing required fabrications of Philips/CGL/Bajaj/GE/Osram or equivalent standard make, suitable for 1 x 250 Watt HPSV/T with allied accessories such as Capacitor igniter, ballast, control gear box etc, 4 core 2.5 sq mm double insulated flexible stranded wire should be used from control gear tilting to junction box. ii Providing & erection of swaged type welded GI tubular street light pole, by excavating as per inst. of E.I.C. in any type of soil confirming to relevant IS made of GI tubes of following size For Pole having Over all length 7.0 Mtr. Effective length of section. Bottom 4 Mtr. long, 114.3mm outer dia and 3.61mm thick, middle 1.50 mtr long, 88.9mm outer dia & 3.25mm thick, top 1.5M mtr long, 76.1 mm dia (outer) and 3.25mm thick with 1 Mtr long plus 240 x 240 x 16 mm thick GI Base plate welded to the pole as per attached Drawing No.GETCO/E/STD/LTG.POLE-R1 & Single arm fixed by fixing bolts (4 Nos) and cap as per specifications and to be so erected that Total tilting angle for the flood light luminaire provided on pole is considered as maximum of 45 degree,looking to the tilting angle 20 degree available with luminaire it self & supporting pipe should be fabricated & welded accordingly as per EIC iii Providing & erection of swaged type welded GI tubular street light pole, by excavating as per inst. of E.I.C. in any type of soil confirming to relevant IS made of GI tubes of following size for Pole having Over all length 4.5 Mtr. long, 60.3 mm outer dia and 3.5mm thick, plus 240 x 240 16 mm thick GI Base plate welded to the pole as per attached Drawing No.GETCO/E/STD/LTG.POLE-R1 & welded accordingly as per EIC iv Providing & fixing of Energy efficient LED Street Light Fixtures of Philips/CGL/Bajaj/GE/Oshram make (1 x 120W) (CGL Cat No-LSTN-120-CDL-A, IP66 PDC Street light 120 W or equivalent on control room / swage pole / GI structure by providing required fabrications & 4-core 2.5mm2 double insulated flexible stranded wire should be supplied by contractor & used from control gear fitting to approved SMC/FRP type junction box as per inst. of EIC. v Providing & fixing of of Philips/CGL/Bajaj/GE/Osram make 1 x 40W decorative LED Post Top Lantern fixtures for 360 Indirect light & IP65 protection. (CGL Cat No.-LPTO-40-CDL 40W or equivalent etc complete fitting in all respect and 4 core x 2.5 mm2 double insulated PVC flexible copper cable from control gear fitting to SMC junction box as per instruction of EIC. (02 nos are to be provided on Main gate & 6 No are to be provided on Tubular pole). 3 Supply and Erection of main lighting Panel ACP-1 as per Specifications. Set comprises minimum 2 nos.of such panels qty may be more if required as per design. Scope also includes the providing and erection of cable (size as per design requirement) and 25x6 GI strip for earthing with main mesh 4 Supply and Erection of main lighting Panel ACP-2 as per Specifications Set comprises minimum 1 nos.of such panels qty may be more if required as per design. Scope also includes the providing and erection of cable (size as per design requirement) and 25x6 GI strip for earthing with main mesh 5 Supply and Erection of main lighting Panel ACP-3 as per Specifications Set comprises minimum 1 nos.of such panels qty may be more if required as per design. Scope also includes the providing and erection of cable ( size as per design requirement) and 25x6 GI strip for earthing with main mesh 6 Supply and Erection of main lighting Panel ACP-4 as per Specifications Set comprises minimum 1 nos.of such panels qty may be more if required as per design. Scope also includes the providing and erection of cable (size as per design requirement) and 25x6 GI strip for earthing with main mesh 7 Supply and Erection of main Yard light Dist. Board as per specifications. Scope also includes the providing and erection of cable (size as per design requirement) and 50x6 GI strip for earthing with main mesh 8 Supply and Erection of DC Panel as per Specifications Set comprises minimum 1 nos.of such panels qty may be more if required as per design. Scope also includes the providing and erection of cable (size as per design requirement) and 25x6 GI strip for earthing with main mesh 9 Providing of concreting in 1:2:4 mix including muffing for erection of pole & Dist. boxes panels including excavation of HR/SR as per approved drawing. 10 Providing & fixing of B Class ISI marked GI pipe of 25 mm inner diameter for cable looping, road crossing with necessary elbow / band to J. Box etc. 11 Providing and fixing of GI clamp (25mm wide GI strip with 6 mm GI nut bolts) on structure at approx. 1/2 Mtr. Interval for clamping of cable . Clamp should be fix in such a way that cable can be easily mount inside it & sustain standing on structure. This also includes required other materials ,accessories required for complete functioning of Illumination system of whole project (switch yard and all buildings, structures) those are not covered in this schedule for Illumination. Please refer the drawing General Schematic for Illumination in the TS Illumination. E-1 Supply and installation of materials for Earthing system in all respect as per respective specifications and special conditions (Successful bidder has to submit the complete design and BOQ for approval) 1 Supply and Installation of earthing strips/round bars including digging of 600 mm depth and 450 mm wide trench, fixing on structure as per std equipment earthing philosophy including fixing arrangement with two bolt arrangement, jointing, welding etc. complete. for below items: a) 75 x 10 mm GI strip. b) 50 x 6 mm GI strip. c) 40 mm dia steel rod d) 40mm dia 3mtr long steel rod 2 Providing and installing Check pit as per drawing and instruction of Engineer In charge with provision of earth chamber. 3 Supply, Installation, Testing and Commissioning of maintenance free treated earth electrodes, as per attached drawing no. GETCO/E/P-021 (1 OF 2) R3 dated 29.05.2020 and Technical specifications GETCO/E/TS-Maintenance free earth pits /R1 dated 04-06-15. 4 Providing BB masonry inspection chamber (man hole) incl.light type CI cover as per GETCO drawing. Note: The quantities of the ACPs mentioned in the schedule of requirement are based on std. shall be finalised during detail engineering. The bidder has to assess the qty. of ACPs at the The qty of ACPs finalised during detail engineering is binding to the bidder & no any extra all the case the decision of GETCO will be final. E-2 Supply and installation of materials for Lightning Protection in all respect as per respective specifications and special conditions. a) 7/3.15 earth wire for earthing of towers with peak. The scope includes fixing of clamps,bolts,connectors, test link etc. as per requirement. b) Supply and erection of 50x6 mm GI flat for control room DSLP protection. The work is to be carried out as per drawing No. GETCO/E/STD/DSPL-66KV CR- R0 Dtd 26.10.2017. The scope includes fixing of clamps,bolts,connectors, test link etc. as per requirement. c) Providing & Fixing of M.S 1.5Mtr long 16MM dia lightning Rod (Spike) for lightning protection of control room building as per drawing No. GETCO/E/STD/DSPL-66KV CR- R0 Dtd 26.10.2017 and on Lighting Mast.The scope includes fixing of clamps,bolts,connectors, test link etc. as per requirement. F Supply and Erection of 11kV Switchyard Materials considering 25mm/kV creepage distance (as per respective technical specifications and relevant special conditions). 1 11kV, 3 Nos. of 1600A Incomer VCB Panels + 12 Nos. of 1250A Feeder VCB Panels along with 2 Nos. of 1600A Bus Coupler VCB Panel as per TS. Outsider Panels (Total 2 Nos.) shall be with Integrated adapter cubicle. One Indoor and one outdoor cable termination kit for each feeder panel suitable for 185Sq. mm. XLPE cable and Three indoor & three outdoor termination kit suitable for 300 Sq. mm XLPE cable for Incomer Panel shall be provided. 2 Supply, Laying & installation of 1RX3CX300 SQMM 11kV XLPE cable in 11kV Power Cable trench with all required materials like circuit identification tag, joints, termination kits, clamps & connectors to connect with conductor etc. It also includes supervision, testing, installation,pre-commissioning tests etc. are in the scope of bidder. 3 Supply, Laying & installation of 1RX3CX185 SQMM 11kV XLPE cable in 11kV Power Cable trench with all required materials like circuit identification tag, joints, termination kits,clamps & connectors to connect with conductor etc. It also includes supervision, testing, installation,pre-commissioning tests etc. are in the scope of bidder. 4 Supply, Laying & installation of 1RX3CX185 SQMM 11kV XLPE cable buried in open space with all required materials like circuit identification tag, joints, termination kits,clamps & connectors to connect with conductor, Associated civil works in any type of soil etc. It also includes supervision, testing, installation,pre-commissioning tests etc. are in the scope of bidder. 5 Support structure of Set of following Items for 11 KV Power cable termination at 11 KV Bushing for 15 MVA / 20 MVA power transformer as per Drawing No: GETCO/E/06S-STD/11 KV STR- A2-02, R0, Dt-05.06.2015. Necessary wooden clamps as per drawing with required nut-bolt-washers HDPE rubber piece for packing etc shall be supplied by contractor. Job also includes : 1) Allu. alloy bus bar of size 75X20x2000 mm : 03 Nos. 2) 11KV Post Insulator of PCD 127 mm - 12 No 3) Copper laminated fusion welded flexible jumper of size 75 X 10 X 600 mm having 2000 Amp capacity : 03 No 4) 11KV Heat shrinkable anti tracking sleeve on Aluminium Bus Bar of all three phase - 06 mtrs 5) Including required GI nut bolts and washer of good quality for fitting support structure. 6) All live part shall be covered with Heat shrinkable MV insulated tape/sleeve. 7) Heavy duty PVC clamps. 6 11KV D.P. Structure as per Drawing No- GETCO/E/06S-STD/11KV STR-A1-01 ( including fixing of 11KV AB Switches ,11KV Pin Insulators,9kVC LA,DO Fuse etc. and jumpering from 11kv cable to AB switch & AB switch to 11KV Bus between DP structure and cross boundary. 7 11KV D.P. Structure as per Drawing No- GETCO/E/06S-STD/11KV STR-A4-04 ( including fixing of 11KV AB Switches ,11KV Pin Insulators,9kVC LA,DO Fuse etc. and jumpering from 11kv cable to AB switch & AB switch to 11KV Bus between DP structure and cross boundary. 8 Radium sticker for outdoor and indoor equipment identification like LA,Isolator,Circuit Breaker,Transformer,CT,PT ,MK box,C&R Panel,11KV panel board etc. 9 Supply and installation of 11 KV outdoor termination kits alongwith 11kV Power cable laying for connection to 11kV DPs, 63 KVA distribution transformer & 66/11 KV power transformers. 11 KV XLPE cable laying shall be as per GETCO philosophy. 10 Support structure for Station Xmer as per Drawing No- GETCO/E/06S-STD/11KV STR-A3-03.Job also includes erection of required 11kv LA and DO. Fuse and minor fabrication if required as per inst. Of EIC. Enhancement Material, gravel, bricks etc. to be supplied by the contractor. Stringing of Single ACSR DOG Bus between 11KV DP structure to cross boundary structure in all respect with fixing of all fitting and accessories with supply of Single tension hardware suitable for ACSR DOG conductor. NOTES: Supply, Erection, Testing and Commissioning of Protection equipments and materials as per respective technical specifications and relevant special conditions and suitable for One Main Bus system on 66kV side Control & Relay Panels for 66kV bays (Control Voltage - 110V DC) as per tech specifications with LED type Semaphore and Digital MFMs instead of analogue meters with following break up. 1) Control & Relay Panel for 66kV lines 2) Control & Relay Panel for Transformer With Differerential Relay (For 66/11kV TR) 3) Control & Relay Panel for Transformer W/O Differerential Relay (For 132/66kV TR) 4) Control & Relay Panel for BC 5) Control & Relay Panel for Capacitor Bank 6) Under Frequency Panel** Supply, Erection, Testing and Commissioning of General purpose equipments and materials as per respective technical specifications and relevant special conditions and suitable for One Main Bus system on 66kV and One Main Bus on 11kV. Battery set - 110 V, 100Ah Tubluar Lead Acid Battery Set with stand Battery Charger - 110 V (Float - 10A / Boost - 20A) DCDB-110 V with 35 Feeder DCDB-110 V with 20 Feeder LTPB Supply, Installation, Testing and Commissioning of materials/item for Power Cable and Control Cable wiring including preparation of wiring schedule. Supply and Laying of 1.1 kV PVC armoured copper/Aluminum control/LT power cable in trench including binding/clamping of cable with PVC locable wire tie as per requirement including supply and fixing of identification tags on both ends and at distance of every 100mtr. (Note :- Aluminium cables of size 185 mm2 & above shall be XLPE type)# 450 2) 2c x 4 mm2 , copper control cable 3) 4cx2.5 mm2, copper control cable 4) 4c x 4 mm2 , copper control cable 5) 7c x 2.5 mm2, copper control cable 6) 12c x 2.5 mm2, copper control cable 7) 12c x 4 mm2, copper control cable 8) 19c x 2.5 mm2 , copper control cable 9) 27c x 2.5 mm2 , copper control cable 10A) 1 x 25 mm2 , copper cable 10B) 4C x 10 mm2 , copper control cable 11) 4 x 10 mm2 , Al. armoured LT cable 12) 3.5 x 25 mm2 , Al. armoured LT cable 13) 3.5 x 50 mm2 , Al. armoured LT cable 14) 3.5 x 120 mm2 , Al. armoured LT cable 15) 1C x 150 mm2 , Al. armoured LT cable 16) 1C x 240 mm2 , Al. armoured LT cable 17) 1C x 300 mm2 , Al. armoured LT cable 18) 3.5 x 300 mm2 , Al. armoured LT cable Termination of the control cable at panel / MK box/equipment including PVC binding dressing/shaping drilling of holes in panels for glands nuts for following size. The work also includes Looping in panel and MK box with using crimping type of lugs of suitable size with ferruling with proper size of copper cable wire. The loops should be bunched with using button tape and proper shaping etc. 1) cables from 2 core to 7 core of 2.5 & 4.0 Sq.mm size 2) cables above 7 core All work is to be carried out strictly as per the manual of OEM (Original equipment manufacturer), FQP All the items shall be supplied from GETCO approved vendor. Minor items shall be got approved from circle office on the basis of past approval and its performance. All the cables and wires required for indoor and outdoor illumination starting from LTPB to Lighting illumination package. Size of the same shall be decided as per Technical requirement. PROTECTION BOQ for 66kV Kotarpur Sub-Station DSLP for Control room building etc. shall be as per IEC 62305 / IS 2309 Normal soil is considered for Earthing of Switchyard. Grid spacing of 4X4 Mtr. is considered for 3 Laying of 1.1kv PVC/XLPE armored Al. LT power cable in ground by digging trench of suitable width and 450 mm depth with providing and fixing of brick and sand layer covering the cable in any type of soil and Laying of 1.1kv PVC armored copper control cable in heavy duty PVC pipe of suitable size buried in ground by digging trench of suitable width and 450 mm depth in any type of soil including supply and fixing of Pipe and identification tags at distance of every 100 Mtrs for following size 1) Control Cables upto 7 core 2) Control Cables above 7 core and all LT cables 3a Supply, Erection, Testing and Commissioning of Modular Variable-diameter Cable sealing system as per respective technical specification and relevant special conditions wherever the electrical / instrumentation / communication / LT Power cable underground and over-ground enter or leave bay control room of substations / cable trench / basement. Providing and fixing of suitable BOX type GI perforated tray with necessary clamps and couplings for control cable of CT/PT/CVT etc. equipments including fixing with structures up to plinth level as per instruction of Engineer-in-charge. 1) 220 kV Switch Yard 2) 132 kV switch yard 3) 66 kV switch yard Providing and fixing of suitable BOX type GI perforated tray with necessary clamps and couplings for control cable of CB, Isolator, Earth Switch etc. equipments including fixing with structures up to plinth level as per instruction of Engineer-in-charge. 1) 220 KV Switch Yard 2) 132 KV Switch Yard 3) 66 KV switch Yard 5 Providing and fixing bay MK as per tech spec 6 Providing and fixing Yard LT ACDB as per tech spec -with 20 OG feeders 7 Providing and fixing Yard LT ACDB as per tech spec -with 12 OG feeders 8 Providing and fixing of CT-PT/CVT JB as per Technical specification 1) PT JB 2) CT JB 3) CVT JB 4 4a
|